Samlexpower SEC-1245A Owner's Manual

Other manuals for SEC-1245A: Owner's Manual, Owner's Manual
Manual is about: AUTOMATIC BATTERY CHARGER

Summary of SEC-1245A

  • Page 1

    Sec - 1245a sec - 2425a models automatic battery charger owner’s manual please read this manual before operating your charger.

  • Page 2

    Important safety precautions............................................................2 description.......................................................................................3 features............................................................................................3 componen...

  • Page 3

    Important safety precautions hazardous conditions may result if the charger is not installed or operated correctly. Please read the following instructions to prevent personal injury or damage to the charger battery related • to reduce the risk of battery explosion, follow these instructions and thos...

  • Page 4

    Description sec-1245a (for 12 v batteries) and sec-2425a (for 24 v batteries) are high current, 3 stage chargers that deliver 45 a and 25 a respectively for almost 75% to 80% of the charging cycle ensuring a very fast, safe and complete charging of lead acid batteries. The nomenclature “ i uo u” is ...

  • Page 5

    Components and accessories 1. Output connnector + bank 1 2. Output connector + bank 2 3. Output connector - common 4. Charging indicator led 5. Dip switches for mode selection 6. Jack for remote panel 7. Push switch for mute mode 8. Led for mute mode indication 9. Ac input power on / off switch 10. ...

  • Page 6

    Specifying lead acid batteries and chargers flooded / wet cell and sla (sealed lead acid) batteries there are two categories of lead acid batteries – flooded/wet cell and sealed lead acid (sla). A flooded/wet cell battery has a high tolerance to overcharging. However, it will release hydrogen gas wh...

  • Page 7

    Tteries reduction in usable capacity at higher discharge rates. As stated above, the rated capacity of the battery in ah is applicable at a discharge rate of 20 hours. As the discharge rate is increased, the usable capacity reduces due to “peukert effect”. This relationship is not linear but is more...

  • Page 8

    Depth of discharge and battery life the more deeply a battery is discharged on each cycle, the shorter the battery life. Using more batteries than the minimum required will result in longer life for the battery bank. A typical cycle life chart is given at table 2 below: table 2. – typical cycle life...

  • Page 9

    Charging batteries the batteries can be charged by using good quality ac powered battery charger or from alternative energy sources like solar panels, wind or hydro systems. Make sure an appropriate battery charge controller is used. It is recommended that the batteries may not be charged at current...

  • Page 10

    Charging stages note! - voltage reading on no load . The output terminals of the charger consist of one common white / black negative terminal (3) and two red positive terminals (1, 2) for charging two banks of batteries. Each of the two positive terminals of the two banks has a schottky diode in se...

  • Page 11

    Battery voltages – charged and discharged conditions the cell voltage of a battery depends upon the temperature of the battery and has a negative temperature coefficient – the voltage level increases at lower temperature and decreases at higher temperature. The voltages are normally specified at 80º...

  • Page 12

    Stage 2 - constant overcharge voltage, timed absorption / boost charge mode (uo phase): when the charger enters stage 2 from stage 1, the battery is approximately 70% to 80% recharged. As soon as it enters this stage, a timer circuit is also initiated. The timer circuit can be selected to operate fo...

  • Page 13

    Caution! 3 stage charging is recommended for charging stand-alone unloaded batteries (there is no load connected to the battery when it is being charged). If a load is also connected simultaneously, a part of the charger’s output current will be diverted to this load. Thus, the charger may remain lo...

  • Page 14

    Protection the charger has the following protections: short circuit shut down in case of a short circuit on the output side, the output of the charger will be shut down. The charging indication led (4) on the front panel will turn red (on the remote panel (15), the red led “i phase” will light, the ...

  • Page 15

    Installation location, mounting and safety the charger is required to be installed in a safe, well ventilated and dry location. Please see the details given under “important safety precautions” the charger can be mounted horizontally or vertically. When mounting vertically, please ensure that the ax...

