Hrx-om-i051-p 1 st edition:january.2005 17 th edition:sep.2016 operation manual original instructions thermo-chiller hrz001-l hrz002-l hrz004-l hrz008-l hrz001-l1 hrz002-l1 hrz004-l1 hrz008-l1 hrz001-l2 hrz002-l2 hrz004-l2 hrz008-l2 hrz001-h hrz002-h hrz004-h hrz008-h hrz001-h1 hrz002-h1 hrz004-h1 h...
To the customers thank you for purchasing our thermo chiller hrz series (hereinafter called “this system”). For the long-term, safe use of this system, be sure to read and understand this manual thoroughly before performing operation of this system. warnings and precautions defined in this manual ...
Hrx-om-i051 table of contents hrz series toc-1 table of contents chapter 1 safety.................................................................................... 1-1 1.1 before using this system ....................................................................................... 1-1 1.2 dange...
Hrx-om-i051 table of contents hrz series toc-2 3.3.4 wiring installation ................................................................................................................. 3-8 3.3.5 procedures for wiring installation .......................................................................
Hrx-om-i051 table of contents hrz series toc-3 5.4.2 example 2: communication mode is switched from “dio remote” to “local”. ........... 5-13 5.4.3 example 3: alarm signal of contact s ignal is changed from “n/a” to “alarm1”. ............. 5-14 chapter 6 error message and troubleshooting ..............
Hrx-om-i051 table of contents hrz series toc-4.
Hrx-om-i051 chapter 1 safety hrz series 1.1 before using this system 1-1 chapter 1 safety 1.1 before using this system this "safety" chapter describes the safety-related items that users should be aware of upon handling this system. This system, which is operated under high voltage, is outfitted wit...
Hrx-om-i051 chapter 1 safety 1.2 danger, warning, and caution used in this manual hrz series 1-2 1.2 danger, warning, and caution used in this manual 1.2.1 hazard levels this system is designed with its first priority being the safety of workers and the prevention of system damage. This manual class...
Hrx-om-i051 chapter 1 safety hrz series 1.2 danger, warning, and caution used in this manual 1-3 1.2.3 symbols this manual provides the following symbols in addition to “danger”, “warning”, and “caution” to present the warning details in easy-to-understand manner. symbol of electrical hazard sym...
Hrx-om-i051 chapter 1 safety 1.3 hazard warning label hrz series 1-4 1.3 hazard warning label the hazard warning labels are applied to the sections of this system where potential hazards are present during system operation and maintenance. The hazard warning labels are in appropriate sizes and color...
Hrx-om-i051 chapter 1 safety hrz series 1.3 hazard warning label 1-5 1.3.2 location of hazard warning label high voltage hazard figure 1-7 high voltage hazard confirm the locations of the hazard warning labels. read the contents of the hazard warning labels carefully and keep them in mind. Do ...
Hrx-om-i051 chapter 1 safety 1.3 hazard warning label hrz series 1-6 hot/cold surface hazard figure 1-8 hot/cold surface hazard front rear hazard warning label no.5 hazard warning label no.6.
Hrx-om-i051 chapter 1 safety hrz series 1.4 location of model label 1-7 1.4 location of model label information on your system such as serial no. And model no. Need to be furnished when you contact the store you purchased from. Serial no. And model no. Are listed on the label as shown below. Figure ...
Hrx-om-i051 chapter 1 safety 1.5 safety measures hrz series 1-8 1.5 safety measures 1.5.1 safety precautions while this system is protected by various safety measures including the safety interlocks, the following basic safety precautions should be observed to assure further safe operations. Read an...
Hrx-om-i051 chapter 1 safety hrz series 1.5 safety measures 1-9 1.5.2 safety interlock system safety interlock system the function of the safety interlock system is not only protect personnel by restricting operation that may cause damage to this system or the facility around it but also eliminate...
Hrx-om-i051 chapter 1 safety 1.5 safety measures hrz series 1-10 1.5.3 lockout/tagout summary lockout in this system disables the main breaker operation to prevent electric shocks. Tagout, to be placed on a locked out main breaker, to prevent improper breaker operation (on) conducted by other pers...
