Samson FOUNDATION 3730-5 Configuration Manual

Manual is about: Electropneumatic Positioner Series 3730

Summary of FOUNDATION 3730-5

  • Page 1

    Series 3730 electropneumatic positioner type 3730-5 configuration and operation over f oundation™ fieldbus configuration manual kh 8384-5 en firmware version k 2.04/r 1.55 edition october 2010 fig. 1 · configuration and operation over foundation™ fieldbus.

  • Page 2

    Note concerning this configuration manual the rotary pushbutton on the positioner allows the type 3730-5 positioner to be operated and configured on site. In addition, the settings can be performed over the f oundation fieldbus network or over the samson ssp interface. The mounting and operating ins...

  • Page 3

    Contents page 1 introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 2 principle of operation. . . . . . . . . . . . . . . . . . . . . . . . . . 7 2.1 application type . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 2.2 additional equipment . . . . . . . . . . . . . ....

  • Page 4

    Revisions of positioner firmware in comparison to previous versions previous new communication k 1.11 k 1.21 leakage sensor at binary input 2 the connection of a leakage sensor at binary input 2 (by selecting leakage sensor in config_binary_input2 parameter of the ao transducer block) causes: 4 info...

  • Page 5

    Revisions of positioner firmware in comparison to previous versions previous new k 1.24 bus_address parameter the bus address has the default setting of 248. Device type in the delivery state, the device is configured as a basic device. K 1.25 internal modifications k 2.01 additional function blocks...

  • Page 6: Introduction

    1 introduction this section is based upon: 4 fieldbus f oundation™ specification “function block application process part 1 – 3“ revision 1.7 (ff-890 to ff-892) 4 fieldbus f oundation™ specification “positioner transducer block“ revision 3.0 (ff-906) type 3730-5 positioner the microprocessor-control...

  • Page 7: Principle of Operation

    2 principle of operation the electropneumatic positioner is attached to pneumatic control valves. It is used to assign the valve position (controlled variable x) to the control signal (reference variable w). The input sig- nal received from a control system is compared to the travel or rotational an...

  • Page 8: 2.1

    As a standard feature, the positioner comes with a binary input used to signalize process infor- mation over the f oundation™ fieldbus network. The extended expertplus diagnostics are integrated into the positioner. They provide informa- tion on the positioner and generate diagnostic and status mess...

  • Page 9: 2.2

    2.2 additional equipment solenoid valve if the operating voltage for the solenoid valve (12) fails, the supply pressure for the i/p module is vented to the atmosphere. The positioner can no longer operate and the control valve moves to the fail-safe position determined by the actuator, regardless of...

  • Page 10: 2.3

    2.2.1 configuration using trovis-view software the positioner can be configured using the trovis-view configuration and operator inter- face software. The positioner is equipped with an additional digital serial interface to connect the rs-232 or usb port of the computer to the positioner over an ad...

  • Page 11: Fieldbus

    3 f oundation™ fieldbus block model f oundation™ fieldbus assigns all the functions and data of a device to different types of blocks. Each type of block has a different range of tasks to fulfill in the block model. The following types of blocks are implemented in the samson type 3730-5 positioner: ...

  • Page 12

    4 initialization and zero calibration of the positioner both an initialization and a zero calibration can be started over the xd_command parame- ter of the ao transducer block. The relevant parameters for a max/nom initialization and the diagnostic functions of expertplus are listed below (also refe...

  • Page 13: Resetting The Positioner

    5 resetting the positioner the start-up and diagnostic data (in code 36 std) can be reset over the xd_command (41) parameter of the ao transducer block. The resetting of the device data and the wiring of the function blocks to the values stipulated in the f oundation™ fieldbus specification are perf...

  • Page 14

    6 status classification and condensed state all status alarms are classified in the positioner to report an error that has occurred. The status classification can be changed over the following f oundation™ fieldbus parameters in the ao transducer block (ao trd): 4 error_option_init_failure (36): mas...

  • Page 15

    Parameters in the ao transducer block (ao trd) with another status for block errors. The fol- lowing classifications are possible: • no message • device needs maintenance soon • device needs maintenance now the block error (block_err) results from the summary of classified alarms that are active. Kh...

  • Page 16: 7.1

    7 foundation™ fieldbus parameters several parameters can only be modified in certain modes (see read/write capability in the pa- rameter description). In this case, not the actual mode is decisive, but the target mode. 7.1 resource block (res) the resource block contains all the data that identify t...

  • Page 17: 7.2

    7.2 transducer blocks transducer blocks link the function blocks to the input and output variables of a field device. For example, the di function blocks are linked to the physical binary inputs, an internal solenoid valve, the current valve position or the condensed state of the positioner. This li...

  • Page 18

    • move to fail-safe position • move to fault state value xd_fstate_val the ao transducer block (ao trd) can still set an output error in the ao function block. For this purpose, the following events to activate an output error can be configured in the alarm_options parameter: • no (never) • local ov...

