Panasonic CS-25DM1HPK Installation Manual - page 17
English
16
(2)
Turn the MAIN/SUB changeover switch on one of the
two remote controller PC boards to “S”.
(Leave the switch of the other remote controller set to
“M”.)
9-5 COMPUTERISED CONTROL (FORCED OFF AND ON/OFF OPERATION)
(1)
Wire specifications and how to perform wiring
•
Connect input from outside to terminals T1 and T2 of the terminal board (remote controller to transmis-
sion wiring).
(2)
Actuation
•
The following table explains FORCED OFF and ON/OFF OPERATIONS in response to Input A.
(3)
How to select FORCED OFF and ON/OFF OPERATION
•
Turn the power on and then use the remote
controller to selet operation.
•
Set the remote controller to the field set mode.
For details, refer to the “HOW TO SET IN THE
FIELD”, in the remote controller manual.
•
When in the field set mode, select mode No. 12,
then set the first code (switch) No. to “1”. Then
set second code (position) No. to “01” for
FORCED OFF and “02” for ON/OFF
OPERATION. (FORCED OFF at factory set)
9-6 CENTRALIZED CONTROL
•
For centralized control, it is necessary to designate the group No. For details, refer to the manual of each
optional controllers for centralized control.
Wire specification
Sheathed vinyl cord or cable (2 wire)
Gauge
0.75 - 1.25 mm
2
Length
Max. 100 m
External terminal
Contact that can ensure the minimum applicable load of 15 V
DC, 10 mA.
FORCED OFF
ON/OFF OPERATION
Input “ON” stops operation (impossible by remote controllers).
Input “OFF”
→
“ON” turns ON unit.
Input “OFF” enables control by remote controller.
Input “ON”
→
“OFF” turns OFF unit.
S
M
S
S
M
Remote controller
PC board
(Factory setting)
Only one remote controller
needs to be changed if
factory settings have
remained untouched.
F2
T1
T2
FORCED
OFF
Input A
SETTING
Mode No.
SECOND
CODE NO.
FIRST CODE
NO.
FIELD SET
MODE