Radiant EcoSmart ES50LVP Installation, operation and maintenance manual - Service
26 |
P a g e
SERVICE
AND
MAINTENANCE
NOTE: The ecosmart is not to be used for temporary heat during construction. Use for this
purpose will void equipment warranty.
Filter
Inspect the filter monthly and replace, remove and vacuum or rinse as required. A clogged or
inadequate filter may void product warranty. Replacement filter size is 16 x 20 x 1.
Coils
Air conditioning and heating coils should not require cleaning if the filter maintenance schedule
is adhered to. If a filter is damaged or collapses from plugging, dust may foul the coils. If this
happens, replace the filter and carefully vacuum the coils. The fan may need to be removed to
gain access to the face of the heating coil.
Fan and Motor
Check fan for dust once a year. If dirty, vacuum or wash to remove dust. Keeping the fan blades
clean will reduce noise and improve capacity and efficiency of the heating system.
Control and Blower Assembly Removal
1. Turn off main power.
2. Disconnect power, thermostat and any other miscellaneous wiring from the control
board and remove them from the control casing.
3. On the bottom side of the upper cover, disconnect the supply air temperature sensor by
sliding out the rubber grommet.
4. Gently pull out the black wire until a white connector is revealed.
5. Unplug the white connector noting that there is a polarizing/locking feature when re-
assembling.
6. Remove (Qty. 2) ¼-20 bolts, lockwashers and flat washers holding the control and
blower assembly to the centre plate.
7. Slide out assembly.
8. Re-assemble in the reverse order.