Ŗ Battery test of a single UPS (individual): It is a control com-
mand for a UPS that it is running in a parallel system currently
, to make a battery test equipment by equipment.
Ŗ Battery test of parallel UPSs: It is a control command of all
parallel UPS, to make the battery test in all the equipments
that made it up.
6.3.6. Identification
submenu.
Ŗ When pressing over the key
for less than 1 sec. from
"Identification" submenu, it is accessed to the identification
structure (see figure 39).
This submenu shows the serial number of the UPS, firmware
version and model of the equipment.
Ŗ When pressing the key
for more than 1 sec., the LCD
panel will display the "Identification" screen from the main
menu structure again.
Press
> 1 sec.
Press
or
< 1 sec.
Control submenu
structure
Main menu structure
Press
< 1 sec.
(*) Accessible with the S.T.S
password only
(*)
Fig. 39. Identification submenu screens.
Ŗ When pressing the key
for more than 1 sec., the LCD
panel will show the "Identification" screen of the main menu
structure again.
6.3.7. Setting
submenu.
Ŗ This submenu is exclusively reserved for Service and Tech-
nical Support or authorised personnel and it is only acces-
sible by password.
Some settings modify the specifications and settings to acti-
vate or deactivate some functions. Wrong modifications and/
or settings can make possible faults or lack of protection to
the own UPS and even they can affect or damage the load/s,
battery or the own equipment directly.
Ŗ Almost all the settings can only be done meanwhile the UPS
is on bypass mode.
6.4. Special
functions
The UPS has some special functions, that could satisfy a special
application of the user.
In case you require any of these special functionalists, contact
with the S.T.S. to change the standard configuration from factory.
6.3.5. Control
submenu.
Ŗ When pressing the key the key
for less than 1 sec. from
this "Control" submenu, it is accessed to the control structure
(see figure 37 depending on the power rate of the model).
Ŗ The acoustic alarm can be activated or deactivated from this
menu. Any new alarm, will activate the own acoustic alarm.
Ŗ Battery test: It is a control command of the UPS , to make a
battery test of the equipment. It is also possible to do it in the
0,7 to 3kVA units manually (see section 6.1).
Ŗ By means of the "Loads segments" menu, the IEC outlets
group stated as "LS1" and/or "LS2"can be activated "On" or
deactivated "Off", so the UPS will supply or not voltage to the
connected loads respectively.
Also by means of the WinPower software, it is possible to
combine other functionality of this menu.
Ŗ EPO status cleared: When the EPO button is activated, the
UPS output breaks the supply, either if the configuration is
single or it is parallel and power supply to load/s is broken.
To restore the normal condition, the EPO button has to be
deactivated previously (close the circuit again) and enter into
the "Clear EPO status" submenu to clear the current status
of the EPO. Doing this the alarm of the UPS is cleared and
the output voltage is restored through the bypass (bypass
mode). The equipment recover the start up functionality with
its normal procedure. See figure 38 as an example.
Ŗ Error status cleared: When there is a fault in the UPS, the
fault and alarm mode is activated.
To restore the normal status, enter into this menu to clear the
error status. Doing this the alarm of the UPS is cleared and
the output voltage is restored through the bypass (bypass
mode). It is needed to check the cause and cancel it before
starting up the equipment again with its normal procedure.
Ŗ The event log clearance of the last events can be done
through this menu. But in lack of this the system logs in the
memory the las 50 events.
Ŗ Restore the preset configuration from factory: All values are
set to the preset values from factory. This action can only be
done on bypass mode.
Ŗ Shutdown of a single UPS (individual): It is a command to
shutdown the UPS that is running in a parallel system cur-
rently and other equipment of the system will supply the
load/s in the parallel system.
Press
< 1 sec.
Press
< 1 sec.
Press
o
< 1 sec.
(1)
(2)
(1) Blinking option.
(2) This option ends the blinking
once validated
Fig. 38. Example of screens of EPO status cleared.