Samsung AE022MNJDEH Installation Manual - page 13
13
Ins
tallation Pr
oc
edur
e
English
Step 9 Installing the drain hose and
drain pipe
When installing the drain hose for the indoor unit, check
if condensation draining is adequate. When passing the
drain hose through the 65-mm hole drilled in the wall,
check the following:
The hose must NOT
slant upwards.
The end of the drain
hose must NOT be
placed under water.
Do NOT bend the hose
in different directions.
Keep a clearance of at
least 5cm between
the end of the hose
and the ground.
Do NOT place the end
of the drain hose in a
hollow.
1 If necessary, connect the 2-meter extension drain hose to
the drain hose.
Shield
Drain hose
Extension drain hose
2 If you use the extension drain hose, insulate the inside of
the extension drain hose with a shield.
3 Fit the drain hose into 1 of 2 drain hose holes, then
fix the end of the drain hose tightly with a clamp.
• If you don’t use the other drain hose hole, block it
with a rubber stopper.
4 Pass the drain hose under the refrigerant pipe,
keeping the drain hose tight.
5 Pass the drain hose through the hole in the wall.
Check if it slants downwards as seen in the picture.
6-ways for drain hose and drain pipe connection
Knock out
NOTE
• The hose will be fixed permanently into position after
finishing the installation and the gas leak test; refer
to page 12 for further details.