Setec BCE4 User Manual - Installation
INSTALLATION
Personnel
Installation should only be conducted and/or closely supervised by
appropriately qualified personnel.
Mounting Options
The unit is supplied with 4 rubber feet for bench use. However, a number
of mounting options have been provided to suit various installations.
Mounting options have been provided at the front and the underneath of
unit in the form of M3 x 0.5mm threads. The unit can be mounted
horizontal or vertical to suit all types of installations. See figures 4 – 6.
The maximum thread length for these screws is 4mm from the outside
edge of the power supply. Hazardous Voltages exist within the power
supply so it is important that the screw lengths are adhered to.
Connectors
Input Mains:
IEC320
DC Output:
6 Way female plugable type
Pinout for the DC output connector is as follows;
Pin Function
1 0V
2 0V
3 Load
4 Battery
5 Alarm
1
6 Alarm
2
Mating Connectors:
Phoenix: MSTB 2.5/6-ST
Weco 120-A-111/06
Camden CTB9200/6A
Hooking Up
The requirements for wiring a BCE4/BCE5 into a system are as follows:
LOAD, 0V
These 2 connections are the DC output of the power supply. These
connections are to supply the load.
• These connections cannot be paralleled with output of duplicate
power supply for increased current output.
• The load connection must not be directly connected to the battery or
paralleled with the BATTERY connection. This will disable the battery
low voltage disconnect circuit and defeat the internal battery fuse.
Issue D
Page 11 of 13