Samsung ACH1800E Technical Manual - page 39
38 |
SAMSUNG
INSTALLATION
3
Drain Hose Installation
(Cont.)
●
Testing the drainage
You should test the drainage after completing the installation. Prepare a little water about 2.0 liter.
Œ
Remove two screws on the cover drain pump and pull out the cover.
´
Pour water into the indoor unit as shown in figure.
ˇ
Confirm that the water flows out through the drain hose.
¨
Reassemble the cover drain pump and the screws.
CAUTION
Do not install air bleeding tubes, as this may
cause water to spray from the drain tube outlet.
Do not give the hose and upward gradient after the
connection port.
This will cause water to flow backwards when the unit
is stopped, resulting in water leaks.
If it is necessary to increase the height of the drain
hose somewhat, the portion directly after 30cm. If it is
raised higher than 50cm, there can be water leaks.
;;
;;
Air bleeder
Ceiling
;
;;
300mm or less
1~1.5m
C
B
A
Do not apply force to the piping on the unit side when
connecting the drain hose. The hose should not be
allowed to hang loose from its connection to the unit.
Fasten the hose to a wall, frame or other support as
close to the unit as possible.
;
;;
;;
;;
;;;;
;;;;
;
;
Upward gradient
Support pieces
1~1.5m
1/100 or more
Flexible hose
Band joint
Ceiling
Ceiling
Ceiling
✳✳18/✳✳24
✳✳36/✳✳44
A
750 mm
750 mm
B
200 mm
258 mm
C
550 mm
482 mm
If you do not pour water inside the water supply intake,
water may spill from the indoor unit.
You can check the drainage only when the air conditioner is
turned on.
Œ
´
Cover drain pump
Check that the indoor unit is level with the ceiling by using the leveler.
Note
Note