12.3 Room Thermostat Connection:
• The room thermostat
must be connected to
the terminal block
situated next to the
control panel
Figure 12.6
•
Any external controls
and connection lines
must be rated at 120
VAC but under no
circumstances should
external live voltage
be connected to the
room thermostat link
on the boiler
• When connecting
any type of external
control, the jumper J
in Fig. 12.6 must be
removed.
• The room
thermostat must be
connected to the
“Control Terminal
Block” (Fig 12.7).
Figure 12.7
• Connect the room
thermostat between
terminals 1 and 3 as
shown in Fig. 12.7.
12.4 Relay Panel Connection:
• The relay control must
be connected to the
terminal block
situated next to the
control panel
1
2
L
N
3
To fused spur
isolation switch
Power supply
terminal block
External controls
terminal block
J
120 VAC Control
Terminal Block
Figure 12.8
• When connecting any
type of relay control,
the jumper J in Fig.
12.8 must be
removed.
• Connect the dry
contact switch of the
relay panel to the
control terminal block
(Fig 12.9).
Power supply
terminal block
External controls
terminal block
Generic Relay Control
1
2
L
N
3
(120V rating)
T
Figure 12.9
• Connect the dry
contact switch to
terminals 1 and 3
shown in Fig. 12.9.
12. Electrical Connections/Wiring
1
2
L
N
3
To fused spur
isolation switch
Power supply
terminal block
External controls
terminal block
J
120 VAC Control
Terminal Block
Power supply
terminal block
External controls
terminal block
T
Room thermostat
1
2
L
N
3
(120V rating)
Control Block Do
Not Apply Power
Control Block Do
Not Apply Power