Hrx-om-i051 chapter 1 safety hrz series 1.5 safety measures 1-11 lockout procedure 1. Turn the breaker handle to ‘off ’. 2. Turn the breaker handle to ‘reset’. Hold the breaker handle with hand. The handle turns back to ‘off ’ if released. 3. Push the lock pushing part of the breaker handle, and...
Hrx-om-i051 chapter 1 safety 1.5 safety measures hrz series 1-12 1.5.4 protective equipment this manual defines protective equipment according to work type. Wear proper protective equipment as shown below, according to work type. for system transportation, installation and removal protective foo...
Hrx-om-i051 chapter 1 safety hrz series 1.6 emergency measures 1-13 1.6 emergency measures 1.6.1 emergency off [emo] switch press the red emergency off [emo] switch on the front of the system only if the need to shut off the power arises due to emergency such as natural disaster, fire, earthquake or...
Hrx-om-i051 chapter 1 safety 1.6 emergency measures hrz series 1-14 reset of emergency off [emo] switch 1. Before restarting, always make sure that the cause of the emergency off condition (the reason why the emo switch was activated) has been eliminated from the power supplies, the system and per...
Hrx-om-i051 chapter 1 safety hrz series 1.7 waste disposal 1-15 1.7 waste disposal 1.7.1 disposal of refrigerant and compressor oil hfc- refrigerant and compressor oil are present in this system. When recovering the refrigerant or compressor oil, the precautions provided below should thoroughly be r...
Hrx-om-i051 chapter 1 safety 1.8 material safety data sheet (msds) hrz series 1-16 1.7.2 circulating fluid disposal as to the disposal of a circulating fluid (ethylene glycol solution, fluorinated fluid), consign the specialized industrial waste disposal agency with the contents detailed. 1.7.3 syst...
Hrx-om-i051 chapter 2 name of each section hrz series 2.1 name of each section (1) 2-1 chapter 2 name of each section 2.1 name of each section (1) hrz001-l hrz002-l hrz004-l hrz001-l1 hrz002-l1 hrz004-l1 hrz001-l2 hrz002-l2 hrz004-l2 hrz008-l2 hrz001-h hrz002-h hrz004-h hrz008-h hrz001-h1 hrz002-h1 ...
Hrx-om-i051 chapter 2 name of each section 2.2 name of each section (2) hrz series 2-2 2.2 name of each section (2) hrz008-l hrz008-l1 figure 2-2 name of each section (2) when transporting the system with the casters, raise the adjustable feet (4 pcs.) to the highest position and lock them with the ...
Hrx-om-i051 chapter 3 transporting and installation hrz series 3.1 transporting 3-1 chapter 3 transporting and installation 3.1 transporting this system is heavy, which poses potential danger at transportation. When transporting this system, the following safety precautions should be observed to pre...
Hrx-om-i051 chapter 3 transporting and installation 3.1 transporting hrz series 3-2 3.1.1 transporting with forklift figure 3-1 transport with forklift this system is heavy, and requires a forklift to safely move it. forklift insertion positions are on either left or right side of this system. A...
Hrx-om-i051 chapter 3 transporting and installation hrz series 3.2 installation 3-3 3.1.2 transporting with caster 3.2 installation this system is heavy, which requires assistance for this work. Exercise caution and look out for sloped surfaces such as ramps, etc. Do not grab piping on the back of t...
Hrx-om-i051 chapter 3 transporting and installation 3.2 installation hrz series 3-4 3.2.1 installation conditions system installation is not allowed outside or in the conditions described below. Potential system malfunction and damage may occur if disregarded. Clean room specifications are not appli...
Hrx-om-i051 chapter 3 transporting and installation hrz series 3.2 installation 3-5 3.2.2 installation location and maintenance work area this system does not have ventilating hole on the both right and left sides. Although this can be installed directly contacting to walls or devices, installation ...
