Salus VS10BRF Installer's/user's Manual

Other manuals for VS10BRF: User Manual
Manual is about: 4 in 1 Digital Thermostat RF

Summary of VS10BRF

  • Page 1

    4 in 1 digital thermostat rf models: vs20wrf and vs20brf vs10wrf and vs10brf i n s t a l l e r / u s e r m a n u a l.

  • Page 2: Contents

    02 vs20wrf and vs20brf installer manual contents 1 x installer / user manual vs10wrf 4x aaa batteries vs20brf fixing screws contents box contents introduction product compliance system options overview installation parameter settings error codes user guide installers notes warranty box contents icon...

  • Page 3: Introduction

    Product compliance & safety information introduction thank you for purchasing the salus 4 in 1 room thermostat it must be used with the co10rf zigbee coordinator. The zigbee coordinator allows communication with other devices in the it600 rf system range. Other zigbee devices include wiring centre, ...

  • Page 4: Warning

    These instructions are applicable to the salus model stated on the front cover of this manual only. Warning this product must be fitted by a competent person, and installation must comply with the guidance, standards and regulations applicable to the city, country or state where the product is insta...

  • Page 5: Programmable Room

    Vs20wrf and vs20brf installer manual 05 system overview - configuration options programmable room thermostat (prt) * grouping and timer option only available when used with wiring centre. 1 ufh manifold wiring centre radiator boiler hot water trv towel rails group control thermostat* 2 group thermos...

  • Page 6: Group Control Thermostat

    System overview - configuration options 06 vs20wrf and vs20brf installer manual programmable room thermostat (prt) when configured for prt (see page 32) it mainly works by itself and allows the user to have separate time and temperature control of each zone on the wiring centre, radiator valve or sy...

  • Page 7

    System overview - zigbee coordinator vs20wrf and vs20brf installer manual 07 zigbee coordinator required for communication between these devices. System overview kl10rf rx10rf co10rf wbtrv10rf wbtrv10rfm kl08rf vs10 / vs20rf.

  • Page 8

    08 vs20wrf and vs20brf installer manual system overview - it600 system the thermostat can communicate with all these it600 devices. System receiver configured to boiler receiver. Refer to system receiver manual rx10rf. System receiver configured to one room receiver rx2. Refer to system receiver rx1...

  • Page 9

    System overview - hot water option unit configured to hot water timer. When the unit is configured as a hot water timer (see page 32) there are two methods of connecting the cylinder thermostat. Cylinder thermostat options 1 connected direct to wc (default) 2 connected direct to vs10/20rf (requires ...

  • Page 10

    System overview - hot water option 1 connected direct to wc (default) for convenience there is a unique built in option allowing the cylinder thermostat to be connected to either the hw timer or wiring centre. Please refer to note 1 on wiring centre guide and pages 15 and 20 for more information. 10...

  • Page 11

    Vs20wrf and vs20brf installer manual 11 installation – thermostat mounting not to be positioned on an exterior wall. For your benefit symbol to ensure trouble free operation and efficient control. The room thermostat nea is best positioned behind a door and at 130cm from the floor. (pic) do not posi...

  • Page 12

    12 vs20wrf and vs20brf installer manual carefully remove the front housing. Installation – thermostat mounting vs20wrf 1 3 2 60mm.

  • Page 13: Sensor Terminals

    Installation – terminal connections vs20wrf understanding your terminal connections rear of unit sensor terminals can be used for external air, floor sensor when configured as thermostat. Can also be used for cylinder thermostat when configured for hw. See page 57. 1 1 vs20wrf and vs20brf installer ...

  • Page 14: Note:

    Installation – thermostat external sensor vs20wrf note: if you are using an external sensor, the unit has to be configured for external air sensor or floor protection sensor please see device parameter setting page 57. Salus external sensor (sold separately) 14 vs20wrf and vs20brf installer manual.

  • Page 15: Note:

    Installation – hot water timer cylinder thermostat vs20wrf note: the unit can be configured for cylinder thermostat or connected to the hot water timer. Please see device parameters page 57. For additional wiring centre information refer to note 1 on wiring centre guide. Hw timer connected cylinder ...

