Panasonic CS-A120TE Service Manual - Functions
– 2 –
CS-A120TE
Anti-freezing Control For The
Evaporator
●
Compressor will be stopped when the
Evaporator’s piping temperature is 0°C or
less for three minutes
●
Restarting at 12°C or higher (Time Delay
Safety Control has a priority)
Airflow Direction Control
Automatic Airflow Direction Control
●
The louver automatically swings up and down
(Cooling, Soft Dry)…horizontal and 30°
downward
●
The louver is set at 60° downward during
Heating Operation
●
The louver is set at horizontal when the fan is
stopped
Airflow Direction Manual Control
●
Can be set within a range at horizontal to 60°
downward
Hot-start Control (Heating)
●
The indoor fan stops until the Evaporator
piping temperature will be reached.
Automatic Restarting Control
●
7 minutes automatic restarting at Cooling,
Soft Dry operation
Sleep Mode Auto Control
●
The Fan is switched to Low fan speed and the
unit will be stopped after 5 hours
●
The setting temperature will be raised by 1°C
at the starting and by 1°C one hour later (Soft
Dry of Cooling Operation)
●
The setting temperature will be dropped by
2°C at the starting and by 3°C one hour later
(Heating operation).
Deice (defrost) Control
●
Both the indoor and outdoor fan stops during
deicing
●
Hot start after deice ends
●
Starts operation when indoor piping
temperature drops below temperature setting
60 ± 10 minutes after heating start or deice
ends
●
Operations LED flashes.
Overload Protection
●
Thermostat OFF if the Piping temperature
exceeds 100°C
Automatic Operation Determination
●
Selects cooling, dry or heating with the indoor
intake sensor
25°C or higher ..... cooling
21 to 24°C ........... dry
20°C or lower ...... heating
●
5-minutes automatic restarting is activated
instead of 7-minutes
Functions
Outdoor Unit
Overload Protection
30sec. Forced Operation Control
●
Once the compressor is activated it does not
stop for 30 secs
●
Stops immediately with remote control stop
Untitled-9
6/19/00, 6:35 PM
2