Hrx-om-i051 chapter 3 transporting and installation 3.3 procedure for installation hrz series 3-6 anti-seismic bracket is an optional part (except for hrz008-l, hrz008-l1), which is required for the installation of this system (hrz-tk002). preparation of anchor bolts suitable for floor material ...
Hrx-om-i051 chapter 3 transporting and installation hrz series 3.3 procedure for installation 3-7 3.3.3 procedure for system securing (2) hrz008-l hrz008-l1 adjust and secure the adjustable feet of this system to secure the anti-seismic bracket. 1. Transfer this system to the installation site. 2. A...
Hrx-om-i051 chapter 3 transporting and installation 3.3 procedure for installation hrz series 3-8 3.3.4 wiring installation power cable the power cables are to be prepared under your responsibility, referring to the following table. Table 3-1 power cable and main breaker (this system) item hrz001-...
Hrx-om-i051 chapter 3 transporting and installation hrz series 3.3 procedure for installation 3-9 selection of the breaker for the customer ’s equipment (primary side) hrz001-l hrz002-l hrz004-l hrz001-l1 hrz002-l1 hrz004-l1 hrz001-l2 hrz002-l2 hrz004-l2 hrz008-l2 hrz001-h hrz002-h hrz004-h hrz008...
Hrx-om-i051 chapter 3 transporting and installation 3.3 procedure for installation hrz series 3-10 hrz008-l hrz008-l1 hrz010-ws hrz010-w1s hrz010-w2s figure 3-8 breaker operating characteristics curve current (% to the capacity of the main breaker of this product) min o p e ra ti n g t im e 4h 2h 1h...
Hrx-om-i051 chapter 3 transporting and installation hrz series 3.3 procedure for installation 3-11 m a i f r screw breaker cover breaker front panel screw front main breaker off off 3.3.5 procedures for wiring installation 1. Turn off the power breaker on customer side (primary side), and then use t...
Hrx-om-i051 chapter 3 transporting and installation 3.3 procedure for installation hrz series 3-12 5. Loosen the cap and insert the power cable from the power cable access. 6. Connect the communication cables with p1 and p2. [tips] see “table 3-1 power cable and main breaker (this system)” on page 3...
Hrx-om-i051 chapter 3 transporting and installation hrz series 3.3 procedure for installation 3-13 7. Connect the power cables to the breaker terminal. Be sure to use a phillips screwdriver. See table 3-1 on page 3-8 for recommended torque. 8. Connect the grounding terminal (m8) of the power cable t...
Hrx-om-i051 chapter 3 transporting and installation 3.3 procedure for installation hrz series 3-14 3.3.6 installation of circulating fluid and facility water piping pipe diameter table 3-3 pipe diameter pipe diameter recommended torque (material: ss* vs ss) facility water inlet rc1/2 28 to 30n • m...
Hrx-om-i051 chapter 3 transporting and installation hrz series 3.3 procedure for installation 3-15 procedure for piping installation secure the pipe coupling section with a pipe wrench, and provide proper tightening to the pipe. recommended piping installation table 3-4 recommended pipe no. Name...
Hrx-om-i051 chapter 3 transporting and installation 3.3 procedure for installation hrz series 3-16.
Hrx-om-i051 chapter 4 system startup and shutdown hrz series 4.1 pre-check 4-1 chapter 4 system startup and shutdown 4.1 pre-check check the following items prior to starting up the system. 4.1.1 installation condition make sure that the system is installed in a horizontal position. No heavy object ...
Hrx-om-i051 chapter 4 system startup and shutdown 4.3 supply of circulating fluid hrz series 4-2 4.3 supply of circulating fluid 4.3.1 preparation of circulating fluid when the circulating fluid is a 60% ethylene glycol aqueous solution always check the concentration of the circulating fluid. wh...
Hrx-om-i051 chapter 4 system startup and shutdown hrz series 4.3 supply of circulating fluid 4-3 4.3.2 supply of circulating fluid remove the circulating fluid fill cap, and fill the circulating fluid until it reaches its specified level. The circulating fluid specified level is a range between “hig...
