Blower CFM tables
AC042KNZDCH/AA
HP : 1/2Default motor taps:High / Mid
/Low = 5/3/1
Motor Tap
P(inwg)
CFM
Motor Tap
P(inwg)
CFM
1
0.1
1090
4
0.1
1261
0.2
1048
0.2
1226
0.25
1026
0.25
1209
0.3
1005
0.3
1191
0.4
959
0.4
1155
0.5
909
0.5
1120
0.6
858
0.6
1082
0.7
805
0.7
1043
0.8
747
0.8
1005
0.9
685
0.9
964
1
620
1
922
2
0.1
1137
5
0.1
1315
0.2
1101
0.2
1282
0.25
1083
0.25
1266
0.3
1064
0.3
1251
0.4
1025
0.4
1217
0.5
984
0.5
1184
0.6
940
0.6
1149
0.7
892
0.7
1113
0.8
841
0.8
1076
0.9
783
0.9
1039
1
718
1
1000
3
0.1
1180
= Default Setting
0.2
1147
0.25
1128
0.3
1110
0.4
1074
0.5
1035
0.6
995
0.7
952
0.8
907
0.9
857
1
804
!
!