- DL manuals
- Panasonic
- Air Conditioner
- CS-CE12JKE
- Service Manual
Panasonic CS-CE12JKE Service Manual - page 30
30
4. Close the Low side valve of the charging set and turn off the vacuum pump. Make sure that the needle in the gauge does not
move after approximately five minutes.
Note: BE SURE TO TAKE THIS PROCEDURE IN ORDER TO AVOID REFRIGERANT GAS LEAKAGE.
5. Disconnect the charging hose from the vacuum pump and from the service port of the 3-way valve.
6. Tighten the service port caps of the 3-way valve at a torque of 18 N
•
m with a torque wrench.
7. Remove the valve caps of both of the 2-way valve and 3-way valve. Position both of the valves to “OPEN” using a hexagonal
wrench (4 mm).
8. Mount valve caps onto the 2-way valve and the 3-way valve.
• Be sure to check for gas leakage.
11.3.4. Connect the Cable to the Outdoor Unit
1. Remove the control board cover from the unit by
loosening the screw.
2. Cable connection to the power supply through Isolating
Devices (Disconnecting means).
• Connect approved type polychloroprene sheathed
power supply cord
3 x 1.5 mm
2
(1.0 ~ 1.5HP) type
designation 245 IEC 57 or heavier cord to the terminal
board, and connect the others end of the cord to
Isolating Devices (Disconnecting means).
3.
Connecting cable
between indoor unit and outdoor unit
shall be approved polychloroprene sheathed 4 x 1.5 mm
2
flexible cord, type designation 245 IEC 57 or heavier
cord.
4. Connect the power supply cord and connecting cable
between indoor unit and outdoor unit according to the
diagram below.
5. Secure the power supply cord and connecting cable onto the control board with the holder.
6. Attach the control board cover back to the original position with screw.
7. For wire stripping and connection requirement, refer to instruction of indoor unit.
This equipment must be properly earthed.
• Note: Isolating Devices (Disconnecting means) should have minimum 3.0 mm contact gap.
• Earth wire shall be Yellow/Green (Y/G) in colour and longer than other AC wires for safety reason.
11.3.5. Pipe Insulation
1. Please carry out insulation at pipe connection portion as mentioned in Indoor/Outdoor Unit Installation Diagram. Please wrap
the insulated piping end to prevent water from going inside the piping.
2. If drain hose or connecting piping is in the room (where dew may form), please increase the insulation by using POLY-E
FOAM with thickness 6mm or above.
• If gauge needle does not move from 0 cmHg (0 MPa) to -76 cmHg (-0.1 MPa), in step above take the following measure:
- If the leak stops when the piping connections are tightened further, continue working from step .
- If the leak does not stop when the connections are retightened, repair the location of leak.
- Do not release refrigerant during piping work for installation and reinstallation.
- Take care of the liquid refrigerant, it may cause frostbite.
Summary of CS-CE12JKE
Page 1
© panasonic ha air-conditioning (m) sdn. Bhd. 2010. Unauthorized copying and distribution is a violation of law. Order no. Phaam1007138c2 air conditioner indoor unit outdoor unit cs-ce9lke cu-ce9lke cs-ce12lke cu-ce12lke table of contents page page 1 safety precautions ------------------------------...
Page 2
2 12.7. Indication panel------------------------------------------- 34 13 protection control ---------------------------------------------- 35 13.1. Protection control for all operations--------------- 35 13.2. Protection control for cooling & soft dry operation--------------------------------------...
Page 3: 1 Safety Precautions
3 1 safety precautions • read the following “safety precautions” carefully before perform any servicing. • electrical work must be installed or serviced by a licensed electrician. Be sure to use the correct rating of the power plug and main circuit for the model installed. • the caution items stated...
Page 4
4 18. For r410a models, when connecting the piping, do not use any existing (r22) pipes and flare nuts. Using such same may cause abnormally high pressure in the refrigeration cycle (piping), and possibly result in explosion and injury. Use only r410a materials. Thickness of copper pipes used with r...
Page 5: 2 Specifications
5 2 specifications model indoor cs-ce9lke outdoor cu-ce9lke performance test condition eurovent power supply phase, hz single, 50 v 230 min. Mid. Max. Cooling capacity kw 0.60 2.50 3.00 btu/h — — — kcal/h 520 2150 2580 running current a — 2.6 — input power w 125 545 750 annual consumption kwh — 273 ...
