Samlexpower SAM-250-12 Owner's Manual - Section 6 |
16 | SAMLEX AMERICA INC.
SAMLEX AMERICA INC. | 17
operating
condition/
protection
threshold/
reason
Green
LeD (5,
power)
yeLLoW
LeD (6,
input
fault)
reD
LeD (4,
fault)
Buzzer
remedy/reset
No output due
to Over Load
Shut Down
Output power
is > Continu-
ous / Surge
Rating
ON
OFF
ON
OFF
Check starting surge rating
of load. If happens with low
power CFL or SMPS, try adding
small resistive load.
If happens when inverter
is switched ON with high
capacitance load already in ON
condition, try switching ON the
load 10 sec after the inverter
has been switched ON.
Manual Reset. Unit will latch in
shut down condition. To reset,
switch OFF the ON/OFF Switch,
wait for 3 minutes and switch
ON again.
No output due
to Ground Fault
Shut Down
Neutral or
Line con-
nected to
Ground
ON
OFF
ON
OFF
Check if there is Neutral to
Ground bond or Ground Fault.
Manual Reset. Unit will latch in
shut down condition. To reset,
switch OFF the ON/OFF Switch,
wait for 3 minutes and switch
ON again.
No output
No DC Input
Voltage due
to Blown DC
Input Fuse
OFF
OFF
OFF
OFF
Check 8A fuse in the 12V
Power Plug or in the battery
input line.
SECTION 6 |
Protections Monitoring
& Troubleshooting