seCtIOn 10 |
Protections
The inverter has been provided with protections detailed below:
overload / Short circuit Shut Down
Theinvertercanprovideahigherthannormalinstantaneouspower(<1second)limited
tothesurgepowerratingoftheinverter.Also,theinvertercanprovidecontinuous
power limited to the continuous power rating of the inverter. If there is an overload
beyondthesespecifiedlimits,theACoutputoftheunitwillbeshutdownpermanently.
StatusLED(2)willturnoRANGE,theGREENindicationontheGfCIwillbeoffand
buzzer alarm will sound. The unit will be latched in this shutdown condition and will
requiremanualreset.Toreset,switchoff the power oN/offswitch,waitfor3min-
utes and then switch oN again. before switching oNagain,removethecauseofthe
shutdown.
Warning Alarm - Low Dc input Voltage
ThevoltageattheDCinputterminalswillbelowerthanthevoltageatthebatteryter-
minals due to voltage drop in the battery wires and connectors. The drop in the voltage
attheDCinputterminalsoftheinvertercouldbeduetolowerbatteryvoltageordue
toabnormallyhighdropinthebatterywiresifthewiresarenotthickenough(Please
External Fuse Sizes”).IfthevoltageattheDCinputterminalsfallsbelow10.5Vfor12V
versionsor21.0Vfor24Vversions,abuzzeralarmwillbesounded.TheStatusLED(2)
andindicationlightontheGfCIwillcontinuetobeGREENandtheACoutputvoltage
would continue to be available. This warning buzzer alarm indicates that the battery
is running low and that the inverter will be shut down after sometime if the voltage at
theinverterterminalsfurtherdropsto10Vfor12Vversionsor20Vfor24Vversions.
Low Dc input Voltage Shut Down
IfthevoltageattheDCinputterminalsfallsbelow10Vfor12Vversionsor20Vfor24V
versions,theACoutputisshutdown.BuzzeralarmissoundedandtheStatusLED(2)
willturnoRANGE.TheGREENindicationlightontheGfCIwillbeoff.
TheunitwillresetautomaticallywhentheDCinputvoltagerises>11.5Vfor12Vver-
sionsand>23Vfor24Vversions
High Dc input Voltage Shutdown
IfthevoltageattheDCinputterminalsexceeds16.5Vfor12Vversionsor33Vfor
24Vversions,theinverterwillbeshutdowntemporarily.TheStatusLED(2)willturn
oRANGEandtherewillbebuzzeralarm.TheGREENindicatorlightontheGfCIwillbe
off.Theunitwillberesetautomaticallywhenthevoltagedropsdownto<16.5Vfor
12Vversionsandto<33Vfor24Vversions.
over-temperature Shut Down
In case of failure of the cooling fan or in the case of inadequate heat removal due to
higherambienttemperatures/insufficientairexchange,thetemperatureinsidetheunit