  • Page 16: Note:

    Installation – thermostat mounting vs20wrf 1 2 3 4 once you have connected your choice of external sensor (if applicable) insert batteries note: please proceed to page 23 16 vs20wrf and vs20brf installer manual.

  • Page 17

    Carefully remove the front housing. 1 3 2 installation – thermostat mounting vs10wrf 60mm vs20wrf and vs20brf installer manual 17 installation.

  • Page 18: Power Terminals 110 Vac

    Installation – terminal connections vs10wrf understanding your terminal connections rear of unit power terminals 110 vac used for supplying power to the unit. 110v supply can be sourced from the wiring centre or any convenient source. Sensor terminals can be used for external air, floor sensor when ...

  • Page 19: Note:

    Installation – thermostat external sensor vs10wrf note: if you are using an external sensor, the unit has to be configured for external air sensor or floor protection sensor please see device parameter setting page 57. Vs20wrf and vs20brf installer manual 19 salus external sensor (sold separately) i...

  • Page 20: Note:

    Installation – hot water timer cylinder thermostat vs10wrf note: the unit can be configured for cylinder thermostat or connected to the hot water timer. Please see device parameters page 57. For additional wiring centre information refer to note 1 on wiring centre guide. Hw timer connected cylinder ...

  • Page 21

    Installation – thermostat mounting vs10rf check that the wiring is completed for: 1 2 please use the screws provided ensure the orientation arrow is pointing upwards. Power terminals sensor terminals (if applicable) you are ready to secure the rear housing to the wall box vs20wrf and vs20brf install...

  • Page 22

    Installation – thermostat mounting 1 fit the front housing to the rear housing align the front housing at the bottom edge. 2 lightly press until you hear a positive click. Ensure the pin connections are aligned 22 vs20wrf and vs20brf installer manual.

  • Page 23: Box

    Installation – lcd graphics icon function box means to select the mode e.G. Means the current setpoint is hi temp, means the hi temp is not selected. Sunny: hi comfortable temperature. Cloudy: middle comfortable temperature. Moon: low comfortable temperature. Programmable thermostat program mode ind...

  • Page 24: Heat Indicator:

    Installation – lcd graphics icon function heat indicator: indicates heat is required. Cool mode indicator: indicates cooling is required (if applicable) temperature indicator: display the room temperature. Display the set-temp. Also used to show the other information. Temporary manual override indic...

  • Page 25: Hot Water (Hw) Indicator:

    Installation – lcd graphics icon function hot water (hw) indicator: unit has been configured for hw timer. Hot water (hw) indicator: indicates that there is hot water demand. Hw program mode indicator: indicates program is running. Hw mode indicator: mode for 1 period of hw a day, from program 1 on ...

  • Page 26: Floor Sensor Probe Indicator

    Installation – lcd graphics icon function floor sensor probe indicator show only when air + floor sensor is connected. Floor sensor probe flashing indicates that heating of the zone has been halted to protect the floor from over-heating. Low battery indicator: batteries need to be replaced. Setting ...

  • Page 27

    Installation – user interface key function 1. Increase or decrease setpoint temperature. 2. Increase or decrease day, clock, timer, party, holiday and boost. 3. Select installer parameter value. 1. Mode selection. 2. Long press to return to home display without saving. 3. Short press to return to th...

  • Page 28

    Installation - graphics key 28 vs20wrf and vs20brf installer manual press once press x amount of times hold for five seconds flashing xx short press to save and long press to save and exit short press to back up.

  • Page 29

    Installation – first power up vs20wrf and vs20brf installer manual 29 installation the following screens show examples only mcu software version will be shown zigbee software version will be shown *please note that 88.8 and 8.8 are a reference to the software version..

  • Page 30: System Setup Checklist

    Installation - system setup system setup checklist 1 the zigbee coordinator must be in pairing mode. Before starting the pairing, make sure the light is flashing on the coordinator by holding the button for 5 seconds. For more information refer to the coordinator instruction manual. 2 the device tha...

