Provib Tech VS102 User Manual - page 10
VS102 Electronic Vibration Switch
ProvibTech
9
9 Adjust Alert: hold down RESET/SET button for 10s, OK LED and Alert LED flash. Press
RESET/SET button again, ALERT LED flash and it changes into Alert calibration mode. Three
seconds later, the ampere meter displays the last set alert set-point (default factory setting is
50% of full scale). Press + or – to adjust it to the desired value. Press RESET/SET button again,
DANGER LED flash. Three seconds later, press RESET/SET button and OK LED, ALERT LED
and DANGER LED flash. At last, press RESET/SET button to withdraw from Alert calibration
mode.
9 Adjust Danger: hold down RESET/SET button for 10s, OK LED and Alert flash. Press
RESET/SET button again, ALERT LED flash. Three seconds later, press RESET/SET button
and DANGER LED flash and the instrument changes into Danger calibration mode. Three
seconds later, the ampere meter displays the last set DAGER set point (default factory setting is
75% of full scale). Press + or – to adjust it to desired value. Press RESET/SET button again OK
LED, ALERT LED and DANGER LED flash. At last, press RESET/SET button to withdraw from
Danger calibration mode.