  • Page 19

    Kh 8384-5 en 19 foundation™ fieldbus parameters mode=auto setfailsafepos ao fb cas_in readback mode control scaling fvr final_v alue signal_action characterization end position function characterization end position function mode=auto mode open/close final_v alue_d signal_action final_pos_v alue_d s...

  • Page 20: 7.3

    7.3 function blocks 7.3.1 analog output function block the ao function block processes an analog signal from an upstream block (e.G. Pid function block) to an output value that can be used for the downstream transducer block (e.G. Valve positioner). It contains scaling functions and ramp functions a...

  • Page 21

    • fstate_time defines the length of time that the ao block will wait to activate the fault state. Refer to page 88 for list of parameters. Kh 8384-5 en 21 foundation™ fieldbus parameters rcas_in cas_in readback pv out 100 % 0 % 0 °c pv_scale sp_lo_lim sp pv sp readback out xd_scale mode_blk sp_hi_li...

  • Page 22

    7.3.2 proportional integral derivative function block a pid function block contains the input channel processing, the proportional-integral-derivative (pid) control loop and the analog output channel processing. The configuration of the pid block (pid controller) depends on the automation task. Simp...

  • Page 23

    4 derivative component: in controlled systems with long delay times, e.G. In temperature control loops, it is better to use the derivative component rate of the controller. Using the derivative component rate, the output variable is calculated depending on the rate of change of the system de- viatio...

  • Page 24

    7.3.3 discrete output function block (do1 + do2) the do function block processes a discrete signal from an upstream function block and makes it available as a discrete reference variable out_d over the channel. Both do function blocks can be assigned to various applications over the select_do_1…2 pa...

  • Page 25

    • set local op. Write protection this command locks the local operation of the positioner (see also local_ op_ena pa- rameter of the res block). This state is indicated on the positioner display by a blinking 'ff' when code 3 is selected. • reset/stop diagnosis this application is able to implement ...

  • Page 26

    7.3.4 discrete input function block (di1 + di2) the di function block processes single discrete signals and makes them available to other func- tion blocks with the out_d parameter. The positioner has two di function blocks which provide the application options described below. The type of applicati...

  • Page 27

    0 no message 1 maintenance required 2 maintenance demanded 3 maintenance alarm 7 function check refer to page 117 for the list of parameters. Kh 8384-5 en 27 foundation™ fieldbus parameters bin2 mgv channel pos_d condensed state config_binary_input_2 simulate simulate_d optional invert filter pv_fti...

  • Page 28

    7.3.5 input selector function block the is function block is used to generate an output signal from maximum four input signal val- ues. The select_type parameter allows the selection criterion to be determined to select which one of the input values is to be placed at the output. The following possi...

  • Page 29

    7.3.6 multiple analog output function block the mai function block makes analog measured variables of the positioner available to the other analog function blocks at its outputs. The following measured variables can be issued to the eight outputs: • current valve position (final_position_value) • cu...

  • Page 30

    7.3.7 multiple analog output function block the mao function block currently still has no function within the positioner. It will serve to sup- port/use future diagnostic functions. Refer to page 129 for the list of parameters. 30 kh 8384-5 en foundation™ fieldbus parameters select_mao_in_1...8 in_1...

  • Page 31: 7.4

    7.4 other parameters 7.4.1 stale counter the stale counter serves to judge the quality of a process variable received over a configured cy- clic connection (publisher/subscriber connection). These connections are used to transfer the process variable wired amongst the various function blocks. For th...

  • Page 32: 7.5

    7.5 parameter lists legend the parameter index is written in parentheses after the parameter description in the following tables. Class of memory: s d n static parameter dynamic parameter non-volatile parameter read/write capability: (access): r w read capability write capability supported modes: ot...

  • Page 33: 7.5.1 Resource Block (Res)

    7.5.1 resource block (res) res: ack_options (38) storage class: s · read/write capability (r/w) · supported modes: o/a determines whether an alarm is to be automatically acknowledged in the resource block. • [undefined] · no selection • disc alm · write lock has been changed • block alm · block alar...

  • Page 34

    • device needs maintenance now · block alarm (block_alm) in resource block is activated. Note: the assignment of error or diagnostic messages to the desired function block is deter- mined over the error_option parameters in the transducer block. Res: bus_address (55) storage class: d · read capabili...

  • Page 35

    Res: dd_resource (9) storage class: s · read capability (r) specifies the resource that contains the device description file in the device. Note: if the device contains no device description, '0' is indicated. Res: dd_rev (13) storage class: s · read capability (r) specifies the revision number of t...

  • Page 36

    Res: fault_state (28) storage class: n · read capability (r) indicates the fault state of the analog output function block res: features (17) storage class: s · read capability (r) specifies the additionally supported resource block options, see features_sel. Res: features_sel (18) storage class: s ...

  • Page 37

    Kh 8384-5 en 37 foundation™ fieldbus parameters res: hw_revision (43) storage class: s · read capability (r) specifies the hardware revision number of the electronic/mechanical components. Res: itk_ver (41) storage class: s specifies the version of the interoperability tester used on certifying the ...

