Panasonic CS-E12BKP Supplemental Service Manual - page 3
2.1.2. Frequency Instruction for Compressor Operation (Page: 18 - 20)
Table on Frequency Number
No.
Frequency (Hz)
Remarks
E9BKP
E12BKP
13
39.0
52.0
Fc
15
47.0
62.0
Fc max. (E9BKP)
16
49.0
67.0
Fc max. (E12BKP)
17
56.0
68.5
Fh
30
90.0
110.0
Fh max.
Table on Initial Frequency Zone
Temperature, X (°C)
Freq. No. - E12BKP
(Intake Air - Internal Setting)
Cooling
X
1
-2.5
X
1
-1.5
X
1
-1.0
X
1
-0.5
X
4
+0.5
X
6
+1.0
X
9
+1.5
X
16
X
+2.5
16
Table on Shifting Frequency Zone
Temperature, X (°C)
Zone
Frequency No. Shifting:
(Intake Air - Internal Setting)
Cooling Mode / Soft Dry Mode
Heating Mode
X
-2.5
0
Shift to Freq. MIN
Shift to Freq. MAX
-2.5
X
-1.5
1
Shift to Freq. MIN
Shift to Freq. MAX
-1.5
X
-1.0
2
-2 Freq. No.
+2 Freq. No.
-1.0
X
-0.5
3
-1 Freq. No.
+1 Freq. No.
-0.5
X
+1.0
4
Same Freq. No.
Same Freq. No.
+0.5
X
+1.0
5
+1 Freq. No.
-1 Freq. No.
+1.0
X
+1.5
6
+2 Freq. No.
-2 Freq. No.
+1.5
X
+2.5
7
Shift to Freq. MAX
Shift to Freq. MIN
X
+2.5
8
Shift to Freq. MAX
Shift to Freq. MIN
Condition:
Freq. no. for E9BKP
Freq. no. for E12BKP
Remarks
MIN
MAX
MIN
MAX
Cooling Mode
1
15
1
16
(a)
- if remote controller set
28°C & fan speed =
Hi
7
15
7
16
(a), (c)
- if remote controller set
28°C & fan speed =
Me-, Me, Me+, Auto
5
15
6
16
(a), (c)
- if remote controller set
28°C & fan speed =
Lo
4
15
5
16
(a), (c)
- if Powerful Mode ON
7
15
7
16
(a), (c)
Soft Dry Mode
4
7
4
8
Heating Mode
1
30
1
30
(b)
- if remote controller set
18°C & fan speed =
Hi
10
30
10
30
(b), (d)
- if remote control set
18°C & fan speed =
Me-, Me, Me+, Auto
9
30
9
30
(b), (d)
- if remote controller set
18°C & fan speed =
Lo
8
30
8
30
(b), (d)
- if Powerful Mode ON
10
30
10
30
(b), (d)
(a)
If frequency decreases from MAX, the following frequency performed will be depending to outdoor temperature, as given in below table
(for 30 seconds only) and then continues as normal rule.
(b)
(If frequency increases from Freq. No. 17, the following frequency performed is as below (for 30 seconds only) and then continue as
normal rule.
(c)
When temperature different (intake - setting)
Mode, Soft Dry Mode, and Anti-freezing control.
(d)
When temperature different (intake - setting) > +1.5 °C or Thermo-Off activated and only valid for 130 seconds.
(b) The frequency judged falls on frequency shifting zone number 0 or 1 (shift to Frequency MIN) at Cooling mode operation.
(d) The frequency judged falls on frequency shifting zone number 7 or 8 (shift to Frequency MAX) at Cooling mode operation.
The instructed frequency is the value referred by the frequency number, which resulted from previous instructed frequency
number with the numbers of frequency numbers to be shifted, in Table on Frequency Number at automatic fan speed.
3
CS-E9BKP CU-E9BKP5 / CS-E12BKP CU-E12BKP5