Page 6
6 out d oor f an type propeller fan material pp motor type dc type (8-poles) input power w — output power w 40 speed hi cool rpm 800 heat rpm 790 moisture removal l/h (pt/h) 1.5 (3.2) indoor airflow lo cool/fan m 3 /min (ft 3 /min) 5.4 (190) heat m 3 /min (ft 3 /min) 6.4 (230) me cool/fan m 3 /min (...
Page 7
7 1. Cooling capacities are based on indoor temperature of 27 ° c dry bulb (80.6 ° f dry bulb), 19.0 ° c wet bulb (66.2 ° f wet bulb) and outdoor air temperature of 35 ° c dry bulb (95 ° f dry bulb), 24 ° c wet bulb (75.2 ° f wet bulb) 2. Heating capacities are based on indoor temperature of 20 ° c ...
Page 8
8 model indoor cs-ce12lke outdoor cu-ce12lke performance test condition eurovent power supply phase, hz single, 50 v 230 min. Mid. Max. Cooling capacity kw 0.60 3.50 4.00 btu/h — — — kcal/h 520 3010 3440 running current a — 4.5 — input power w 125 950 1.18k annual consumption kwh — 475 — eer w/w 4.8...
Page 9
9 out d oor f an type propeller fan material pp motor type dc type (8-poles) input power w — output power w 40 speed hi cool rpm 840 heat rpm 820 moisture removal l/h (pt/h) 2.0 (4.2) indoor airflow lo cool/fan m 3 /min (ft 3 /min) 6.3 (220) heat m 3 /min (ft 3 /min) 9.4 (332) me cool/fan m 3 /min (...
Page 10
10 1. Cooling capacities are based on indoor temperature of 27 ° c dry bulb (80.6 ° f dry bulb), 19.0 ° c wet bulb (66.2 ° f wet bulb) and outdoor air temperature of 35 ° c dry bulb (95 ° f dry bulb), 24 ° c wet bulb (75.2 ° f wet bulb) 2. Heating capacities are based on indoor temperature of 20 ° c...
Page 11: 3 Features
11 3 features • inverter technology - wider output power range - energy saving - more precise temperature control • environment protection - non-ozone depletion substances refrigerant (r410a) • long installation piping - long piping up to 15 meters during single split connection only • easy to use r...
Page 12
12 4 location of controls and components 4.1. Indoor unit 4.2. Outdoor unit 4.3. Remote control.
Page 13: 5 Dimensions
13 5 dimensions 5.1. Indoor unit.
Page 14
14 5.2. Outdoor unit.
Page 15
15 6 refrigeration cycle diagram.
Page 16: 7 Block Diagram
16 7 block diagram.
Page 17: 8 Wiring Connection Diagram
17 8 wiring connection diagram 8.1. Indoor unit.
Page 18
18 8.2. Outdoor unit.
Page 19
19 9 electronic circuit diagram 9.1. Indoor unit.
Page 20
20 9.2. Outdoor unit.
Page 21: 10 Printed Circuit Board
21 10 printed circuit board 10.1. Indoor unit 10.1.1. Main printed circuit board.
Page 22
22 10.1.2. Power printed circuit board 10.1.3. Indicator printed circuit board.
Page 23
23 10.2. Outdoor unit.
Page 24: 11 Installation Instruction
24 11 installation instruction 11.1. Select the best location 11.1.1. Indoor unit • do not install the unit in excessive oil fume area such as kitchen, workshop and etc. • there should not be any heat source or steam near the unit. • there should not be any obstacles blocking the air circulation. • ...
Page 25
25 11.2. Indoor unit 11.2.1. How to fix installation plate the mounting wall is strong and solid enough to prevent it from the vibration. The centre of installation plate should be at more than at right and left of the wall. The distance from installation plate edge to ceiling should more than . Fro...
Page 26
26 1. For the right rear piping 2. For the right and right bottom piping 3. For the embedded piping (this can be used for left rear piping and bottom piping also.).
Page 27
27 11.2.4. Connect the cable to the indoor unit 1. The inside and outside connecting cable can be connected without removing the front grille. 2. Connecting cable between indoor unit and outdoor unit shall be approved polychloroprene sheathed 4 x 1.5 mm 2 flexible cord, type designation 245 iec 57 o...
Page 28
28 cutting and flaring the piping 1. Please cut using pipe cutter and then remove the burrs. 2. Remove the burrs by using reamer. If burrs is not removed, gas leakage may be caused. Turn the piping end down to avoid the metal powder entering the pipe. 3. Please make flare after inserting the flare n...