  • Page 38

    Res: mode_blk (5) storage class: n · read/write capability (r/w) · supported modes: o/a operating mode of the resource block: – target mode ® code 48 s0 – actual mode (read only) ® code 48 s1 – permitted mode – normal mode (read only) • auto · the execution of the function blocks (ao and pid) is ena...

  • Page 39

    Kh 8384-5 en 39 foundation™ fieldbus parameters res: select_usage_io (57) storage class: n · read/write capability (r/w) · supported mode: o select_di_1 · used to select the data to be processed in di1 function block. • [5-30 vdc] · state of the standard binary contact be1 (terminals +87/–88) 0 inpu...

  • Page 40

    Select_do_1 · used to select the purpose of do1 function block • do1 o/c · open/close (on/off) application • [vst] · start vst (valve stroke test). See setting in the vst_mode parameter in ao trd. • reset diag · reset diagnosis (reset statistical information and tests, classification of status messa...

  • Page 41

    Select_mao_in_1 to select_mao_in_8 · signal processed over the input in_1…in_8 of of the mai function block • flow sensor • p1 · pressure p 1 • p2 · pressure p 2 • proc temp · process temperature default settings: [flow sensor] for select_mao_in_1, select_mao_in_5 [p1] for select_mao_in_2, select_ma...

  • Page 42

    Res: strategy (3) storage class: s · read/write capability (r/w) · supported modes: o/a permits strategic grouping and thus faster processing of blocks. • [0] blocks are grouped by entering the same number in the strategy parameter of each block. Note: these data are neither checked nor processed by...

  • Page 43

    Res: write_pri (39) storage class: s · read/write capability (r/w) · supported modes: o/a used to set the priority for the write_alm parameter. • [0] · the write-lock alarm is not processed. • 1 · the write-lock alarm is not broadcast to the fieldbus host system. • 2 · reserved for block alarms • 3 ...

  • Page 44

    Parameter index: resource block (res) 44 kh 8384-5 en foundation™ fieldbus parameters index parameter 0 – 1 st_rev 2 tag_desc 3 strategy 4 alert_key 5 mode_blk 6 block_err 7 rs_state 8 test_rw 9 dd_resource 10 manufac_id 11 dev_type 12 dev_rev 13 dd_rev 14 grant_deny 15 hard_types 16 restart 17 feat...

  • Page 45

    7.5.2 advanced positioner transducer block (ao trd) ao trd: act_fail_action (45) storage class: s · read/write capability (r/w) the fail-safe action to be performed by the actuator in case of a supply air failure is deter- mined automatically during initialization. • air to open (in 0 % position) • ...

  • Page 46

    Ao trd: alert_key (4) storage class: s · read/write capability (r/w) used to specify the identification number of the plant section. • 1 to 255, [0] this information can be used by the fieldbus host system to group alerts and events. Note: '0' is not a permissible value and will be rejected when tra...

  • Page 47

    Ao trd: block_alm (8) storage class: d · read/write capability (r/w) indicates the current block state with details on all configuration, hardware or system prob- lems in the block including details on the date and time of the alarm when the fault occurred. Ao trd: block_err (6) storage class: d · r...

  • Page 48

    Ao trd: closed_pos_deadband (61) storage class: s · read/write capability (r/w) zero point limit [%] ® code 48 d5 ao trd: closed_pos_shift (62) storage class: n · read capability (r) indicates a shift of the end position. Ao trd: closing_direction (134) storage class: s · read/write capability (r/w)...

  • Page 49

    Ao trd: custom_curve_xy_float (65) storage class: s · read/write capability (r/w) · supported modes: o/m/a used to enter the user-defined characteristic. Ao trd: cycle_cntr (38) storage class: d · read capability (r) indicates the number of measured cycles since the counter was last reset. Ao trd: c...

  • Page 50

    Ao trd: device_characteristic (125) storage class: s · read/write capability (r/w) · supported modes: o/m/a reflects positioner-specific data. • model · actuator model • attachment · actuator attachment • booster • actuator_size • signal_pressure_lower_value • signal_pressure_upper_value • supply_pr...

  • Page 51

    Ao trd: diag_reflauf_info (211) storage class: s · read capability (r) indicates the status of the reference tests in progress. Ao trd: diag_reset_after_time (155) storage class: s · read/write capability (r/w) · supported modes: o/m/a indicates the time until the next reset of the diagnosis. Ao trd...

  • Page 52

    Ao trd: diagr_stell_x_stat_test_ref (217) storage class: d · read capability (r) tests – drive signal diagram steady-state (test d1) measured values – valve position x of the reference characteristic ao trd: diagr_stell_x_stat_test_wh (219) storage class: d · read capability (r) tests – drive signal...

  • Page 53

    Ao trd: diagr_stell_y_stat_test_ref (216) storage class: d · read capability (r) tests – drive signal diagram steady-state (test d1) measured values – drive signal y of the reference characteristic ao trd: diagr_stell_y_stat_test_wh (218) storage class: d · read capability (r) tests – drive signal d...