  • Page 31: Function

    Vs20wrf and vs20brf installer manual 31 you are now ready to configure the unit using the system parameter table below. Note: this unit is already pre-configured as a programmable thermostat. To configure this differently refer to table below and instructions on following pages. Function system sett...

  • Page 32

    Installation – system parameters if the pre-configured program is not suitable for your application, hold down the bottom three keys for a short time, until the display shows sel prog. 32 vs20wrf and vs20brf installer manual.

  • Page 33: Selecting What Type of Unit

    Installation - system setup selecting what type of unit selecting what unit to pair with use or to select the type of unit. After selection has been made, press to confirm. Prog dgt wtr wiring centre. Page 33 radiator valve. Page 37 system receiver configured rx2. Page 41 system receiver only config...

  • Page 34: Checklist

    Installation - pairing with wiring centre wiring centre checklist 1 the zigbee coordinator must be in pairing mode. Hold the button for five seconds until it flashed red. 2 ensure the wiring centre and optional system receiver (configured to rx1) for remote boiler switch are powered up. Note: the wi...

  • Page 35

    Installation - pairing with wiring centre use to select the wiring centre number to pair with. If you are using groups, use to select group number of each group required. If unit is stand alone then please select -- group 1 group 2 1 3 5 2 4 6 pairing with wc vs20wrf and vs20brf installer manual 35.

  • Page 36

    Installation - pairing with wiring centre use or to select the wiring centre zone number 1 to 8. If you add a kl04rf to your kl08rf you will be able to add up to 12 zones. Zone number 36 vs20wrf and vs20brf installer manual.

  • Page 37

    Installation - testing the pairing with the rf wc n l n l supplied cables 230v to ufh pump underfloor heating manifold 1.5mm cable (installer supplied) external power supply optional boiler connection heat / cool changeover (open = heat, closed = cool) dew point sensor n l n l supplied cables 230v t...

  • Page 38: Checklist

    Installation - pairing the radiator valve(s) radiator valves checklist 1 the zigbee coordinator must be in pairing mode. Hold the button for five seconds until it flashed red. 2 ensure that the radiator valves are in pairing mode (refer to trv manual). A maximum of 6 radiator valves can be used with...

  • Page 39

    Installation - pairing with radiator valve tap to start the pairing process. 5 1 3 2 4 6 pairing with trv vs20wrf and vs20brf installer manual 39.

  • Page 40

    Installation - pairing with the radiator valve once all trv’s have paired press if you use the maximum number of trvs it will automatically take you to the mainscreen. The pre fix number on the trv will change as the trv(s) pair. 1 3 2 4 40 vs20wrf and vs20brf installer manual.

  • Page 41

    Installation - testing rf pairing use to increase temperature to 30ºc and then press use to decrease temperature to 10ºc and then press if you are using the optional system receiver configured to rx1 please check that the green light goes on when the temperature is raised and off when reduced. For m...

  • Page 42: Checklist

    Installation - pairing with system receiver rx2 system receiver configured to rx2 single room receiver. Checklist 1 the coordinator must be in pairing mode. Hold the button for five seconds until it flashed red. 2 the system receiver (rx2) is powered up and the red led will flash when the pairing is...

  • Page 43

    Installation - pairing with system receiver rx2 4 5 1 3 2 6 pairing with rx2 vs20wrf and vs20brf installer manual 43.

  • Page 44

    Installation - testing pairing with system receiver rx2 use to increase temperature to 30ºc and then press green led on green led off use to decrease temperature to 10ºc and then press if you are using the optional system receiver configured to rx1 please check that the green light goes on when the ...

  • Page 45: Checklist

    Installation - pairing with system receiver rx1 only checklist 1 the coordinator must be in pairing mode. 2 the system receiver (configured to rx1) is powered up and the red led will flash when the pairing is in process and will be steady when the pairing is complete. System receiver configured to b...