Page 29
29 11.3. Outdoor unit 11.3.1. Install the outdoor unit • after selecting the best location, start installation according to indoor/outdoor unit installation diagram. 1. Fix the unit on concrete or rigid frame firmly and horizontally by bolt nut (ø10 mm). 2. When installing at roof, please consider s...
Page 30
30 4. Close the low side valve of the charging set and turn off the vacuum pump. Make sure that the needle in the gauge does not move after approximately five minutes. Note: be sure to take this procedure in order to avoid refrigerant gas leakage. 5. Disconnect the charging hose from the vacuum pump...
Page 31: 12 Operation and Control
31 12 operation and control 12.1. Basic function inverter control, which equipped with a microcomputer in determining the most suitable operating mode as time passes, automatically adjusts output power for maximum comfort always. In order to achieve the suitable operating mode, the microcomputer mai...
Page 32
32 12.1.5. Automatic operation • this mode can be set using remote control and the operation is decided by remote control setting temperature, remote control operation mode, indoor intake air temperature and outdoor air temperature. • during operation mode judgment, indoor fan motor (with speed of l...
Page 33
33 [heating] • according to indoor pipe temperature, automatic heating fan speed is determined as follows. B. Feedback control • immediately after the fan motor started, feedback control is performed once every second. • during fan motor on, if fan motor feedback 2550 rpm or increase, fan motor is t...
Page 34
34 12.4.2. Horizontal airflow • the horizontal airflow direction louvers can be adjusted manually by hand. 12.5. Timer control 12.5.1. On timer control • on timer can be set using remote control, the unit with timer set will start operate earlier than the setting time. This is to provide a comfortab...
Page 35: 13 Protection Control
35 13 protection control 13.1. Protection control for all operations 13.1.1. Restart control (time delay safety control) • the compressor will not turn on within 3 minutes from the moment operation stops, although the unit is turned on again by pressing off/on button at remote control within this pe...
Page 36
36 13.1.5. Compressor overheating prevention control • instructed frequency for compressor operation will be regulated by compressor discharge temperature. The changes of frequency are as below. • if compressor discharge temperature exceeds 112 ° c, compressor will be stopped, occurs 4 times per 20 ...
Page 37
37 13.2. Protection control for cooling & soft dry operation 13.2.1. Outdoor air temperature control • the compressor operating frequency is regulated in accordance to the outdoor air temperature as shown in the diagram below. • this control will begin 1 minute after the compressor starts. • compres...
Page 38
38 • this control stopped if: - when receive air swing change signal from remote control. • the horizontal louver will be fixed at 26 ° (regardless of auto or manual airflow direction setting). 13.2.7. Odor cut control • to reduce the odor released from the unit. - start condition - auto fan speed i...
Page 39: 14 Servicing Mode
39 14 servicing mode 14.1. Auto off/on button 1. Auto operation mode the auto operation will be activated immediately once the auto off/on button is pressed. This operation can be used to operate air conditioner with limited function if remote control is misplaced or malfunction. 2. Test run operati...
Page 40
40 4. Remote control receiving sound off/on mode the remote control receiving sound off/on mode will be activated if the auto off/on button is pressed continuously for more than 16 seconds (4 “beep” sounds will occur at 16th seconds to identify the remote control receiving sound off/on mode is in st...
Page 41: 15 Troubleshooting Guide
41 15 troubleshooting guide 15.1. Refrigeration cycle system in order to diagnose malfunctions, make sure that there are no electrical problems before inspecting the refrigeration cycle. Such problems include insufficient insulation, problem with the power source, malfunction of a compressor and a f...
Page 42
42 15.1.1. Relationship between the condition of the air conditioner and pressure and electric current • carry out the measurements of pressure, electric current, and temperature fifteen minutes after an operation is started. Cooling mode heating mode low pressure high pressure electric current duri...
Page 43
43 15.2. Breakdown self diagnosis function 15.2.1. Self diagnosis function (three digits alphanumeric code) • once abnormality has occurred during operation, the unit will stop its operation, and timer led blinks. • although timer led goes off when power supply is turned off, if the unit is operated...
Page 44
44 15.3. Error codes table abnormality / protection control abnormality judgement protection operation problem check location diagnosis display h00 no memory of failure — normal operation — — h11 indoor/outdoor abnormal communication after operation for 1 minute indoor fan only operation can start b...