  • Page 54

    Ao trd: dl_histogr_e_1 (175) to dl_histogr_e_4 (178) storage class: d · read capability (r) statistical information – data logger measured values of setpoint deviation e ao trd: dl_histogr_e_long (186) storage class: d · read capability (r) statistical information – data logger measured values of ti...

  • Page 55

    Ao trd: dl_histogr_y_1 (179) to dl_histogr_y_4 (182) storage class: d · read capability (r) statistical information – data logger measured values of drive signal y ao trd: dl_histogr_z_long (189) storage class: d · read capability (r) statistical information – cycle counter histogram, long-term moni...

  • Page 56

    56 kh 8384-5 en foundation™ fieldbus parameters ao trd: end_pos_trend_ref_time_ref (202) storage class: d · read capability (r) statistical information – trend of the travel end position – lower end position reference value of the lower end position, time stamp ao trd: end_pos_trend_ref_values (204)...

  • Page 57

    Ao trd: final_position_value (18) storage class: d · read capability (r) indicates the current valve position after taking the decharacterization into account. Ao trd: final_position_value_d (33) storage class: d · read capability (r) indicates the discrete valve position after taking the direction ...

  • Page 58

    Ao trd: final_value_cutoff_lo (17) storage class: s · read/write capability (r/w) · supported modes: o/m/a setpoint cutoff decrease (final position w ® code 14 • –2.5 to 100.0 %, [1.0 %] if the reference value falls below the entered value, the valve is moved to the final position that corresponds t...

  • Page 59

    Ao trd: friction (68) storage class: n · read capability (r) indicates the friction in percent. Ao trd: friction_limits (301) storage class: s · read/write capability (r/w) · supported modes: o/m/a specifies the upper and lower friction limits. • friction_limit_up, 0 to 1000 % [200 %] • friction_lim...

  • Page 60

    Ao trd: fst_diagr_x1 (281) to fst_diagr_x4 (284) storage class: d · read capability (r) statistical information – data logger: measured values of valve position x ao trd: fst_diagr_y1 (293) bis fst_diagr_y4 (296) storage class: d · read capability (r) statistical information – data logger: measured ...

  • Page 61

    • fst_t98_falling · t98 (falling) • fst_rise_t_falling · rise time (falling) • fst_settl_t_falling · settling time (falling) ao trd: fst_ramp_rate (88) · this parameter is not supported ao trd: fst_settings (269) storage class: d · read/write capability (r/w) · supported modes: o/m/a settings of the...

  • Page 62

    • fst_pressure_friction · aborted due to supply pressure/friction • fst_current_too_low · test aborted – current too low ao trd: his_temperature (148) storage class: d · read capability (r) reading in hours (per hour or fraction thereof) • his_t_zeit_min_temperature · operating hours counter: lowest...

  • Page 63

    Ao trd: ident_options (118) storage class: d · read capability (r) indicates which optional components (additional equipment) are installed. 1 internal solenoid valve 2 binary input 1 3 binary input 2 4 inductive limit switch 5 leakage sensor 6 external position sensor ao trd: init_method (128) stor...

  • Page 64

    Ao trd: internal_temp_units (99) storage class: s · read/write capability (r/w) · supported modes: o/m/a specifies the unit for the temperature inside the positioner. • [°c] • °f ao trd: kp_step (140) storage class: s · read/write capability (r/w) specifies proportional gain factor kp (step) ® code ...

  • Page 65

    Ao trd: ls_alarm_limit_1 (307) to ls_alarm_limit_3 (309) storage class: s · read/write capability (r/w) leakage sensor ls_alarm_limit_1 (307) = first alarm limit in db ls_alarm_limit_2 (308) = second alarm limit in db ls_alarm_limit_3 (309) = third alarm limit in db ao trd: ls_alarm_release (304) st...

  • Page 66

    Ao trd: mode_blk (5) storage class: s · read/write capability (r/w) operating mode: – target mode ® code 48 t0 – actual mode (read only) ® code 48 t1 – permitted mode – normal mode (read only) • auto · a positioning value is calculated from the output value from the ao function block and the control...

  • Page 67

    Ao trd: pos_features (44) storage class: d · read capability (r) parameter groups supported by ao transducer block. Ao trd: positioner_model (122) storage class: d · read capability (r) indicates the positioner model. Ao trd: pressure_limit (138) storage class: s · read/write capability (r/w) pressu...

  • Page 68

    Ao trd: pst_completion_timeout (85) storage class: s · read/write capability (r/w) · supported modes: o/m/a cancelation condition of the partial stroke test (pst): max. Test duration (user-defined) ao trd: pst_diagr_e1 (261) to pst_diagr_e4 (264) storage class: d · read capability (r) statistical in...

  • Page 69

    Ao trd: pst_initial_start_time (79) · this parameter is not supported ao trd: pst_interval (80) storage class: s · read/write capability (r/w) · supported modes: o/m/a specifies the time until the partial stroke test automatically starts (pst_testmode_target must be set to 'pst auto') ao trd: pst_me...

