Pacific Energy NEO 1.6 NEOSTONE Installation And Operating Instructions Manual - Mobile Home
050515-24
15
©PACIFIC ENERGY FIREPLACE
PRODUCTS LTD.
15"
381mm
21 1/2"
549mm
8"
203mm
11"
279mm
5"
127mm
3"
76mm
3"
76mm
Mobile Home
Minimum
Clearance to
Combustibles
Additional Requirements
Warning: Under no circumstances is this heater to be installed
in a makeshift or "temporary" manner. It may be fi red only
after the following conditions have been met.
- DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE
SERVING ANOTHER APPLIANCE.
- DO NOT INSTALL IN A SLEEPING ROOM.
- BOTH CHIMNEY SYSTEM AND CONNECTOR MUST BE
6"(150mm) DIAMETER AND LISTED TO: IN CANADA -
IN CANADA -
ULC S-641 LISTED CONNECTOR AND ULC-S-629 LISTED
ULC S-641 LISTED CONNECTOR AND ULC-S-629 LISTED
CHIMNEY,
CHIMNEY,
IN USA - UL-103 HT LISTED CONNECTOR
IN USA - UL-103 HT LISTED CONNECTOR
AND CHIMNEY
AND CHIMNEY
- Outside air supply must be used for Mobile Home installa-
tions see Figure #8, Page 13.
- Remove the chimney down to the roof fl ashing to allow for
transportation of the mobile home.
Double Wall Connector - Mobile Home
Clearances
This heater must be installed with a listed double-wall connector
and compatible chimney system.
Clearances to combustible surfaces and materials are shown
in Figure #10.
Clearances may be reduced with various heat insulating
materials. Consult local fi re codes and authorities for approval.
NOTE: Longer chimney lengths and different pitch fl ashings
may be used. All other parts listed must be installed (see
Figure #8, Page 13). Install all components to the connector
or chimney manufacturer's installation requirements. Consult
your chimney supplier for installation advice.
FIG. #10
Mobile Home Installation
Procedure:
CAUTION: THE STRUCTURAL INTEGRITY OF THE MOBILE
HOME FLOOR, WALL AND CEILING/ROOF MUST BE
MAINTAINED.
- The services of a competent or certifi ed installer, (certifi ed
by the Wood Energy Technical Training program (WETT) - in
Canada, Hearth Education Foundation (HEARTH) - in U.S.A.,)
are strongly recommended.
Note: See "Combustion Air" section on page 10.
1. Position stove and fl oor protection with hole for combustion
air in accordance with the clearances as stated on the
label and in Figure #10.
2. Mark the position for the hole in the ceiling and roof by
using a string and plumb-bob.
3. Check that the intended location will not interfere with fl oor
joists, ceiling joists or rafters before proceeding further.
4. Cut a hole in the ceiling and roof to suit the chimney
system and frame in the sides. The chimney support is
mounted to the framing.
5. If the chimney connector exits the mobile home less then
7 feet(2.1m) above the ground then a guard must be
installed to cover the connector up to a height of 7(2.1m)
feet.
6. The guard must not have opening larger than 3/8"(10mm)
and must maintain a space of 4"(100mm) minimum around
the chimney
connector.
7. Assemble chimney sections so the fi nished length is resting
on the support and protruding through the roof. Avoid
having joints between ceiling and roof. Install radiation
shield. Assemble fl ashing and storm collar and be sure to
maintain the vapour barrier at this point. (Seal securely.)
Attach rain cap and check fl ashing for leaks.
8. Install connector as per manufacturer's instructions.
9. Attach stove to fl ooring using two 1/4" x 2" or longer lag
screws.