9113 Hardware
Power Terminal:
Power to the 9113 is supplied through a three position removable compression terminal block. The 9113
requires 24 volt, two hundred milliamp direct current power. An earth ground connection is also required and
provided through the terminal block. Do not plug or unplug the terminal block while power is applied. Reverse
voltage and overvoltage protection are included.
Dip Switch:
Four switches are accessible through an opening at the side of the 9113 as shown in the image above. A switch
is OFF when the slider is pushed down toward the product label. Currently switches one and three are not
implemented. The operation of the 9113 is controlled by switch two and four. Do not change switch settings
while power is applied to the 9113!
If switch two and four are off...
This is the normal run mode for the 9113. The Mode LED will flash amber when no session has been initiated by
a PLC or the absence of activity by the PLC has caused a session to expire. The LED will flash green while a
session is active. Refer to the theory of operation topic for more information about sessions.
If switch four is on and switch two is on or off...
This is a mode that allows the 9113 firmware to be updated. Refer to the help file included with the update utility
for specific instructions.