Panasonic CS-ME5PKE Service Manual - page 8
8
Multi Split Combination Possibility:
o A single outdoor unit enables air conditioning of up to two separate rooms for CU-2E15PBE, CU-2E18PBE.
o A single outdoor unit enables air conditioning of up to three separate rooms for CU-3E18PBE.
o A single outdoor unit enables air conditioning of up to four separate rooms for CU-4E23PBE.
OUTDOOR UNIT
CONNECTABLE
INDOOR UNIT
CU-2E15PBE CU-2E18PBE
CU-3E18PBE
CU-4E23PBE
ROOM
A B A B A B C A B C D
TYPE
1.6kW CS-ME5PKE
●
●
●
●
●
●
●
●
●
●
●
2.0kW
CS-E7PKE
CS-XE7PKEW
●
●
●
●
●
●
●
●
●
●
●
2.5kW
CS-E9PKE
CS-XE9PKEW
●
●
●
●
●
●
●
●
●
●
●
3.0kW
CS-E12PKE
CS-XE12PKEW
●
●
●
●
●
●
●
●
●
●
●
3.2kW
CS-E15PKE
CS-XE15PKEW
– – – – ●
●
●
●
●
●
●
5.0kW
CS-E18PKE
CS-XE187PKEW
– – – – ●
●
●
●
●
●
●
Wall
6.0kW
CS-E21PKE
CS-XE217PKEW
– – – – – – – ●
●
●
●
Capacity range of connectable
indoor units
From 4.0kW
to 5.6kW
From 4.0kW
to 6.4kW
From 4.5kW
to 9.0kW
From 4.5kW
to 11.0 kW
1 room maximum
pipe length (m)
20 20
25
25
Allowable elevation (m)
10
10
10
15
Total allowable
pipe length (m)
30 30
50
60
Total pipe length
for maximum
chargeless length (m)
20 20
30
30
Pipe length
Additional gas
amount over
chargeless length (g/m)
20 20
20
20
Note: “●” : Available
Remarks for CU-2E15PBE / CU-2E18PBE
1. At least two indoor units must be connected.
2. The total nominal cooling capacity of indoor unit that will be connected to outdoor unit must be within connectable capacity range of indoor
unit. (as shown in the table above)
Example: The indoor units’ combination below is possible to connect to CU-2E15PBE. (Total nominal capacity of indoor units is between
4.0kW to 5.6kW)
1) Two CS-E7PKEW only. (Total nominal cooling capacity is 4.0kW)
2) One CS-E7PKEW and one CS-E9PKEW. (Total nominal cooling capacity is 4.5kW)
Remarks for CU-3E18PBE / CU-4E23PBE
1. At least two indoor units must be connected.
2. The total nominal cooling capacity of indoor unit that will be connected to outdoor unit must be within connectable capacity range of indoor
unit. (as shown in the table above)
Example: The indoor units’ combination below is possible to connect to CU-3E18PBE. (Total nominal capacity of indoor units is between
4.5kW to 9.0kW)
1) Two CS-E9PKEW only. (Total nominal cooling capacity is 5.0kW)
2) Three CS-E12PKEW. (Total nominal cooling capacity is 9.6kW)