Radionics D7036 Installation Instructions Manual - D7036
D7036 Installation Instructions
43115E
Page 4
Copyright © 2001 Radionics
D7036
5.0
Setting the D7036 Address
Note:
Each keypad must have its address set with its address pins. The keypads must also be programmed at the control
panel.
Address 1
Address 4
Address 7
Address 10
Address 13
Address 2
Address 5
Address 8
Address 11
Address 14
Address 3
Address 6
Address 9
Address 12
Do not use
address 15
1 2
4
8
3
5 6 7
1 2
4
8
3
5 6 7
1 2
4
8
3
5 6 7
1 2
4
8
3
5 6 7
1 2
4
8
3
5 6 7
1 2
4
8
3
5 6 7
1 2
4
8
3
5 6 7
1 2
4
8
3
5 6 7
1 2
4
8
3
5 6 7
1 2
4
8
3
5 6 7
1 2
4
8
3
5 6 7
1 2
4
8
3
5 6 7
1 2
4
8
3
5 6 7
1 2
4
8
3
5 6 7
Figure 5: D7036 Address Jumper Settings
Select the keypad address (1-14).
Place the shorting jumpers over the address pins as shown at the top of the next column.
Note:
Each keypad must have its own address, and each address can only support one device.
6.0
Wiring the D7036
Be sure all wiring is un-powered before routing. Keypad wiring cannot be shared with smoke detector wiring,
NAC wiring or MUX loop wiring.
For the D7024 FACP, the maximum allowed DC current draw from the auxiliary power is 500 mA for keypads. The
maximum length of wire (all branches added together) that can be connected to the option bus terminals is 4,000 ft.
(1,219 m).
The maximum length between any one device and the panel terminals depends on the current drawn on the branch that
the device is on. The current draw on a particular branch can be found by adding together the individual current draws
of each device connected to the branch.
Please refer to the
D7024 Installation Guide
(P/N: 31499) for detailed wire length calculations.
Note:
Up to three keypads may be used on any single 1,000 ft. (305 m) run of #18 AWG (1.2 mm) wire.