Samplex America PSE-1260A Owner's Manual - page 6
PROBLEM
POSSIBLE CAUSE
SOLUTION
& SYMPTOMS
Low battery alarm
Poor DC wiring, poor
Use proper wire
is on all the time.
battery condition.
and make solid
There is output.
connections.
Battery voltage is
Use a new,
below 10.7V.
charged battery.
No output voltage.
Thermal shut-down
Allow the inverter to cool down.
Audible alarm is
due to prolonged overload.
Reduce load if continuous
on and load is in
operation is required, check fan is
excess of 600 Watts.
working.
No output voltage.
Thermal shut-down due to poor
Improve ventilation.
Over-temp indicator
ventilation.
Make sure ventilation
on and load is less than
openings are not obstructed,
600 Watts.
reduce ambient temperature,
check fan is working.
No output voltage,
Short circuit or
Check AC wiring
Over-load
wiring error.
short circuit or
indicator on.
improper polarity.
Very high power load.
Remove load.
5
10
INSTALLATION
1. Where to install
The power inverter should be installed in a location that meets the following requirements:
a. Dry -Do not allow water to drip or splash in the inverter.
b. Cool - Ambient air temperature should be between 0
o
C and 40
o
C, the cooler the better.
c. Ventilated - Allow at least one inch of clearance around the inverter for air flow. Ensure the
ventilation openings on the rear and bottom of the unit are not obstructed.
d. Safe-Do not install the inverter in the same compartment as batteries or in any
compartment capable of storing flammable liquids such as gasoline.
2. Cables
DC to AC inverters convert high amperage/low voltage DC power to low amperage/high voltage AC
power. To operate properly connect inverter DC input terminals direct to battery with heaviest
wire available. See chart below :
Max Watts Out
Approx. Amps Required
Wire Gauge
100W
1O Amps
#18
150W
15 Amps
#14
200W
20 Amps
#12
300W
30 Amps
#10
400W
40 Amps
# 8
600W
60 Amps
# 6