Hrx-om-i051 chapter 4 system startup and shutdown 4.4 requirement for system startup hrz series 4-4 4.4 requirement for system startup 4.4.1 turning on power 1. Make sure that the main breaker for this system is off, and release lockout/tagout of the power breaker on customer side (primary side). Th...
Hrx-om-i051 chapter 4 system startup and shutdown hrz series 4.5 system startup and shutdown 4-5 4.4.2 circulating fluid temperature setting from the “setting screen” on the lcd screen, set the circulating fluid at any temperature. See section 5.4 “examples of system operation” in “chapter 5 system ...
Hrx-om-i051 chapter 4 system startup and shutdown 4.5 system startup and shutdown hrz series 4-6.
Hrx-om-i051 chapter 5 system operation hrz series 5.1 operation display panel 5-1 chapter 5 system operation 5.1 operation display panel use the operation display panel located in front of the system for the basic operations. Figure 5-1 operation display panel be sure to use your fingers only to ope...
Hrx-om-i051 chapter 5 system operation 5.2 flow chart of operation screen hrz series 5-2 5.2 flow chart of operation screen figure 5-2 flow chart of operation screen [tips] with the press of the [sel] key, the screen is swi tched to the “menu screen 1” regardless of the screen status. Table 5-1 desc...
Hrx-om-i051 chapter 5 system operation hrz series 5.3 operation screen 5-3 5.3 operation screen 5.3.1 model indication screen figure 5-3 model indication screen the “model indication screen” is displayed upon power-on of this system. This screen remains on for approx. 20 seconds and is automatically...
Hrx-om-i051 chapter 5 system operation 5.3 operation screen hrz series 5-4 5.3.3 status screen 2 figure 5-5 status screen 2 table 5-4 status screen 2 no. Item descriptions 1 temp pv discharge temperature of the circulating fluid (a value derived according to the offset *1 if applied) 2 temp sp set c...
Hrx-om-i051 chapter 5 system operation hrz series 5.3 operation screen 5-5 5.3.5 status screen 4 figure 5-7 status screen 4 table 5-6 status screen 4 no. Item descriptions 1 temp pv discharge temperature of the circulating fluid 2 temp sp set circulating fluid temperature 3 > displays the band/ready...
Hrx-om-i051 chapter 5 system operation 5.3 operation screen hrz series 5-6 5.3.7 setting screen figure 5-9 setting screen this screen enables the setting of temp sp value. Not available if the communication mode is in “ser remote” *1 . Table 5-8 setting screen no. Item setting range 1 temp sp hrz□□□...
Hrx-om-i051 chapter 5 system operation hrz series 5.3 operation screen 5-7 5.3.8 mode selection screen figure 5-10 mode selection screen this screen enables the selection of the communication mode. The procedures for system start/stop and temp sp value setting may vary with the communication mode. O...
Hrx-om-i051 chapter 5 system operation 5.3 operation screen hrz series 5-8 this screen enables the setting of set values. Table 5-10 initial setting screen no. Item setting range descriptions 1 temp band 1.0 to 5.0°c *1 allows the selection of the band width for temp sp. 2 temp ready 10 to 480sec *1...
Hrx-om-i051 chapter 5 system operation hrz series 5.3 operation screen 5-9 5.3.10 maintenance screen figure 5-12 maintenance screen table 5-11 maintenance screen no. Item setting 1 valve open the solenoid valve is opened forcefully. Close the solenoid valve is closed forcefully. [tips] available onl...
Hrx-om-i051 chapter 5 system operation 5.3 operation screen hrz series 5-10 5.3.12 alarm display screen figure 5-14 alarm display screen in the event of an error in this system, the current screen is switched to the alarm display screen to display the relevant alarm code. And message. The alarm disp...
Hrx-om-i051 chapter 5 system operation hrz series 5.4 examples of system operation 5-11 5.4 examples of system operation 5.4.1 example 1: circulating fluid set temperature is changed from 23.0°c to 34.1°c. Figure 5-16 change of set temperature from 25.0°c to 34.1°c 1. Press the [sel] key to displ ay...
