1 features 2 2 functions 3 2.1. Remote control 3 2.2. Indoor unit 4 2.3. Outdoor unit 5 3 product specifications 6 3.1. Cs-e15dkew cu-e15dke 6 3.2. Cs-e18dkew cu-e18dke 8 3.3. Cs-e21dkes cu-e21dke 10 4 dimensions 12 4.1. Indoor unit & remote control 12 4.2. Outdoor unit 14 © 2005 panasonic ha air-co...
3.1. Cs-e15dkew cu-e15dke 3 product specifications unit cs-e15dkew cu-e15dke cooling capacity kw kcal/h btu/h 4.40 (0.90 - 5.00) 3,780 (770 - 4,300) 15,000 (3,070 - 17,100) heating capacity kw kcal/h btu/h 5.50 (0.90 - 7.10) 4,730 (770 - 6,110) 18,800 (3,070 - 24,200) moisture removal l/h pint/h 2.4...
Unit cs-e15dkew cu-e15dke piping connection port (flare piping) inch inch g ; half union 1/2” l ; half union 1/4” g ; 3-way valve 1/2” l ; 2-way valve 1/4” pipe size (flare piping) inch inch g (gas side) ; 1/2” l (liquid side) ; 1/4” g (gas side) ; 1/2” l (liquid side) ; 1/4” drain hose inner diamet...
3.2. Cs-e18dkew cu-e18dke unit cs-e18dkew cu-e18dke cooling capacity kw kcal/h btu/h 5.30 (0.90 - 6.00) 4,560 (770 - 5,160) 18,100 (3,070 - 20,500) heating capacity kw kcal/h btu/h 6.60 (0.90 - 8.00) 5,680 (770 - 6,880) 22,500 (3,070 - 27,300) moisture removal l/h pint/h 2.9 (6.1) power source (phas...
Unit cs-e18dkew cu-e18dke pipe size (flare piping) inch inch g (gas side) ; 1/2” l (liquid side) ; 1/4” g (gas side) ; 1/2” l (liquid side) ; 1/4” drain hose inner diameter mm 12 — length m 0.65 — power cord length number of core-wire —— — — dimensions height inch (mm) 10 - 13/16 (275) 29 - 17/32 (7...
3.3. Cs-e21dkes cu-e21dke unit cs-e21dkes cu-e21dke cooling capacity kw kcal/h btu/h 6.30 (0.90 - 7.10) 5,420 (770 - 6,110) 21,500 (3,070 - 24,200) heating capacity kw kcal/h btu/h 7.20 (0.90 - 8.50) 6,190 (770 - 7,310) 24,600 (3,070 - 29,000) moisture removal l/h pint/h 3.5 (7.4) power source (phas...
Unit cs-e21dkes cu-e21dke pipe size (flare piping) inch inch g (gas side) ; 1/2” l (liquid side) ; 1/4” g (gas side) ; 1/2” l (liquid side) ; 1/4” drain hose inner diameter mm 12 — length m 0.65 — power cord length number of core-wire —— — — dimensions height inch (mm) 10 - 13/16 (275) 29 - 17/32 (7...
4 dimensions 4.1. Indoor unit & remote control 4.1.1. Cs-e15dkew 12 cs-e15dkew cu-e15dke / cs-e18dkew cu-e18dke / cs-e21dkes cu-e21dke.
4.1.2. Cs-e18dkew cs-e21dkes 13 cs-e15dkew cu-e15dke / cs-e18dkew cu-e18dke / cs-e21dkes cu-e21dke.
4.2. Outdoor unit 4.2.1. Cu-e15dke cu-e18dke cu-e21dke 14 cs-e15dkew cu-e15dke / cs-e18dkew cu-e18dke / cs-e21dkes cu-e21dke.
5 refrigeration cycle diagram 15 cs-e15dkew cu-e15dke / cs-e18dkew cu-e18dke / cs-e21dkes cu-e21dke.
6 block diagram 16 cs-e15dkew cu-e15dke / cs-e18dkew cu-e18dke / cs-e21dkes cu-e21dke.
7 wiring diagram 17 cs-e15dkew cu-e15dke / cs-e18dkew cu-e18dke / cs-e21dkes cu-e21dke.
Attached accessories applicable piping kit cz-4f5, 7, 10bp (e15dk) select the best location indoor unit • there should not be any heat source or steam near the unit. • there should not be any obstacles blocking the air circulation. • a place where air circulation in the room is good. • a place where...
Attached accessories applicable piping kit cz-4f5, 7, 10bp (e18dk, e21dk) select the best location indoor unit • there should not be any heat source or steam near the unit. • there should not be any obstacles blocking the air circulation. • a place where air circulation in the room is good. • a plac...