  • Page 16

    Preparing the charger for operation ac input connection the charger is pre-set to operate from input ac voltage of 120 vac, 60 hz and is provided with a 6 ft attached cord with molded nema5-15p plug. Please ensure that the ac outlet is 2 pole, 3 wire grounding type – “nema5-15r” connecting the batte...

  • Page 17

    Selecting the type of battery and charging stages the float or maintenance charge mode (u phase) voltage and absorption / boost charge mode (uo phase) voltage of different types of lead acid batteries are different. 3 stage charging (stages 1, 2 and 3) is recommended when charging stand alone, unloa...

  • Page 18

    Dip switch setting for sec-2425a s1 s2 float boost battery type charging stages stand-alone charging off * on * 27 v * 28.8 v * flooded / agm * 3 stages (stages 1, 2, 3) on off 27 v 28.0 v gel cell 3 stages (stages 1, 2, 3) charging loaded battery or charging two banks and the batteries in the two b...

  • Page 19

    Reducing maximum charging current capacity to charge lower capacity batteries “mute mode” can also be selected to reduce the maximum charging capacity to approxi- mately 1/3 of rated capacity of the charger. This can be used to safely charge lower capacity batteries batteries should not be charged a...

  • Page 20

    Remote panel - model no. 900-rc an optional wired remote panel model no. 900-rc (15) can be ordered. It comes with 10 metres of flat ribbon cable (14) that has 8 position modular male connector on either end. The remote panel (15) can be used to switch on / switch off the charger and also monitor th...

  • Page 21

    Operation switching on / off the charger is switched on /off with the illuminated ac input power on / off switch (9) located on the rear panel of the unit. The switch is illuminated red when switched on. Indication of normal operation and charging status when the charger is switched on without any l...

  • Page 22

    Charging a battery installed in a vehicle follow these steps when the battery is installed in a vehicle. A spark near a battery may cause battery explosion. For safety and to reduce the risk of spark near the battery: 1. Position ac and dc cords to reduce risk of damage by hood, door or moving engin...

  • Page 23

    Powering other dc loads the charger can be used as a power supply or as a dc ups (dc un-interruptible power supply. For both these applications, first set switches s1 and s2 of dip switch (5) to off position to set the charger to work in 2 stage mode (see under “selecting the type of battery and cha...

  • Page 24

    Troubleshooting the symptoms of abnormal operation and the possible cause(s) and remedies are given in the succeeding paragraphs. There is no output. The ac power on / off switch (9) does not illuminate when switched on. The charging indicator led (4) is off (on the remote panel (15), the green led ...

  • Page 25

    When the charger is powered and is being used as a dc power supply / ups, the output voltage drops when the dc load is switched on or increased. The charger is being forced into current limit condition the load is trying to draw current more than the current limit value of the charger – 45 a for sec...

  • Page 26

    The battery is taking excessively long time to fully recharge or when the charger is powered and is being used as a dc power supply / ups, the output voltage drops at lower dc load currents the unit is in mute mode. (green led (8) located on the bottom left corner of the front panel of the unit is l...

  • Page 27

    Specifications parameter sec-1245a sec-2425a nominal input voltage 120 vac, 60 hz 120 vac, 60 hz input voltage range 110 vac to 125 vac 110 vac to 125 vac output voltage, vdc - absorption / boost, uo* 14.4* v or 14* v or 28.8* v or 28* v or disabled* disabled* - float / maintenance, u* 13.5* v 27.0*...

  • Page 28

    Warranty information 2 year limited warranty sec-1245a / sec-2425a battery chargers manufactured by samlex america, inc. ( the “ warrantor ” ) are warranted to be free from defects in workmanship and materials under normal use and service. This warranty is in effect for 2 years from the date of purc...

  • Page 29

    Notes.

  • Page 30

    Attach receipt.

  • Page 31