  • Page 70

    • pst_ramp_time_rising · ramp time (rising) • pst_ramp_time_falling · ramp time (falling) • pst_settling_time_before_test · settling time before test start • pst_scan_rate · scan rate • pst_step_response · number of steps ao trd: pst_strk_trav (83) storage class: s · read capability (r) step height ...

  • Page 71

    Ao trd: pst_testmode_target (237) storage class: d · read/write capability (r/w) · supported modes: o/m/a required test mode of the partial stroke test (pst) • [pst man] • pst auto ao trd: rated_travel (26) storage class: s · read/write capability (r/w) rated travel ® code 5 • 0 to 255.9 mm, [15.0 m...

  • Page 72

    Ao trd: select_options (119) storage class: s · read/write capability (r/w) · supported modes: o/m/a read/change the installed options that are not automatically recognized (ident_limit_switches, ident_ext_leakage_sensor, ident leakage detection, ident_ext_pos_sensor) ao trd: set_fail_safe_pos (126)...

  • Page 73

    • data logger • tests (d1 to d6 and d9) ao trd: stat_kennl_r (227) storage class: d · read capability (r) tests – static characteristic: reading • stat_kennl_r_test_info · current status of the test • stat_kennl_r_step_heigth · step height • stat_kennl_r_min_dead_band · smallest dead band measured •...

  • Page 74

    Ao trd: stop_lo_pos_on (142) storage class: s · read/write capability (r/w) · supported modes: o/m/a enable travel/angle lower limit ® code 10 • on • [off] ao trd: strategy (3) storage class: s · read/write capability (r/w) permits strategic grouping and thus faster processing of blocks. • [0] block...

  • Page 75

    Ao trd: sub_mod_init (130) storage class: d · read capability (r) indicates whether the initialization was performed in sub mode (subsitition calibration). Ao trd: tag_desc (2) storage class: s · read/write capability (r/w) assigns a unique description to each block for clear identification • max. 3...

  • Page 76

    Ao trd: transducer_type_ver (11) storage class: d · read capability (r) transducer block for positioner according to specification ff-906 ao trd: travel_accum (29) storage class: d · read capability (r) total valve travel: totaled double valve travel. ® code 23 ao trd: travel_accum_deadband (73) · t...

  • Page 77

    Ao trd: valve_model_num (50) storage class: s · read/write capability (r/w) · supported modes: o/m/a indicates the model number of the valve that the positioner is mounted on. Ao trd: valve_sn (51) storage class: s · read/write capability (r/w) · supported modes: o/m/a indicates the serial number of...

  • Page 78

    Ao trd: working_pos (19) storage class: d · read capability (r) actual valve position in % ao trd: working_pos_d (34) storage class: d · read capability (r) actual discrete valve position ao trd: working_sp (20) storage class: n · read capability (r) reference variable after scaling, characterizatio...

  • Page 79

    6 abort zero point adjustment 7 search device ao trd: xd_command_flags (75) · this parameter is not supported ao trd: xd_command_state (42) storage class: d · read capability (r) status of initialization. Ao trd: xd_error (12) storage class: d · read capability (r) errors listed in the transducer bl...

  • Page 80

    • init./int. Solenoid valve ® code 54 • travel time too short ® code 55 • pin position/safety switch ® code 56 • test or calibration running 2 xd_error_ext_2 • x-signal ® code 62 • i/p-converter ® code 64 • hardware ® code 65 • control parameter ® code 68 • poti parameter ® code 69 • adjustment para...

  • Page 81

    24 working range 25 temperature error 26 pst/fst status 27 open/close status ao trd: xd_fstate_opt (37) storage class: s · read/write capability (r/w) · supported modes: o/m/a action on detection of an error in ao transducer block • [hold last value] • fail-safe position • fault state value (xd_fsta...

  • Page 82

    Ao trd: y_hyst_test_info (221) storage class: d · read capability (r) tests – drive signal diagram hysteresis (test d2): test status ao trd: y_hyst_test_progress (222) storage class: d · read capability (r) tests – drive signal diagram hysteresis (test d2): progress of test in % ao trd: y_hyst_testi...

  • Page 83

    Parameter index: ao transducer block kh 8384-5 en 83 foundation™ fieldbus parameters index parameter 0 advanced_pv_basic 1 st_rev 2 tag_desc 3 strategy 4 alert_key 5 mode_blk 6 block_err 7 update_evt 8 block_alm 9 transducer_directory 10 transducer_type 11 transducer_type_ver 12 xd_error 13 collecti...

  • Page 84

    84 kh 8384-5 en foundation™ fieldbus parameters index parameter 62 closed_pos_shift 63 custom_curve_description 64 custom_curve_xy 65 custom_curve_xy_float 66 cycle_counter_deadband 67 friction_units 68 friction 69 hysteresis 70 pos_deadband 71 stroke_time_closed 72 stroke_time_open 73 travel_accum_...