Hrx-om-i051 chapter 5 system operation 5.4 examples of system operation hrz series 5-12 4. Use the arrow keys ([▲], [▼], [ ]) to change the temperature to 34.1°c. [▲] key: used to add one value on which the cursor is placed. [▼] key: used to subtract one value on which the cursor is placed. [ ] key:...
Hrx-om-i051 chapter 5 system operation hrz series 5.4 examples of system operation 5-13 5.4.2 example 2: communication mode is switched from “dio remote” to “local”. Figure 5-22 switching of communication mode from “dio remote” to “local” 1. Press the [sel] key to display the “menu screen 1”. Figure...
Hrx-om-i051 chapter 5 system operation 5.4 examples of system operation hrz series 5-14 5.4.3 example 3: alarm signal of contact signal is changed from “n/a” to “alarm1”. Figure 5-27 change of alarm signal of contact signal from “n/a” to “alarm1” 1. Press the [sel] key to display the “menu screen 1”...
Hrx-om-i051 chapter 5 system operation hrz series 5.4 examples of system operation 5-15 5. Use the arrow keys ([▲], [▼]) to select “alarm1”. Figure 5-32 initial setting screen 3: alarm1 6. Press the [ent] key. “out” flashes again, and the selection takes effect. Figure 5-33 initial setting screen 3:...
Hrx-om-i051 chapter 5 system operation 5.4 examples of system operation hrz series 5-16.
Hrx-om-i051 chapter 6 error message and troubleshooting hrz series 6.1 error message 6-1 chapter 6 error message and troubleshooting 6.1 error message the following are to be performed in the event of an error in this system. The “alarm” lamp comes on. Alarm buzzer comes on. The “alarm display scree...
Hrx-om-i051 chapter 6 error message and troubleshooting 6.2 troubleshooting hrz series 6-2 6.2 troubleshooting the procedure for error recovery varies with alarm types. Alarm code.01 to 20, 22, 24, 25: eliminate the error cause. Press the [reset] key on the operation display panel or power cycle the...
Hrx-om-i051 chapter 6 error message and troubleshooting hrz series 6.2 troubleshooting 6-3 table 6-1 troubleshooting (2/2) code error message system condition cause remedies 12 return low flow flt stop the flow rate of the circulating fluid falls short of 6l/min. Check that the external valve is ope...
Hrx-om-i051 chapter 6 error message and troubleshooting 6.2 troubleshooting hrz series 6-4.
Hrx-om-i051 chapter 7 system maintenance hrz series 7.1 water quality management 7-1 chapter 7 system maintenance 7.1 water quality management table 7-1 water quality standards for fresh water (tap water) substance facility water spec. Circulating water spec. Standards ph (25°c) 6.5 to 8.2 6.0 to 8....
Hrx-om-i051 chapter 7 system maintenance 7.2 inspection and cleaning hrz series 7-2 7.2 inspection and cleaning 7.2.1 daily inspection table 7-2 daily inspection inspection item inspection method installation condition check of the condition of system installation no heavy object is placed on this s...
Hrx-om-i051 chapter 7 system maintenance hrz series 7.3 storage 7-3 7.2.2 quarterly inspection table 7-3 quarterly inspection inspection item inspection method circulating fluid circulating fluid is to be drained for check. Fluid should be free of particles, moisture *1 and foreign substances. For e...
Hrx-om-i051 chapter 7 system maintenance 7.3 storage hrz series 7-4 7.3.1 draining of circulating fluid out of tank 1. Prepare the container for circulating fluid recovery at the back of this system. 2. Connect the drain hoses to the main and sub tank drain ports each. Insert the tip of the hose int...
Hrx-om-i051 chapter 7 system maintenance hrz series 7.3 storage 7-5 plug circulating fluid supply facility water outlet circulating fluid return plug rear drain pan port plug facility water inlet main tank drain port sub tank drain port 6. Upon completion of fluid draining, close the valves of the m...
Hrx-om-i051 chapter 7 system maintenance 7.4 periodic replacement parts hrz series 7-6 2. Remove facility water piping. Remove the joints such as unions if present. 3. Drain the facility water using the facility water inlet port. 7.4 periodic replacement parts replacement of consumables listed in th...