Page 45
45 f97 compressor overheating protection 3 times happen within 30 minutes — compressor overheat • insufficient refrigerant f98 total running current protection 3 times happen within 20 minutes — total current protection • check refrigeration system • power source or compressor lock f99 outdoor direc...
Page 46
46 15.4. Self-diagnosis method 15.4.1. H11 (indoor/outdoor abnormal communication) malfunction decision conditions during startup and operation of cooling and heating, the data received from outdoor unit in indoor unit signal transmission is checked whether it is normal. Malfunction caused • faulty ...
Page 47
47 15.4.2. H14 (indoor intake air temperature sensor abnormality) malfunction decision conditions during startup and operation of cooling and heating, the temperatures detected by the indoor intake air temperature sensor are used to determine sensor errors. Malfunction caused • faulty connector conn...
Page 48
48 15.4.3. H15 (compressor temperature sensor abnormality) malfunction decision conditions during startup and operation of cooling and heating, the temperatures detected by the outdoor compressor temperature sensor are used to determine sensor errors. Malfunction caused • faulty connector connection...
Page 49
49 15.4.4. H16 (outdoor current transformer open circuit) malfunction decision conditions a current transformer (ct) is detected by checking the compressor running frequency ( rated frequency) and ct detected input current (less than 0.65a) for continuously 20 seconds. Malfunction caused • ct defect...
Page 50
50 15.4.5. H19 (indoor fan motor - dc motor mechanism locked) malfunction decision conditions the rotation speed detected by the hall ic during fan motor operation is used to determine abnormal fan motor (feedback of rotation > 2550rpm or malfunction caused • operation stops due to short circuit ins...
Page 51
51 15.4.6. H23 (indoor pipe temperature sensor abnormality) malfunction decision conditions during startup and operation of cooling and heating, the temperatures detected by the indoor heat exchanger temperature sensor are used to determine sensor errors. Malfunction caused • faulty connector connec...
Page 52
52 15.4.7. H27 (outdoor air temperature sensor abnormality) malfunction decision conditions during startup and operation of cooling and heating, the temperatures detected by the outdoor air temperature sensor are used to determine sensor errors. Malfunction caused • faulty connector connection. • fa...
Page 53
53 15.4.8. H28 (outdoor pipe temperature sensor abnormality) malfunction decision conditions during startup and operation of cooling and heating, the temperatures detected by the outdoor pipe temperature sensor are used to determine sensor errors. Malfunction caused • faulty connector connection. • ...
Page 54
54 15.4.9. H30 (compressor discharge temperature sensor abnormality) malfunction decision conditions during startup and operation of cooling and heating, the temperatures detected by the outdoor discharge pipe temperature sen- sor are used to determine sensor errors. Malfunction caused • faulty conn...
Page 55
55 15.4.10. H33 (unspecified voltage between indoor and outdoor) malfunction decision conditions the supply power is detected for its requirement by the indoor/outdoor transmission. Malfunction caused • wrong models interconnected. • wrong indoor unit and outdoor unit pcbs used. • indoor unit or out...
Page 56
56 15.4.11. H97 (outdoor fan motor - dc motor mechanism locked) malfunction decision conditions the rotation speed detected by the hall ic during fan motor operation is used to determine abnormal fan motor. Malfunction caused • operation stops due to short circuit inside the fan motor winding. • ope...
Page 57
57 15.4.12. H98 (indoor high pressure protection) error code will not display (no timer led blinking) but store in eeprom malfunction decision conditions during heating operation, the temperature detected by the indoor pipe temperature sensor is above 60 ° c. Malfunction caused • air short circuit a...
Page 58
58 15.4.13. H99 (indoor freeze prevention protection: cooling or soft dry) error code will not display (no timer led blinking) but store in eeprom malfunction decision conditions freeze prevention control takes place (when indoor pipe temperature is lower than 2 ° c) malfunction caused • air short c...
Page 59
59 15.4.14. F11 (4-way valve abnormality) malfunction decision conditions • when heating operation, when indoor pipe temperature is below 10 ° c • when cooling operation, when indoor pipe temperature is above 45 ° c malfunction caused • connector in poor contact • faulty sensor • faulty outdoor unit...
Page 60
60 15.4.15. F90 (power factor correction protection) malfunction decision conditions during startup and operation of cooling and heating, when power factor correction (pfc) protection circuitry at the outdoor unit main pcb senses abnormal high dc voltage level. Malfunction caused • dc voltage peak d...