  • Page 85

    Kh 8384-5 en 85 foundation™ fieldbus parameters index parameter 126 set_fail_safe_pos 127 trans_pin_pos 128 init_method 129 init_with_ref_test 130 sub_mod_init 131 opti_sub_init 132 device_init_state 133 device_status_init 134 closing_direction 135 final_value_cutoff_lo_on 136 final_value_cutoff_hi_...

  • Page 86

    86 kh 8384-5 en foundation™ fieldbus parameters index parameter 190 dl_histogr_z_short 191 diagr_stell_y_stat_long 192 diagr_stell_y_stat_kurz 193 diagr_stell_y_stat_short 194 diagr_valve_pos_stat_short 195 y_hyst_min_time_distance 196 y_hyst_tolerance_band 197 y_hyst_testinfo 198 hyst_short_diff_y ...

  • Page 87

    Kh 8384-5 en 87 foundation™ fieldbus parameters index parameter 254 pst_diagr_x2 255 pst_diagr_x3 256 pst_diagr_x4 257 pst_diagr_w1 258 pst_diagr_w2 259 pst_diagr_w3 260 pst_diagr_w4 261 pst_diagr_e1 262 pst_diagr_e2 263 pst_diagr_e3 264 pst_diagr_e4 265 pst_diagr_y1 266 pst_diagr_y2 267 pst_diagr_y...

  • Page 88

    7.5.3 analog output function block ao: alert_key (4) storage class: s · read/write capability (r/w) · supported modes: o/m/a used to specify the identification number of the plant section. • 1 to 255, [0] this information can be used by the fieldbus host system to group alerts and events. Note: '0' ...

  • Page 89

    Ao: channel (22) storage class: s · read/write capability (r/w) · supported mode: o assignment between the output of the ao function block and the logical hardware channels (transducer block) • [3] note: in order to be able to put the ao function block into operation, channel must be set to '3' so t...

  • Page 90

    • fault state to value · fstate_val is used as the set point when the fault state is acti- vated (see fstate_val, fstate_time). • use fault state value on restart · fstate_val is used for the set point until there is a valid value on restarting the device. • target to man if fault state activated · ...

  • Page 91

    Ao: pv (7) storage class: d · read capability (r) process variable of the function block (value and status) • unit from xd_scale parameter group note: if out readback is set in the features_sel parameter in the resource block, pv contains the current valve position (same as final_position_value). Ao...

  • Page 92

    • [uninitialized] · not initialized • normal shed_normal return · on failure of remote connection, change to next pos- sible mode until rcas mode is restored. • normal shed_no return · on failure of remote connection, change to next possible mode. The block remains in this mode. • shed to auto_norma...

  • Page 93

    Ao: sp_hi_lim (20) storage class: s · read/write capability (r/w) · supported modes: all upper limit of the reference variable • value and range from pv_scale ±10 %, [100 %] note: this value must be adapted correspondingly if the scale end setting is changed in pv_scale parameter. Ao: sp_lo_lim (21)...

  • Page 94

    Ao: strategy (3) storage class: s · read/write capability (r/w) · supported modes: all grouping to allow faster processing of blocks • [0] blocks are grouped by entering the same number in the strategy parameter of each block. Note: these data are neither checked nor processed by the ao function blo...

  • Page 95

    Parameter index: ao function block kh 8384-5 en 95 foundation™ fieldbus parameters index parameter 0 – 1 st_rev 2 tag_desc 3 strategy 4 alert_key 5 mode_blk 6 block_err 7 pv 8 sp 9 out 10 simulate 11 pv_scale 12 xd_scale 13 grant_deny 14 io_opts 15 status_opts index parameter 16 readback 17 cas_in 1...

  • Page 96

    7.5.4 proportional integral derivative function block pid: ack_options (46) storage class: s · read/write capability (r/w) · supported modes: all determines whether an alarm is to be automatically acknowledged in the pid function block • [undefined] · no selection • hi_hi_alm · high high alarm • hi_...

  • Page 97

    Pid: alert_key (4) storage class: s · read/write capability (r/w) · supported modes: all used to specify the identification number of the plant section. • 1 to 255, [0] this information can be used by the fieldbus host system to group alerts and events. Note: '0' is not a permissible value and will ...

  • Page 98

    Pid: block_alm (44) storage class: d · read/write capability (r/w) · supported modes: all indicates the current block state with details on all configuration, hardware or system prob- lems in the block including details on the date and time of the alarm when the fault occurred. Pid: block_err (6) st...

  • Page 99

    Pid: dv_hi_alm (64) storage class: d · read/write capability (r/w) · supported modes: all deviation high alarm (dv_hi_lim) including details of time of alarm (date and time stamp) as well as the value that activated the alarm. Note: an active block alarm can also be acknowledged manually in this par...

  • Page 100

    Pid: dv_lo_pri (58) storage class: s · read/write capability (r/w) · supported modes: all determines the action to be taken when the value for the deviation low alarm is exceeded (dv_lo_lim) • [0] · the limit for deviation low alarm is not processed. • 1 · alarm is not broadcast to fieldbus host sys...

