Panasonic CS-ME9SB4U Install Manual - page 3
17
6 The indoor unit must allow easy draining.
7 The indoor unit must allow easy connection to the outdoor unit.
8 Place the indoor unit according to the height from the ceiling shown in the illustration below.
9 The indoor unit must be from at least 9.8 ft (3 m) away from any noise-generating equipment. The electrical
wiring must be shielded with a steel conduit.
10 If the power supply is subject to noise generation, add a suppressor.
11 Do not install the indoor unit in a laundry. Electric shocks may result.
Note
Thoroughly study the following installation locations
1 In such places as restaurants and kitchens, considerable amount of oil steam and flour adhere to the turbo
fan, the fin of the heat exchanger and the drain pump, resulting in heat exchange reduction, spraying,
dispersing of water drops, drain pump malfunction, etc.
In these cases, take the following actions:
o
Make sure that the ventilation fan for smoke-collecting hood on a cooking table has sufficient capacity so
that it draws oily steam which should not flow into the suction of the air conditioner.
o
Make enough distance from the cooking room to install the air conditioner in such place where it may not
suck in oily steam.
2 Avoid installing the air conditioner in such
circumstances where cutting oil mist or iron
powder exist especially in factories, etc.
3 Avoid places where inflammable gas is
generated, flows-in, contaminated, or leaked.
4 Avoid places where sulphurous acid gas or
corrosive gas can be generated.
5 Avoid places near high frequency generators.
Model Name
Height in the ceiling
ME9***
11" (280 mm) or
more
11.2.2 Installation of Indoor Unit
This air conditioner uses a drain up motor.
Horizontally install the unit using a level gauge.
CEILING OPENING DIMENSIONS AND
HANGING
BOLT LOCATION
The paper model for installation expand or shrink
according to temperature and humidity.
Check on dimensions before using it.
Caution
During the installation, care must be taken
not to damage electric wires.
The dimensions of the paper model for installation
are the same as those of the ceiling opening
dimensions.
Be sure to discuss the ceiling drilling work with the
workers concerned.
Air conditioner
Cooking table
Ensure ample
distance
Use the ventilation fan for smoke-
collection hood with sufficient capacity.
Drain pipe
25
9
/
16
" (650) (Ceiling opening)
(Hanging bolt)
(Unit: inch (mm))
25
9
/
16
"
(6
50)
(C
e
ili
ng
open
ing)
20
7
/
8
"
(53
0)
(H
ang
ing
bol
t)
22
13
/
16
"
(5
80
)
(U
nit
siz
e
)
22
13
/
16
" (580)
(Unit size)
Refrigerant pipe
20
7
/
8
" (530)
2
3
/
8
"
(60)
2
3
/
8
"
(60)
2
3
/
8
"
(60)
2
3
/
8
"
(60)