  • Page 46

    Installation - pairing with system receiver rx1 only 5 1 3 4 2 6 46 vs20wrf and vs20brf installer manual.

  • Page 47

    Installation - testing pairing with system receiver rx1 only use to increase temperature to 30ºc and then press green led on green led off if pairing for your system is complete, please take the coordinator out of pair mode. Press for 5 seconds and light will stop flashing. Use to decrease temperatu...

  • Page 48

    Installation - modifying system parameters if you have made an error or need to change your system parameters please follow steps below. This should only be done by your installer. Press all three buttons simultaneously 48 vs20wrf and vs20brf installer manual.

  • Page 49

    Unit will follow power up sequence on page 29. You are now ready to enter or change your system parameters. Refer to page 31. Installation - modifying system parameters installation vs20wrf and vs20brf installer manual 49.

  • Page 50

    Press again for 1 second to cancel identify. Identify mode will time out after 10 minutes. To check that the complete system is communicating and has been configured correctly, you can use identify mode. Using identify from the coordinator will show all products that are connected to your system. In...

  • Page 51

    Installation - checking system configuration prt press tick to cancel identify. Identify mode will time out after 10 minutes. To check that the relevant system is communicating and has been configured correctly, you can use identify mode. Prt system has no grouping prt prt prt prt please follow step...

  • Page 52

    Please follow step 1 on page 47. When in identify mode all receivers, group thermostats and the coordinator will flash. Group control thermostat system has grouping prt group control thermostat group thermostat group thermostat group thermostat press tick to cancel identify. Identify mode will time ...

  • Page 53

    Group thermostat system has grouping prt please follow step 1 on page 47. When in identify mode all receivers, control group thermostat and the coordinator will flash. Group control thermostat group thermostat group thermostat group thermostat press tick to cancel identify. Identify mode will time o...

  • Page 54

    Press again for 5 second to cancel identify. Identify mode will time out after 10 minutes. To check that the complete system is communicating and has been configured correctly, you can use identify mode. Using identify from the wiring centre will show all products that are connected to your wiring c...

  • Page 55

    Installation - checking system configuration prt system has no grouping press tick to cancel identify. Identify mode will time out after 10 minutes. To check that the relevant system is communicating and has been configured correctly, you can use identify mode. Prt prt prt prt please follow step 1 o...

  • Page 56

    Installation - replacing product deleting wiring centre from the network. Press for 15 seconds to delete the wiring centre from the network. All led’s will flash momentarily and then the wiring centre will be deleted from the network. All thermostats relating to the wiring centre will need to be rec...

  • Page 57

    Installation - replacing product before replacing any device it must be removed from the zigbee network. Please ensure the zigbee coordinator is also in pairing mode. Note: if replacing a thermostat connected to the wiring centre, you can use the replacement method. Deleting thermostat from the netw...

  • Page 58

    If you have made an error or need to change your system parameters please follow steps below. This should only be done by your installer. Press all three buttons simultaneously 1 3 4 2 installation - modifying device parameters 58 vs20wrf and vs20brf installer manual.

  • Page 59: Note:

    Installation - modifying device parameters press repeatedly until you reach the d01 screen. Note: you can see the installer mode parameters on page 58 in the manual. *please note that x=1,2, 3 or any ° c value. 5 6 installation vs20wrf and vs20brf installer manual 59.

  • Page 60: Function

    Installation - device parameters dx function system setting definition default d01 heating 0 pulse width modulation control 1* on-off 0.5 deg c +/- 0.25 deg c 0 2 on-off 1.0 deg c +/- 0.5 deg c d02 room -3.0 to 3.0 temperature offset from temperature deg c measured temperature to 0 deg c offset comp...

  • Page 61: Function

    Installation - device parameters continued dx function system setting definition default d07 valve protection 0 disable 1 1 enable d08 frost set point 5-17 deg c required temperature for frost 5 deg temperature protection and holiday mode d09 hour format 0 12 1 1 24 d10 n/a n/a n/a n/a d11 daylight ...