  • Page 101

    Pid: hi_alm (61) storage class: d · read capability (r) indicates high alarm status (hi_lim) including details of time of alarm (date and time stamp) as well as the value that activated the alarm. • unit from pv_scale pid: hi_hi_alm (60) storage class: d · read/write capability (r/w) indicates high ...

  • Page 102

    Pid: hi_pri (50) storage class: s · read/write capability (r/w) · supported modes: all determines the action to be taken when the value for the high alarm is exceeded (hi_lim). • [0] · the limit for high alarm is not processed. • 1 · alarm is not broadcast to fieldbus host system. • 2 · reserved for...

  • Page 103

    Pid: lo_lo_pri (54) storage class: s · read/write capability (r/w) · supported modes: all determines the action to be taken when the value for the low low alarm is exceeded (lo_lo_lim). • [0] · the limit for low low alarm is not processed. • 1 · alarm is not broadcast to fieldbus host system. • 2 · ...

  • Page 104

    • rcas · the ao function block receives the reference variable directly from the fieldbus host system for internal calculation of the output value. The ao block is implemented. • rout · the pid function block receives the output value directly from the fieldbus host system over the rout_in parameter...

  • Page 105

    Pid: pv_scale (10) storage class: s · read/write capability (r/w) · supported modes: o definition of the range for the process variable pv (start, end, unit and decimal point) • [0 to 100 %] pid: rate (26) storage class: s · read/write capability (r/w) · supported modes: all specifies the time const...

  • Page 106

    Rout_out is provided by the fieldbus host system to perform back calculation to allow ac- tion to be taken under mode changes or limited signals. Note: this parameter is only active in the rout mode. Pid: shed_opt (34) storage class: s · read/write capability (r/w) · supported modes: all determines ...

  • Page 107

    • range and value from pv_scale ±10 %, [100] note: this value must be adapted correspondingly if the scale end setting is changed in pv_scale parameter. Pid: sp_lo_lim (22) storage class: s · read/write capability (r/w) · supported modes: all lower limit of the reference variable. • range and value ...

  • Page 108

    • use uncertain as good · the status uncertain is used as good. • target in manual if bad in · reverts to man mode if the input value changes status to bad. Pid: strategy (3) storage class: s · read/write capability (r/w) · supported modes: all permits strategic grouping and thus faster processing o...

  • Page 109

    Parameter index: pid function block kh 8384-5 en 109 foundation™ fieldbus parameters index parameter 0 – 1 st_rev 2 tag_desc 3 strategy 4 alert_key 5 mode_blk 6 block_err 7 pv 8 sp 9 out 10 pv_scale 11 out_scale 12 grant_deny 13 control_opts 14 status_opts 15 in 16 pv_ftime 17 bypass 18 cas_in 19 sp...

  • Page 110

    110 kh 8384-5 en foundation™ fieldbus parameters index parameter 58 dv_lo_pri 59 dv_lo_lim 60 hi_hi_alm 61 hi_alm 62 lo_alm 63 lo_lo_alm 64 dv_hi_alm 65 dv_lo_alm.

  • Page 111

    7.5.5 discrete output function block do: alert_key (4) storage class: s · read/write capability (r/w) · supported modes: all used to specify the identification number of the plant section. • 1 to 255, [0] this information can be used by the fieldbus host system to group alerts and events. Note: '0' ...

  • Page 112

    Note: in order to be able to put the do1 function block into operation, channel must be set to '6' so that it can be assigned to the do1 trd. In order to be able to put the do2 func- tion block into operation, channel must be set to '7' so that it can be assigned to the do2 trd. Do: fstate_time (19)...

  • Page 113

    Do: mode_blk (5) storage class: n · read/write capability (r/w) · supported modes: all type of mode of do function block – target mode – actual mode (read only) – permitted mode – normal mode (read only) • auto · the set point entered by the user is used over the sp_d parameter on implementa- tion o...

  • Page 114

    Do: rcas_out_d (24) storage class: d · read capability (r) discrete reference variable after ramping (value and status) rcas_out_d is provided by the fieldbus host system for back calculation to allow action to be taken under mode changes or limited signals. Note: this parameter is only active in th...

  • Page 115

    • shed to retained target_no return · on failure of remote connection, the block sets the target mode to the retained target mode. • note: this parameter is only active in rcas mode in the do function block. The do func- tion block cannot be set to the rcas mode when the value is set to uninitialize...

  • Page 116

    Do: tag_desc (2) storage class: s · read/write capability (r/w) · supported modes: all assigns a unique description to each block for clear identification. • max. 32 characters, [no text] do: update_evt (25) storage class: d · read capability (r) indicates that static data were changed, including da...

  • Page 117

    Kh 8384-5 en 117 foundation™ fieldbus parameters 7.5.6 discrete input function block (di1 + di2) di: ack_options (21) storage class: s · read/write capability (r/w) · supported modes: o/m/a determines whether an alarm is to be automatically acknowledged, i.E. Without intervention of the fieldbus hos...

