Rittal SK 3201.200 Assembly And Operating Instructions Manual - 8 Filter Mounting
8 Filter mounting
Rittal Thermoelectric Cooler assembly and operating instructions
11
GB
8
Filter mounting
The Rittal Thermoelectric Cooler can be equipped
with a device filter (supplied).
An appropriate filter unit is recommended when the
cooling unit is used in ambient air subject to dust.
When a filter is installed, the lower louvred grille in
the air inlet of the cooling unit must be removed. To
do this, raise the louvred grille with a light tug at the
marked position (see Figure 14) and withdraw it at
the front. Then place the filter mat in the filter holder
of the device. The colour-marked side of the filter mat
must face the device. Then re-mount the louvred
grille and snap it into position by applying light pres-
sure.
Fig. 14:
Removable louvred grille
9
Mounting the
condensate discharge
The Rittal Thermoelectric Cooler is equipped with
a condensate discharge.
Fig. 15:
Condensate discharge
The controlled condensate discharge requires a
condensate discharge hose be connected to the
cooling unit’s condensate discharge supports.
The condensate hose is available as accessory.
The installation of the condensate hose requires
that it
– is laid with a gradient (no siphon formation),
– does not have any kinks,
– must not have a reduced cross-section if extended.
Note:
When a filter unit is used, it must be cleaned
regularly or, if necessary, replaced.
Risk of injury!
The operation of the cooling unit without
controlled condensate discharge can
cause liquid to accumulate below the
device.
Condensate
discharge