  • Page 62

    Installation - error codes error code prog non-prog hw 01 comm connection link failure comm connection link failure comm connection link failure 02 floor sensor: overheated or overcooled floor sensor: overheated or overcooled comm connection link failure 03 floor sensor open floor sensor open - 04 f...

  • Page 63: Error Code

    Installation - error codes installation error code prog non-prog hw 10 wc lost link with hot water timer wc lost link with hot water timer wc lost link with hot water timer (displayed on all relevant thermostats (displayed on all relevant thermostats (displayed on all relevant thermostats and also h...

  • Page 64

    Installation - error codes error code prog non-prog hw 25 26 27 28 29 thermostat lost link with parent (including any it600 device) wc lost link with zone 9 prog/ non-prog thermostat (displayed on all connected thermostats) wc lost link with zone 10 prog/ non-prog thermostat (displayed on all connec...

  • Page 65: Error Code

    Error code prog non-prog hw 30 31 32 33 installation - error codes installation trv gear issue trv adaptation issue reserved for future use receiver lost link with devices trv gear issue trv adaptation issue reserved for future use receiver lost link with devices - - reserved for future use receiver...

  • Page 66: Model

    Installation - technical detail model vs10rf / vs20rf type electronic programmable room thermostat, digital room thermostat and hot water rf programming modes user selectable for 5/2, all and individual day options program number 1-6 selectable modes party, vacation, program and frost override perma...

  • Page 67

    User guide - setting time and date prt and group control thermostat user guide vs20wrf and vs20brf installer manual 67.

  • Page 68

    User guide - setting time and date use left to select 12 hour and right to select 24 hour. Adjust the time using the up or down arrow key. Prt and group control thermostat hour minutes 68 vs20wrf and vs20brf installer manual.

  • Page 69

    User guide - setting time and date prt and group control thermostat month year day user guide adjust the year/month/ day using the up or down arrow key. Vs20wrf and vs20brf installer manual 69.

  • Page 70: Typically 21 Deg C

    User guide - understanding temperature levels heating highest temperature typically used for early morning and early evening. Typically 21 deg c mid temperature typically used for times of day when you are active around the home typically 19 deg c lower temperature typically used for unoccupied or s...

  • Page 71

    User guide - understanding temperature levels cooling occupied temperature. Typically 22ºc unoccupied temperature typically 40ºc this avoids cooling being active when the property is unoccupied. Evening temperature typically 24ºc your thermostat comes preset for the above temperatures. These can be ...

  • Page 72

    User guide - default heating schedule monday to friday 22 19 17 12.00 7.00 9.00 17.00 23.00 22 19 17 12.00 8.00 9.00 17.00 23.00 saturday to sunday prt and group control thermostat if using grouping, the schedule from the group control thermostat will be applied to group members. 72 vs20wrf and vs20...

  • Page 73

    User guide - default cooling schedule 22 40 24 12.00 7.00 9.00 17.00 23.00 monday to friday 22 40 24 12.00 8.00 9.00 17.00 23.00 saturday to sunday prt and group control thermostat if using grouping, the schedule from the group control thermostat will be applied to group members. User guide vs20wrf ...

  • Page 74

    User guide - graphics key press once press x amount of times hold for five seconds flashing xx short press to save and long press to save and exit short press to back up 74 vs20wrf and vs20brf installer manual.

  • Page 75

    User guide - setting required temp levels by setting the low temperature the program schedule will use this as the low setting. The temperature set are applicable to the individual thermostat. Prt, group control thermostat and group thermostat setting the low temperature user guide vs20wrf and vs20b...

  • Page 76

    User guide - setting required temp levels repeat for by setting the low temperature the programs will use this as the low setting. The temperature set are applicable to the individual thermostat. Prt, group control thermostat and group thermostat move back to once temperature levels have been chosen...

  • Page 77

    User guide – setting the temperature schedule use right and left to select the day of the programs. 5/2 7 days individual if using grouping, the schedule from the group control thermostat will be applied to group members. User guide vs20wrf and vs20brf installer manual 77.