Hrx-om-i051 chapter 8 appendix hrz series 8.1 specification 8-1 chapter 8 appendix 8.1 specification 8.1.1 system specification specification for fluorinated fluid (low temperature) table 8-1 specification for fluorinated fluid (low temperature) model hrz001-l hrz002-l hrz004-l hrz008-l cooling me...
Hrx-om-i051 chapter 8 appendix 8.1 specification hrz series 8-2 specification for fluorinated fluid (high temperature) table 8-2 specification for fluorinated fluid (high temperature) model hrz001-h hrz002-h hrz004-h hrz008-h cooling method water cooled refrigerant cooling capacity *1 (50hz/60hz) ...
Hrx-om-i051 chapter 8 appendix hrz series 8.1 specification 8-3 specification for fluorinated fluid (wide temperature) table 8-3 specification for fluorinated fluid (wide temperature) model hrz002-w hrz008-w cooling method water cooled refrigerant cooling capacity *1 (50hz/60hz) kw 2.0 (at 20°c) 8...
Hrx-om-i051 chapter 8 appendix 8.1 specification hrz series 8-4 specification for ethylene glycol solution (low temperature) table 8-4 specification for ethylene glycol aqueous solution (low temperature) model hrz001-l1 hrz002-l1 hrz004-l1 hrz008-l1 cooling method water cooled refrigerant cooling ...
Hrx-om-i051 chapter 8 appendix hrz series 8.1 specification 8-5 specification for ethylene glycol solution (high temperature) table 8-5 specification for ethylene glycol aqueous solution (high temperature) model hrz001-h1 hrz002-h1 hrz004-h1 hrz008-h1 cooling method water cooled refrigerant coolin...
Hrx-om-i051 chapter 8 appendix 8.1 specification hrz series 8-6 specification for ethylene glycol solution (wide temperature) table 8-6 specification for ethylene glycol aqueous solution (wide temperature) model hrz002-w1 hrz008-w1 cooling method water cooled refrigerant cooling capacity *1 (50hz/...
Hrx-om-i051 chapter 8 appendix hrz series 8.1 specification 8-7 specification for water (low temperature) table 8-7 specification for water (low temperature) model hrz001-l2 hrz002-l2 hrz004-l2 hrz008-l2 cooling method water cooled refrigerant cooling capacity *1 (50hz/60hz) kw 1.0 (at 20°c) 2.0 (...
Hrx-om-i051 chapter 8 appendix 8.1 specification hrz series 8-8 specification for fluorinated fluid (wide temperature with inverter) table 8-8 specification for fluorinated fluid (wide temperature with inverter) model hrz010-ws cooling method water cooled refrigerant cooling capacity *1 (50hz/60hz...
Hrx-om-i051 chapter 8 appendix hrz series 8.1 specification 8-9 specification for ethylene glycol solution (low temperature with inverter) table 8-9 specification for ethylene glycol solution (low temperature with inverter) model hrz010-w1s cooling method water cooled refrigerant cooling capacity ...
Hrx-om-i051 chapter 8 appendix 8.1 specification hrz series 8-10 specification for water (low temperature with inverter) table 8-10 specification for water (low temperature with inverter) model hrz010-w2s cooling method water cooled refrigerant cooling capacity *1 (50hz/60hz) kw 9.0 (at 20°c) oper...
Hrx-om-i051 chapter 8 appendix hrz series 8.1 specification 8-11 8.1.2 communication specification this section provides the general outline of communications utilized in this system. For detail specification, we provide a separate system manual “communication specification”, which is available thro...
Hrx-om-i051 chapter 8 appendix 8.1 specification hrz series 8-12 serial rs-485 table 8-12 serial rs-485 item specification connector no. P2 connector type (this system) d-sub9p female connector standard eia rs485 protocol modicon modbus circuit block diagram internal circuit this system your syste...
