Pneumercator TMS2000 Quick Start Up Manual - page 11
Quick Start-up Guide
TMS Series
TMS Quick Start-up Guide.docx
Page 11 of 24
November 21, 2017
8) Press the EDIT ENABLE/THEFT ALARM ACKNOWLEDGE button on the inside of the front door
up one time. This will NOT cause the display to change but will authorize you to make
programming changes to the TMS for the duration of the programming session.
Figure 6 - Edit Enable Button
9) Press the EDIT (TEST) button one time and the first digit (cursor) will start flashing. This digit
indicates a positive or negative number. Use the ▼ (GROUP SELECT) and/or ▲ (TEST) buttons
to change the value of what’s flashing. Use the ► (MODE) button to move the cursor to the right.
Once the last digit is flashing the correct value, enter by pressing the ► (MODE) button. It will
stop flashing and show you the current value for the Product Float Height Offset.
10) Press and hold the STEP (MODE) button until it beeps ONE TIME and immediately release the
button. h2o HO (H
2
O HO) will appear briefly then the current value for the Water Float Height
Offset will appear. Note that this number will start with a + (+) or a - (-) sign indicating a positive
or negative number.
11) Press the EDIT (TEST) button one time and the first digit (cursor) will start flashing. This digit
indicates a positive or negative number. Use the ▼ (GROUP SELECT) and/or ▲ (TEST) buttons
to change the value of what’s flashing. Use the ► (MODE) button to move the cursor to the right.
Once the last digit is flashing the correct value, enter by pressing the ► (MODE) button. It will
stop flashing and show you the current value for the Water Float Height Offset.
12) If there is more than one tank enabled, go to Step 6 to calibrate the next tank.
13) Press and hold the STEP (MODE) button until it beeps TWO TIMES and immediately release the
button. Return (Return) appears.
14) Press the EDIT (TEST) button two times. Probe (Probe) will appear flashing on the display.
15) Press the GROUP SELECT (TANK SELECT) button until Return (Return) appears flashing.
16) Press the ► (MODE) button one time. Config (Config) appears.
17) Press the EDIT (TEST) button until Return (Return) appears flashing.
18) Press the ► (MODE) button one time. The system returns to normal operating mode.
DWG NO. 20045 REV. N/C
EDIT ENABLE/
THEFT ALARM
ACKNOWLEDGE
ACKNOWLEDGE
THEFT ALARM
EDIT ENABLE/
PUSH UP AND
RELEASE