Samsung ACH1800E Technical Manual - page 66
SAMSUNG | 65
DIAGRAMS
5
Refrigerating Cycle Block Diagram
(Cont.)
Heat
Exchanger
(Evaporator)
Heat
Exchanger
(Condenser)
Gas Side
Muffler
High Pressure switch
Compressor
Accumulator
4-Way Valve
Reservior
Capillary Tube
Cooling
Heating
Gas leak check point
Liquid Side
Capillary Tube
Check Valve
3-Way Valve
3-Way Valve
Heat
Exchanger
(Evaporator)
Heat
Exchanger
(Condenser)
Gas Side
Muffler
High Pressure switch
Compressor
Accumulator
4-Way Valve
Capillary Tube
Cooling
Heating
Gas leak check point
Liquid Side
Capillary Tube
Check Valve
3-Way Valve
3-Way Valve
● ADH3200E, DH32ZA1(A2)
● ADH4400G, DH44ZA1(ZA2)
Indoor Unit
Outdoor Unit
*Allowable pipe length : Max. 30m
*Allowable drop distance : Max. 15m
Indoor Unit
Outdoor Unit
*Allowable pipe length : Max. 50m
*Allowable drop distance : Max. 25m
*Amount of refilling per extension length of 1m;
When extending the pipe length by more than 5m, 55gr(55gr: Outdoor Unit is higher than Indoor Unit) of R-22
refrigerant should be refilled per extension length of 1m.