Rasmussen Yellow Flame Owner's Manual - page 10
10
Wireless Wall
Switch
(WS-2R)
Wireless Wall
Thermostat
(TS-2R)
Wireless
Wall Timer
(Up to 120 Minutes)
(WT-2R)
Wireless
On/Off
Remote
(SR-2R)
Wireless
On/Off Remote
with Thermostat
(THR-2R)
SERVICE AND TROUBLESHOOTING GUIDE FOR THE “EASY” SAFETY PILOT KIT
Analysis and correction of control of service problems must be made by qualified gas service technicians only. Attempts
to service or repair the “EASY” Safety Pilot Kit by other than authorized service personnel will void the manufacture’s
warranty. In general , failure of “EASY” Safety Pilot Control may be due to the reasons noted below:
1. Pilot will not light initially:
●
Check for loose Thermocouple terminal nut connection.
●
Check for improper pilot flame adjustment.
●
Check that Valve Knob is fully depressed during pilot lighting operation and hold for 30 to 60 seconds.
●
Check for defective Thermocouple.
●
Check for defective thermo magnet unit.
2. Pilot / Main burner clicks off after 5 to 30 minutes of burning:
●
Valve and Thermocouple are not defective, otherwise pilot would not initially light.
●
Thermocouple loses temperature difference between hot tip and cold junction (base).
●
Check that only tip of Thermocouple is in main burner flame.
●
Remove then replace logs to alter heat radiation pattern. Ensure that glass doors are open.
●
Ensure that proper size gas log set is installed. Too large of a set decreases cooling air flow.
BURNER OPERATION (“RE” VARIABLE FLAME HEIGHT MODELS AND“SE” REMOTE READY MODELS)
C) PILOT ADJUSTMENT
SCREW
1. Turn
VALVE KNOB
to “ON” position (Figure 21A)
2. Slide switch on the
RECEIVER
(Figure 22) to
“REMOTE”
position.
“RE Models
3. Depress the “ON/HI” button on the
TRANSMITTER
(Figure 22) until a click is heard. The burner will then
light to “Full on”
NOTE:
Reducing the burner flame can be achieved by pressing
the “LO” button one beep at a time to the desired flame height.
Pressing the “ON/HI” button one beep at a time will raise the
burner flame). To verify the burner is completely off, press the
“OFF” button once.
A) VALVE KNOB
“SE” Models
3. Consult Operating Instructions for Accessory Control (below).
4. Adjust the burner flame height by turning the valve knob (Figure
23A)
clockwise to lower and counter-clockwise to raise up to full on.
NOTE:
During the heating season leave valve knob in “PILOT”
position for convenience. Otherwise, turn to “OFF” position
for any prolonged non-use.
FIGURE 23
FIGURE 21
A) VALVE KNOB
KNOB POSITION
INDICATOR
B)
TRANSMITTER
Accessory Controls
KNOB POSITION
INDICATOR
DC Variable Motor Drive
FIGURE 22
Slide Switch in “REMOTE” Position
NOTE:
THE RECEIVER HAS
3 POSITIONS;
“OFF”, “FULL ON”
AND “REMOTE
ACCESS ON”
ON/OFF
SOLENOID
B) PILOT ADJUSTMENT
SCREW