Smart Temp SMT - 131 User Manual - page 15
Page 15
17
0-10V
Heat
minimum
Voltage
0 -10V
Data format : 0-10V Heat minimum value * 10
18
Cool span
0.5C-3.0C/1.0F-6.0F 0.5C/1F steps
Data format : Fan span * 10
19
0-10V Cool interval (PI)
10-300 seconds 10 seconds steps (60 seconds default)
20
0-10V Cool direction
0: 10V is 100% open (forward acting)
1: 0V is 100% open n(reverse acting)
21
0-10V
Cool
minimum
Voltage
0 -10V
Data format : 0-10V Cool minimum value * 10
22
Auto Off Timer
0: No auto off timer
1-10hours 0.5 hours steps
Data format : hour * 10
23
Un-occupied heat
Set point
0: OFF
5C-30C/41F-86F 0.5C/1F steps
24
Un-occupied cool
Set point
0: OFF
5C-30C/41F-86F 0.5C/1F steps
25
Un –Occupied fan mode
Fan 3 Speed mode
1: Low (Auto) (default)
2: Med (Auto)
3: High (Auto)
4: Low (ON)
5: Med (ON)
6: High (ON)
26
Backlight
0: On with button press Only
1: Always On high
2: Low when standby / high when active (Default)
27
TT sensor (SI & Com)
0: Remote – Use this sensor in place of the fitted sensor.
1: Average – Use both remote and fitted sensor and control
to the average temperature of both sensors.
2: Data – Sensor value used for Modbus only.
3 : Duct – Used for 2 pipe mode.
28
Temperature Calibration
+/- 10 deg (C or F)
Adjust to show correct room temp.
29
Digital Input
0: Force Room to Unoccupied Mode
1: Chime Door Bell
30
Digital Input Logic
0: Normally Open
1: Normally Closed
31
Window Input Logic
0: Normally Open
1: Normally closed
32
Window Input Delay
0 - 300 seconds 30 seconds steps (30 seconds default)
33
Door Input Logic
0: Off (default)
1: Normally open
2: Normally close
34
Door Input Delay
0 - 300 seconds 30 seconds steps (30 seconds default)
35
PIR Input Delay
0: Off (default)
1 - 15minutes 1 minute steps
36
Reset Fan
0: Off 1: On
(resets indoor fan to auto every time mode is set to off)
37
Belimo Mode
0: Off 1: On
38
Modbus Address
1-255