5. INSTALLATION.
•
Read and respect the Safety Information, described in
section 2 of this document. To obviate some of the indi-
cations stated in it, can cause a serious or very serious injuries
to persons in direct contact or in the vicinity, as well as break-
downs in the equipment and/or loads connected to itself.
As well as the own user's manual of the equipment, other
annex documents are supplied in the documentation CD. Con-
sult them and follow the described procedure strictly.
• Unless the opposite is indicated, any action, indications, prem-
ises, notes and others, are applicable to SLC CUBE3+ equip-
ments, that belong or not to a parallel system.
5.1.
RECEPTION OF THE EQUIPMENT.
•
It is dangerous to handle the equipment over the pallet
with not much prudent, because it could overturn and
cause serious or very serious injuries to the operators due to
impact of the possible fall and/or trapping. Pay attention to sec-
tion «2.2.3.1. To keep in mind» as regards to handling, moving
and location of the unit.
• Use the most suitable medium to move the UPS meanwhile is
packaged, with a pallet truck or fork lifting.
• Any equipment handling will be done paying attention to the
weights according to the model stated in the technical specifi-
cations of section «9. Annexes».
5.1.1.
Reception, packaging and contents.
• Reception. To check:
Data in the label sticked in the packaging corresponds to
the ones stated in the purchase order. Once the UPS is un-
packed, check the previous data with the one in the name-
plate of the equipment, sticked at the back of the front door
(PF).
If discrepancies exist, make the nonconformity as soon as
possible, by quoting the serial number of the equipment and
the references of the delivery note.
No incident has happened during the transport (packaging
and impact indicator are in perfect status).
Otherwise, follow the protocol stated in the label attached
to the impact indicator, located to the packaging.
• Unpacking.
To check the contents the packaging must be removed.
Complete the unpacking according to the «Un-
packing» procedure of the supplied document to-
gether with this manual and/or attached to the CD.
• Contents.
Standard equipment up to 20 kVA (LV) / 40 kVA (HV): Docu-
mentation CD and battery fuses.
Standard equipment > 20 kVA (LV) / 40 kVA (HV) or type
B1: Documentation CD.
Equipment 0 /: Documentation CD, wires and needed sup-
ports to fit the batteries in, hardcopy circuit diagram and
battery fuses (equipments up to 20 kVA (LV) / 40 kVA (HV)
only).
Battery cabinet: Fuses and cable connection bundle of 3,5
m. length and suitable cross section.
If the UPS belongs to a parallel system: A communication
BUS bundle per equipment.
• Once the reception is finished, it is advisable to pack the UPS
again till its commissioning in order to protect it against mechan-
ical impacts, dust, dirt, etc.
• The packaging of the equipment has a cardboard pallet or
wooden type depending on the case, expanded polystyrene
corners, bag and polyethylene strip, all of them are recyclable
materials. When it is required to dispose them, do it in accord-
ance to the regulation in force.
It is advisable to keep the packaging for 1 year as minimum.
5.1.2. Storage.
• The storage of the equipment, will be done in a dry and cool
place, and protected from rain, dust, water jets or chemical
agents. It is advisable to keep each equipment and battery
set, inside their original packaging because they have been
designed to assure the maximum protection during transport
ant storage.
Charging date written down by the factory.
Space to write down the new recharge date.
15-07-2013
Data label corresponding to the model.
Fig. 29. Label sticked in the packaging.
•
In general, less particular cases, the UPS has sealed lead
acid batteries and their storage must not exceed 6
months without recharging them (see last date of charge,
written down in the label sticked in the packaging of the equip-
ment or battery set).
Lapsed this period of 6 months, connect the equipment to
mains together with the battery set if any, paying attention
to the safety instructions and connection.
Models with separate static bypass line, is not needed to
connect this power terminal strip.