Smart Temp SMT - 131 User Manual - Specifications
Page 21
400
67
Read Only
PIR Status
0:No Movement detected
1:Movement detected
400
68
Read Only
0-10V Fan Value
Value / 100 (e.g. 2.1V = 210)
400
69
Read Only
0-10V Fan Max
Value
0-10v (@*10)
400
70
Read / Write
Digital Input logic
0:Normally Open
1:Normally Closed
Specifications
Input Voltage
24VAC 50/60 Htz +/- 15%
Operating Temperature
0°C to 50°C (32°F to 122°F)
Operating RH
0-95% (Non Condensing)
Storage Temperature
0°Cto 65°C (32°F to 150°F)
Size
113 x 103 x 25mm.
Display Size
69.5 x 46.3mm.
Backlight
White LED (Other Colours Available Upon Request)
Display Type
STN Touch Panel
Relay Rating
30V @ 1Amp Max
0-10V Output Load
10mA Max
Control Range
5°C to 30°C (41°F to 86°F)
Memory Type
Non Volatile - Settings Do Not Require Battery Backup
Communications
Modbus RTU 4 .8K / 9.6K / 19.2 K
1 Stop Bit, 8 Data Bits, 1 Start Bit. No Parity.
Plastic
ABS / Poly Blend – UV Stabilised and Fire Rated
Warranty
3 Year RTB
Great care has been taken in the preparation of this manual. Smart Temp Australia P/L takes no
responsibility for errors or omissions contained in this document. It is the responsibility of the
user to ensure this controller or equipment connected to it, is operating to their respective
specifications and in a safe manner.
Due to ongoing product improvement Smart Temp Australia P/L reserves the right to change the
specifications of the SMT-131 thermostat (or its components) without notice.
All rights reserved. © Smart Temp Australia P/L 2011
Intellectual rights apply.