Setec BCE4 User Manual - Specification
SPECIFICATION
The following table lists the specifications of the BCE4 and BCE5
Specification
Input Voltage:
200-240V nominal,
±10%, 50/60Hz.
A 5 minute, +15% surge will not damage the power supply.
Input Surge:
Holdup Time:
>20mS, over the nominal input range
BCE4 BCE5
Output Voltage:
12.0 –14.0V Adjustable
24.0 – 28.0V Adjustable
Output Voltage factory set:
13.65V 27.20V
Output Ripple Voltage:
Output Current:
10.0A 5.0A
Over Voltage Protection:
Battery Disconnect
10.2
± 0.2V
23.5
± 0.7V
Battery Reconnect
&
11.9
± 0.3V
20.5
± 0.6V
Battery Hysteresis
1.7V typ
3.0V typ
Battery Fuse
15A, 32Vdc
10A, 32Vdc
Load Regulation 1:
± 2% from set point taking into account all of line and load
regulation and temperature coefficient when load powered by
power supply
Load Regulation 2:
+0 –2% of battery terminal voltage when load powered by
battery.
Alarm Relay Contact
Rating
Normally closed contacts
60V @ 0.2A
Operating Environment:
0 – 50’C Ambient. Convection cooled
Efficiency:
90% typ
Mechanical
See figures 1 - 6
Weight
Compliance:
AS/NZS 60950-1 : 2003
AS/NZS CISPR22 Class A
ACA EMC Compliance, C-Tick Mark
&
Battery is automatically connected if mains is present and the battery voltage is > 9.5V.
Issue D