  • Page 78

    User guide – setting the temperature schedule adjust the time using the up or down arrow key. Use right and left to select the hi/mid or low temp. 78 vs20wrf and vs20brf installer manual.

  • Page 79

    User guide – setting the temperature schedule to remove a program out set the time to --:--. When you set the temperature the schedule will respond to those temperatures see page 71 on how to change repeat through to program 4. If you require a 5th or 6th program enter a time and select your tempera...

  • Page 80

    User guide - temporary override use the up or down arrow key to view your program set temperature. The temporary override is applicable to the thermostat being changed only. Use the up or down arrow key to adjust the temperature to the setting you desire. Temporary override allows you to increase th...

  • Page 81

    User guide - temporary override to cancel temporary override press or see below. Prt, group control thermostat and group thermostat confirm the temporary set temperature. User guide vs20wrf and vs20brf installer manual 81.

  • Page 82

    User guide - permanent override permanent override in a control group thermostat will also affect the group thermostats unless they are removed from the group. See page 64. To cancel permanent override select see below. Use the up or down arrow key to view your set temperature. See page 71. To adjus...

  • Page 83

    User guide - party mode the party mode is an option that enables temperature for a period of time you select up to 9hr 50min. Use the right arrow to select the party mode. Use the up arrow to select the hr/min. Press tick to confirm and it will start to count down . Party mode set in a control group...

  • Page 84

    User guide - holiday mode use the right arrow to select the holiday mode. Use the up arrow to select how many days to be off for . Press tick to confirm and it will start the holiday count down. Holiday set in a control group thermostat will also affect group thermostats unless they are removed from...

  • Page 85

    User guide - frost protection use the right arrow to select the frost mode. Use the up arrow to select the frost protection temperature. Press tick to confirm the temperature that has been set to. Frost protection set in a control group thermostat will also affect group thermostats unless they are r...

  • Page 86

    User guide - group thermostat overview when a group thermostat is in it will follow the mode status of the group control thermostat. When a group thermostat is in and the group control thermostat is in or then the group thermostat will follow this mode. Or will be displayed. The group thermostat has...

  • Page 87

    User guide - group thermostat overview the group thermostat has now left the group and is in permanent to adjust the set temperature, please refer to page 71. The group thermostat has now left the group and is in permanent to adjust the set temperature, please refer to page 71. The group thermostat ...

  • Page 88: Mode Selection

    User guide - hot water (optional) mode selection 2 3 mode selection when is selected, the hot water timer will follow the program schedule. See page 86. Hot water will be on once per day. Hot water will be continuously on. Hot water will be continuously off. Hot water will follow holiday mode from t...

  • Page 89

    User guide - hot water boost user guide vs20wrf and vs20brf installer manual 89.

  • Page 90

    User guide - default hot water schedule 12.00 6.00 8.00 18.00 22.00 on on off off off 12.00 6.00 8.00 18.00 22.00 saturday and sunday monday to friday on on off off off your hot water timer comes preset with the times below. These can be adjusted. See next page. 90 vs20wrf and vs20brf installer manu...

  • Page 91

    User guide - setting hot water times 5/2 7 days individual user guide vs20wrf and vs20brf installer manual 91.

  • Page 92

    User guide - setting hot water times repeat these steps for programs 92 vs20wrf and vs20brf installer manual.

  • Page 93

    User guide - setting hot water times user guide repeat these steps for programs vs20wrf and vs20brf installer manual 93.

  • Page 94

    Installer notes 94 vs20wrf and vs20brf installer manual.

  • Page 95

    Salus controls warrants that this product will be free from any defect in materials or workmanship, and shall perform in accordance with its specification, for a period of five years from the date of installation. Salus controls sole liability for breach of this warranty will be (at its option) to r...

  • Page 96: Salus North America

    Www.Salusna.Com salus north america 850 main street redwood city ca 94063 t: +1-650-360-1725 e: sales@salusna.Com for pdf installation guide please go to www.Salus-controls.Com maintaining a policy of continuous product development salus controls plc reserve the right to change specification, design...