  • Page 118

    Di: channel (15) storage class: s · read/write capability (r/w) · supported modes: o assignment between the output of the di function block and the logical hardware channels (transducer block) • [1] in di1 function block and [2] in di2 function block note: in order to be able to put the di1 function...

  • Page 119

    Di: io_opts (13) storage class: s · read/write capability (r/w) · supported modes: o used to select how the input/output is processed in the di function block. • invert · used to logically invert the value of field_val_d before it is stored as out_d. Di: mode_blk (5) storage class: n · read/write ca...

  • Page 120

    Di: status_opts (14) storage class: s · read/write capability (r/w) · supported modes: o status options to determine the handling and processing of the status. • [uninitialized] · not initialized • propagate fail fwd · fault state is passed on to the downstream function block. Di: strategy (3) stora...

  • Page 121

    Kh 8384-5 en 121 foundation™ fieldbus parameters parameter index: di1 function block and di2 function block index parameter 0 – 1 st_rev 2 tag_desc 3 strategy 4 alert_key 5 mode_blk 6 block_err 7 pv_d 8 out_d 9 simulate_d 10 – 11 – 12 grant_deny index parameter 13 io_opts 14 status_opts 15 channel 1...

  • Page 122

    122 kh 8384-5 en foundation™ fieldbus parameters 7.5.7 input selector function block is: alert_key (4) storage class: s · read/write capability (r/w) · supported modes: o/m/a used to specify the identification number of the plant section. • 1 to 255, [0] this information can be used by the fieldbus ...

  • Page 123

    Is: mode_blk (5) storage class: n · read/write capability (r/w) · supported modes: o/m/a betriebsart is function block – target mode – actual mode (read only) – permitted mode – normal mode (read only) • auto · the analog input values selected from in_1 to in_4 are processed by the function block an...

  • Page 124

    Is: st_rev (1) storage class: n · read capability (r) indicates the revision number of static data. Note: the revision state is incremented by one each time a static parameter in the block is written. Is: status_opts (10) storage class: s · read/write capability (r/w) · supported modes: o options fo...

  • Page 125

    Parameter index: is function block kh 8384-5 en 125 foundation™ fieldbus parameters index parameter 0 – 1 st_rev 2 tag_desc 3 strategy 4 alert_key 5 mode_blk 6 block_err 7 out 8 out_range 9 grant_deny 10 status_opts 11 in_1 12 in_2 index parameter 13 in_3 14 in_4 15 disable_1 16 disable_2 17 disable...

  • Page 126

    7.5.8 multiple analog input function block mai: alert_key (4) storage class: s · read/write capability (r/w) · supported modes: all used to specify the identification number of the plant section. • 1 to 255, [0] this information can be used by the fieldbus host system to group alerts and events. Not...

  • Page 127

    • man · the output values of the mai function block can be directly entered by the operator over the out_1 to out_8 parameters. • o/s · the mai function block is not executed. The last value is issued at the output out_1 to out_8. Mai: out_1 (8) to out_8 (15) storage class: n · read/write capability...

  • Page 128

    128 kh 8384-5 en foundation™ fieldbus parameters parameter index: mai function block index parameter 0 – 1 st_rev 2 tag_desc 3 strategy 4 alert_key 5 mode_blk 6 block_err 7 channel 8 out_1 9 out_2 index parameter 10 out_3 11 out_4 12 out_5 13 out_6 14 out_7 15 out_8 16 update_evt 17 block_alm.

  • Page 129

    Kh 8384-5 en 129 foundation™ fieldbus parameters 7.5.9 multiple analog output function block mao: alert_key (4) storage class: s · read/write capability (r/w) · supported modes: all used to specify the identification number of the plant section. • 1 to 255, [0] this information can be used by the fi...

  • Page 130

    • [0] note: the fault state is activated when the fault still exists after the time interval has elapsed. The fault state of the mao function block is set in the mo_opts parameter of this block. Mao: fstate_val1 (18) to fstate_val8 (25) storage class: s · read/write capability (r/w) · supported mode...

  • Page 131

    Mao: st_rev (1) storage class: n · read capability (r) revision state of static data note: the revision state is incremented by one each time a static parameter in the block is written. Mao: strategy (3) storage class: s · read/write capability (r/w) · supported modes: all grouping to allow faster p...

  • Page 132

    Parameter index: mao function block 132 kh 8384-5 en foundation™ fieldbus parameters index parameter 0 – 1 st_rev 2 tag_desc 3 strategy 4 alert_key 5 mode_blk 6 block_err 7 channel 8 in_1 9 in_2 10 in_3 11 in_4 12 in_5 13 in_6 14 in_7 index parameter 15 in_8 16 mo_opts 17 fstate_time 18 fstate_val1 ...

  • Page 133

    Kh 8384-5 en 133.

  • Page 134

    134 kh 8384-5 en.

  • Page 135

    Kh 8384-5 en 135.