AC048KNZDCH/AA
HP : 3/4Default motor taps:High / Mid
/Low = 4/2/1
Motor Tap
P(inwg)
CFM
Motor Tap
P(inwg)
CFM
1
0.1
1260
4
0.1
1538
0.2
1167
0.2
1500
0.3
1075
0.3
1462
0.4
981
0.4
1422
0.5
887
0.5
1379
0.6
793
0.6
1331
0.7
699
0.7
1280
0.8
606
0.8
1224
0.9
510
0.9
1158
1
415
1
1078
2
0.1
1379
5
0.1
1739
0.2
1293
0.2
1705
0.3
1210
0.3
1670
0.4
1130
0.4
1633
0.5
1045
0.5
1597
0.6
963
0.6
1559
0.7
878
0.7
1522
0.8
795
0.8
1485
0.9
711
0.9
1446
1
627
1
1406
3
0.1
1475
= Default Setting
0.2
1410
0.3
1348
0.4
1282
0.5
1216
0.6
1148
0.7
1076
0.8
1003
0.9
929
1
850
!
!
8