Panasonic CS-25DM1HPK Installation Manual - page 8
7
English
6. REFRIGERANT PIPING WORK
〈〈〈〈
For refrigerant piping of outdoor units, see the installation manual attached to the outdoor unit.
〉 〉 〉 〉
〈〈〈〈
Be sure to thermally insulate both the gas pipes and fluid pipes. Water leakage may result if the pipes
are not insulated. (Only use insulation resistant to at least 120 °C.)
Furthermore, if the temperature/humidity in the refrigerant piping are expected to exceed 30 °C or
80% RH, the thermal insulation of the refrigerant pipes should be strengthened (to be a thickness of
20 mm or more). There may be some condensation on the surface of the insulation material.
〉 〉 〉 〉
〈〈〈〈
Before rigging tubes, check which type of refrigerant is used. Proper operation is not possible if the
types of refrigerant are not the same.
〉〉〉〉
6-1 CAUTION
• Use a pipe cutter and flare suitable for the type of refrigerant.
• Apply ester oil or ether oil around the flare portions before connecting.
• To prevent dust, moisture or other foreign matter from infiltrating the tube, either pinch the end or
cover it with tape.
•
The outdoor unit is charged with refrigerant.
•
Be sure to use both a spanner and torque wrench together, as shown in the drawing, when connecting or
disconnecting pipes to/from the unit.
•
Refer to the Table 2 for flare measurements.
•
When connecting the flare nut, coat the flare both inside and outside with refrigerating machine oil and ini-
tially tighten by hand 3 or 4 turns before tightening firmly.
•
Refer to the Table 2 for tightening torque.
Overtightening may damage the flare.
•
Check the pipe connector for gas leaks, then insulate it as shown in the drawing.
•
Wrap only the gas line side with the sealing pad. Bend the pad over the insulation for fitting (union) from above.
CAUTION
Overtightening may damage the flare and cause leaks.
Use “ Tabel 3 ” as a reference if a torque wrench is not available. Once work is complete, make sure there is
no gas leaking. As the flare nut is tightened with the wrench, the torque will suddenly increase. From that posi-
tion, tighten the nut to the angle shown on “ Tabel 3 ”.
•
Make absolutely sure to execute heat insulation works on the pipe-connecting section after checking gas
leakage by thoroughly studying the following figure and using the attached heat insulating materials for
fitting (6) and (7). (Fasten both ends with the clamps (4) (attached).)
•
Wrap the sealing pad (9) (attached) only around the insulation for the joints on the gas piping side.
CAUTION
Be sure to insulate any field piping all the way to the piping connection inside the unit. Any exposed piping
may cause condensation or burns if touched.
•
When brazing the refrigerant piping, only begin brazing after having carried out nitrogen substitution
(NOTE 1) or while inserting nitrogen into the refrigerant piping (NOTE 2). Once this is done, connect the
indoor unit with a flared or a flanged connection.
NOTES
1.
Refer to the “Manual for Multi Installation for Buildings” for directions on how to carry out nitrogen substi-
tution. (Inquire with your dealer.)
Coated with ester oil
or ether oil.
Torque wrench
Flare nut
Piping union
Spanner
Small sealing pad
(attached)
Gas pipe
Liquid pipe
Insulation
for fitting
(attached)
Clamp
(× 6 attached)