Page 61
61 15.4.16. F91 (refrigeration cycle abnormality) malfunction decision conditions • during cooling, compressor frequency = fcmax. • during heating, compressor frequency > fhrated. • during cooling and heating operation, running current: 0.65a • during cooling, indoor intake - indoor pipe ° c • durin...
Page 62
62 15.4.17. F93 (compressor rotation failure) malfunction decision conditions a compressor rotation failure is detected by checking the compressor running condition through the position detection circuit. Malfunction caused • compressor terminal disconnect • faulty outdoor pcb • faulty compressor tr...
Page 63
63 15.4.18. F95 (cooling high pressure abnormality) malfunction decision conditions during operation of cooling, when outdoor unit heat exchanger high temperature data (61 ° c) is detected by the outdoor pipe temperature sensor. Malfunction caused • air short circuit at indoor unit • dust accumulati...
Page 64
64 15.4.19. F96 (ipm overheating) malfunction decision conditions during operating of cooling and heating, when ipm temperature data (100 ° c) is detected by the ipm temperature sensor. Multi models only • compressor overheating: during operation of cooling and heating, when the compressor ol is act...
Page 65
65 15.4.20. F97 (compressor overheating) malfunction decision conditions during operation of cooling and heating, when compressor tank temperature data (112 ° c) is detected by the compressor tank temperature sensor. Malfunction caused • faulty compressor tank temperature sensor • 2/3 way valve clos...
Page 66
66 15.4.21. F98 (input over current detection) malfunction decision conditions during operation of cooling and heating, when an input over-current (x value in total running current control) is detected by checking the input current value being detected by current transforme r (ct) with the compresso...
Page 67
67 15.4.22. F99 (output over current detection) malfunction decision conditions during operation of cooling and heating, when an output over-current (dc peak current value at ipm prevention control) is detected by checking the current that flows in the inverter dc peak sensing circuitry. Malfunction...
Page 68
68 16 disassembly and assembly instructions 16.1. Indoor electronic controllers, cross flow fan and indoor fan motor removal procedures 16.1.1. To remove front grille 16.1.2. To remove power electronic controller high voltages are generated in the electrical parts area by the capacitor. Ensure that ...
Page 69
69 16.1.3. To remove discharge grille.
Page 70
70 16.1.4. To remove control board 16.1.5. To remove cross flow fan and indoor fan motor.
Page 71
71.
Page 72
72 16.2. Outdoor electronic controller removal procedure caution! When handling electronic controller, be careful of electrostatic discharge. 1. Remove the 3 screws of the top panel. Fig. 1 2. Remove the 6 screws of the front panel. Fig. 2 3. Remove the screw of the terminal board cover. 4. Remove t...
Page 73: 17 Technical Data
73 17 technical data 17.1. Operation characteristics 17.1.1. Cu-ce9lke.
Page 74
74.
Page 75
75.
Page 76
76.
Page 77
77 17.1.2. Cu-ce12lke.
Page 78
78.
Page 79
79.
Page 80
80
Page 81
81 17.2. Sensible capacity chart • cu-ce9lke • cu-ce12lke 230v outdoor temp. ( ° c) indoor wet bulb temp. 30 35 40 46 tc shc ip tc shc ip tc shc ip tc shc ip 17.0 ° c 2.48 1.88 0.50 2.32 1.80 0.54 2.16 1.73 0.57 1.96 1.65 0.62 19.0 ° c 2.50 0.55 19.5 ° c 2.72 1.97 0.51 2.55 1.89 0.55 2.37 1.82 0.59 ...
Page 82
82 18 exploded view and replacement parts list 18.1. Indoor unit note the above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts..
Page 83
83 (note) • all parts are supplied from phaam, malaysia (vendor code: 00029488). • “o” marked parts are recommended to be kept in stock. Ref. No. Part name & description qty. Cs-ce9lke cs-ce12lke remarks 1 chassy complete 1 cwd50c1653 ← 2 fan motor 1 arw6101cb ← o 3 cross flow fan complete 1 cwh02c1...
Page 84
84 18.2. Outdoor unit note the above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts..
Page 85
85 (note) • all parts are supplied from phaam, malaysia (vendor code: 00029488). • “o” marked parts are recommended to be kept in stock. [phaam] printed in malaysia sfyw1007-00 ref. No. Part name & description qty. Cu-ce9lke cu-ce12lke remarks 1 chassy ass’y 1 cwd50k2202 ← 2 anti-vibration bushing 3...