1. Rated frequency operation 13 servicing information caution: • pb free solder has a higher melting point than standard solder; typically the melting point is 50 - 70°f (30 - 40°c) higher. Please use a high temperature soldering iron. In case of the soldering iron with temperature control, please s...
2. Troubleshooting air conditioner refrigeration cycle system in order to diagnose malfunctions, make sure that there are no electrical problems before inspecting the refrigeration cycle. Such problems include insufficient insulation, problem with the power source, malfunction of a compressor and a ...
1. Relationship between the condition of the air conditioner and pressure and electric current cooling mode heating mode condition of the air conditoner low pressure high pressure electric current during operation low pressure high pressure electric current during operation insufficient refrigerant ...
Error codes table diagnosis display abnormality / protection control abnormality judgement emergency operation primary location to verify h11 indoor / outdoor abnormal communication > 1 min after starting operation indoor fan operation only • internal / external cable connections • indoor / outdoor ...
• remote control reset when the batteries are inserted for the first time, or the batteries are replaced, all the indications will blink and the remote control might not work. If this happen, remove the cover of the remote control and push the reset point once to clear the memory data. • changing th...
1 technical data (page: 100) 1.1. Operation characteristics 1.1.1. Cs-e15dkew cu-e15dke 2 cs-e15dkew cu-e15dke / cs-e18dkew cu-e18dke / cs-e21dkes cu-e21dke [phaam] printed in malaysia.
14.1.2. Cs-e18dkew cu-e18dke 101 cs-e15dkew cu-e15dke / cs-e18dkew cu-e18dke / cs-e21dkes cu-e21dke.
14.1.3. Cs-e21dkes cu-e21dke 102 cs-e15dkew cu-e15dke / cs-e18dkew cu-e18dke / cs-e21dkes cu-e21dke.
14.2. Sensible capacity chart ● cs-e15dkew cu-e15dke 230v outdoor temp. (°c) indoor wet bulb temp. 30 35 40 46 tc shc ip tc shc ip tc shc ip tc shc ip 17.0°c 4.36 3.31 1.25 4.08 3.17 1.35 3.79 3.05 1.44 3.45 2.90 1.56 19.0°c 4.40 1.37 19.5°c 4.79 3.46 1.28 4.48 3.33 1.38 4.17 3.20 1.47 3.79 3.05 1.5...
15 exploded view (indoor unit) 15.1. Cs-e15dkew note: the above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts. 104 cs-e15dkew cu-e15dke / cs-e18dkew cu-e18dke / cs-e21dkes cu-e21dke.
15.2. Cs-e18dkew cs-e21dkes note: the above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts. 105 cs-e15dkew cu-e15dke / cs-e18dkew cu-e18dke / cs-e21dkes cu-e21dke.
16 replacement parts list (indoor unit) 16.1. Cs-e15dkew ref. No. Part name & description qty. Cs-e15dkew remarks 1 chassy complete 1 cwd50c1431 2 fan motor 1 cwa981149 0 3 cross flow fan complete 1 cwh02c1031 4 bearing ass’y 1 cwh64k007 5 screw - cross flow fan 1 cwh4580304 6 evaporator 1 cwb30c172...
16.2. Cs-e18dkew cs-e21dkes ref. No. Part name & description qty. Cs-e18dkew cs-e21dkes remarks 1 chassy complete 1 cwd50c1382 ← 2 fan motor 1 cwa981149 ← 0 3 cross flow fan complete 1 cwh02c1010 ← 4 screw - cross flow fan 1 cwh4580304 ← 5 bearing ass’y 1 cwh64k007 ← 6 evaporator 1 cwb30c1533 cwb30c...
17 exploded view (outdoor unit) 17.1. Cu-e15dke cu-e18dke cu-e21dke note: the above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts. 108 cs-e15dkew cu-e15dke / cs-e18dkew cu-e18dke / cs-e21dkes cu-e21dke.
18 replacement parts list (outdoor unit) 18.1. Cu-e15dke cu-e18dke cu-e21dke ref no. Description & name qty. Cu-e15dke cu-e18dke cu-e21dke remarks 1 chassy assy 1 cwd50k2085 ← ← 2 anti-vibration bushing 3 cwh50077 ← ← 3 compressor 1 5cs130xad04 ← ← o 4 nut-compressor mount 3 cwh56000 ← ← 5 sound pro...
118 cs-e15dkew cu-e15dke / cs-e18dkew cu-e18dke / cs-e21dkes cu-e21dke.