Warning: Under no circumstances is this heater to be installed
in a makeshift or "temporary" manner. It may be fi red only
after the following conditions have been met.
* DO NOT ATTEMPT TO CONNECT THIS HEATER TO
ANY AIR DISTRIBUTION DUCT.
*
Do not connect this unit to a chimney fl ue serving another
appliance.
* Outside combustion air or fresh air into the room may be
required in your area, consult local building codes (see
Combustion Air section).
- The services of a competent or certifi ed installer, (certifi ed
by the Wood Energy Technical Training program (WETT) - in
Canada,or the Hearth Education Foundation (HEARTH) - in
U.S.A.,) are strongly recommended.
BOTH CHIMNEY SYSTEM AND CONNECTOR MUST BE
6"(150mm) DIAMETER AND LISTED TO: IN CANADA -
IN CANADA -
ULC S-641 LISTED CONNECTOR AND ULC-S-629 LISTED
ULC S-641 LISTED CONNECTOR AND ULC-S-629 LISTED
CHIMNEY, IN USA - UL-103 HT LISTED CONNECTOR
CHIMNEY, IN USA - UL-103 HT LISTED CONNECTOR
AND CHIMNEY
AND CHIMNEY
Clearances
1. This heater may be installed using a single-wall connector
(smoke pipe) or listed double-wall connector (see Mobile
Home installation).
2. Clearances to combustible surfaces and materials using
single-wall connector are shown in Figure #7, page 12.
Clearances may be reduced with various heat insulating
materials. Consult local fi re codes and authorities for ap-
proval.
3. Alternately, for close clearances, use a listed double-wall
connector. See Fig #7 page 12.
It is possible to store wood between the stove supports, un-
derneath the unit but not recommended. The wood must not
extend further forward than fl ush with the supports.
NOTE: Refer to local fi re codes, CAN-B365 in Canada and
NFPA 211 in the U.S..
Chimney and Connector
Connect to a listed chimney or a chimney suitable for use
with solid fuel that is lined and in good condition. Chimney
fl ue exit is to be 3 feet (1 m.) above roof and two feet (0.6 m.)
above highest projection within 10 feet (3 m.). The installation
must meet all local codes. Minimum system height is 15 feet
(4.6 m.) (measured from base of appliance).
* The chimney connector should not pass through an at-
tic, roof space, closet or similar concealed space, fl oor,
or ceiling. Where passage through a wall, or partition
of combustible material is desired, the installation shall
conform to CAN/CSA-B365, Installation Code for Solid-
Fuel-Burning Appliances and Equipment in Canada or
NFPA 211: Standard for Chimneys, Fireplaces, Vents, and
Solid Fuel-Burning Appliances in the U.S.A..
Double-Wall Connector
-
Use a listed double-wall connector.(listed to ULC S641)
-
Install all components to the chimney connector manu-
facturer's installation requirements.
Single-Wall Connector(smoke pipe)
Smoke pipe must be:
* as short and straight as possible, use six inch
diameter, 24GA or thicker black pipe that is clean and in
new condition.
* secured at every joint and collar with 3 sheet metal screws.
* installed with the crimped or male ends pointing down.
This will carry any liquid creosote or condensation back
into the stove.
Procedure
1. If a listed chimney and double-wall connector is to be con-
nected to the stove, install all components to the chimney
manufacturer's installation requirements.
2. If a roof or ceiling support is used in the installation, you
will fi nd the chimney manufacturer's complete instructions
packed with the roof support.
3. If it is desirable to use smoke pipe in conjunction with the
insulated chimney, see step 4.
4. To start installing smoke pipe (chimney connector), slip
crimped edge of the pipe inside the stove collar. Use
holes provided in collar to secure pipe with three screws.
5. Install the remaining lengths of pipe one on top of the
other to the fi nished height of the chimney connector up
to the start of the chimney and secure to each other.
(Outside combustion air may be required, consult local
building codes. See Combustion Air section on page 10.)
NOTE: Longer chimney lengths and different pitch fl ashings
may be used. All other parts installed must be listed(see
Figure #8, Page 13). Install all components to the connector
and chimney manufacturer's installation requirements. Con-
sult your chimney supplier for additional installation advice.
Residential Installation