Pacific Energy NEO 1.2 EU A SERIES Owners Manu - Floor Protector
Installation Instructions
Floor Protector
The stove may be installed on a combustible floor provided noncombustible ember protection is used.
This protection must extend as follows:
UK: The Hearth Protection must be 12mm thick and protrude at least 305mm in front of the unit. See Figure 9, below.
Chimney and Connector
Connect to a listed chimney or a chimney suitable for use with solid fuel that is lined and in good condition and
meets local building codes. The chimney flue size should be the same as the stove outlet for optimal performance.
Reducing or increasing the flue size may adversely affect stove performance. The Chimney flue exit must meet chimney
manufacturer's specifications. The installation must meet all local and National codes. Do not connect this unit to a
chimney flue serving another appliance.
Minimum system height is 4.6 m. (measured from base of appliance).
The Chimney System must be:
• secured at every joint and collar with 3 sheet metal screws.
• installed with the crimped or male ends pointing down. This will carry any liquid creosote or condensation back into
the stove.
• Installed according to the chimney/chimney pipe manufacturer's installation and safety guidelines
Installation Procedure
1. Install all components to the chimney manufacturer's installation requirements. (Outside combustion air may be
required, consult local building codes. See "Combustion Air" on page 17)
2. If it is desirable to use smoke pipe in conjunction with the insulated chimney, see step 4.
3. If a roof or ceiling support is used in the installation, you will find the chimney manufacturer's complete instructions
packed with the roof support.
4. To start installing smoke pipe (chimney connector), slip crimped edge of the pipe inside the stove collar. Use holes
provided in collar to secure pipe with three screws.
5. Install the remaining lengths of pipe one on top of the other to the finished height of the chimney connector and
secure to each other.
Minimum Width - 1.08m
Minimum Overall Depth - 900m
Non-combustible
floor protector
200mm
305mm
200mm
200mm
Figure 9: NEO 1.2 Floor protector EU
16
120416-24_ NEO 1.2
5055.600EU-A