Option
SEG19
SEG20
SEG21
SEG22
SEG23
SEG24
Explanation
PAGE
Individual control of a
remote control
Heating setting compensation / Removing
condensated water in heating mode
EEV Step of stopped unit during oil return/
defrost mode
-
Indication and
Details
Indication
Details Indication Details Indication
Details
Indication
Details
Heating
Setting
Compensation
Removing
Condensated
Water in
Heating
Mode
3
0 or 1 channel 1 0
Default (*5)
Disuse
0
Default value
2
channel 2
1
2 °C
Disuse
1
Oil return or Noise decreasing
in defrost mode
3
channel 3
2
5 °C
Disuse
4
channel 4
3
Default (*5) Use (*6)
4
2 °C
Use (*6)
5
5 °C
Use (*6)
(*) Advanced function: Controlling cooling/heating current or power saving with motion detect.
(*1) Minimizing fan operation when thermostat is off
– Fan operates for 20 seconds at an interval of 5 minutes in Heat mode.
(*2) 1: Fan is turned on continually when the hot water heater is turned on, 3: Fan is turned off when the hot water
heater is turned on with cooling only indoor unit
Cooling only indoor unit: To use this option,install the Mode Select switch(MCM-C200) on the outdoor unit and fix
it as Cool mode.
(*3) It is only for wall-mounted indoor unit with EEV Integrated. If any design condition meets either of the following
below, please set SEG11 to “7”.
a The total number of wall-mounted indoor units with EEV Integrated in one (modular) system is more than 20.
b The total number of wall-mounted indoor units with EEV Integrated in one (modular) system is more than “the
total of one(modular) system’s capacity(kW) / 2” (“the total of one(modular) system’s capacity(BTU/h) / 6800”).
ex) Outdoor capacity 28kW
→ 28 /2 = 14. The total number of wall-mounted indoor units with EEV Integrated
in one (modular) system is more than 14.