Hrx-om-i051 chapter 8 appendix hrz series 8.1 specification 8-13 8.1.3 alarm signal selection user can designate one alarm signal for contact signal. See section 5.3.9 “initial setting screen” for signal selecting. The following table presents the setting-alarm relationship. The alarm signal is turn...
Hrx-om-i051 chapter 8 appendix 8.2 outer dimensions hrz series 8-14 8.2 outer dimensions 8.2.1 part 1 hrz001-h hrz001-h1 hrz002-h hrz002-h1 figure 8-1 outer dimensions 8.2.2 part 2 hrz001-l hrz002-l hrz004-l hrz008-l2 hrz001-l1 hrz002-l1 hrz004-l1 hrz008-h hrz001-l2 hrz002-l2 hrz004-l2 hrz008-h1 hrz...
Hrx-om-i051 chapter 8 appendix hrz series 8.2 outer dimensions 8-15 8.2.3 part 3 hrz008-l hrz008-l1 figure 8-3 outer dimensions top left back front.
Hrx-om-i051 chapter 8 appendix 8.3 flow chart hrz series 8-16 8.3 flow chart 8.3.1 part 1 hrz001-h hrz002-h hrz004-h hrz008-h hrz001-h1 hrz002-h1 hrz004-h1 hrz008-h1 hrz002-w hrz008-w hrz002-w1 hrz008-w1 hrz010-ws hrz010-w1s hrz010-w2s figure 8-4 flow chart facility water circuit circulating fluid c...
Hrx-om-i051 chapter 8 appendix hrz series 8.3 flow chart 8-17 8.3.2 part 2 hrz001-l hrz002-l hrz004-l hrz008-l hrz001-l1 hrz002-l1 hrz004-l1 hrz008-l1 hrz001-l2 hrz002-l2 hrz004-l2 hrz008-l2 figure 8-5 flow chart facility water circuit circulating fluid circuit compressor refrigerant pressure gauge ...
Hrx-om-i051 chapter 8 appendix 8.4 offset function hrz series 8-18 8.4 offset function potential deviations in temperature between this system and your system may be concerned depending on the installation environment. The offset function falling into three types (mode1 to 3) is assigned to calibrat...
Hrx-om-i051 chapter 8 appendix hrz series 8.4 offset function 8-19 8.4.1 example of offset function when the discharge temperature of the circulating fluid is at 30°c, heat is dissipated by 1°c to allow the circulating fluid in your system to be 29°c. Under the above condition, the following process...
Hrx-om-i051 chapter 8 appendix 8.4 offset function hrz series 8-20 when mode2 is selected with offset value set at -1°c, temp pv and communication data express “29°c” (circulating fluid discharge temp. Value + offset value) that agrees with the temperature of the circulating fluid in your system. ...
Hrx-om-i051 chapter 8 appendix hrz series 8.5 band/ready function 8-21 8.5 band/ready function sets band to temp sp value, and notifies temp pv value reaches within band range by the operation display panel or the communication. See section “5.3.9 initial setting screen” on page 5-7, “5.3.11 option ...
Hrx-om-i051 chapter 8 appendix 8.6 anchor bolt mounting position hrz series 8-22 8.6 anchor bolt mounting position 8.6.1 part 1 hrz001-l hrz002-l hrz004-l hrz001-l1 hrz002-l1 hrz004-l1 hrz001-l2 hrz002-l2 hrz004-l2 hrz008-l2 hrz001-h hrz002-h hrz004-h hrz008-h hrz001-h1 hrz002-h1 hrz004-h1 hrz008-h1...
Hrx-om-i051 chapter 8 appendix hrz series 8.6 anchor bolt mounting position 8-23 8.6.2 part 2 hrz008-l hrz008-l1 adjust and secure the adjuster foot of this system to secure the anti-seismic bracket. Figure 8-12 anchor bolt mounting position anchor bolt anchor bolt adjustable foot top anchor bolt an...
Hrx-om-i051 chapter 8 appendix 8.7 compliance hrz series 8-24 8.7 compliance this system conforms to the following standards. Table 8-14 compliance ce marking emc directive 2004/108/ec low voltage directive 2006/95/ec machinery directive 2006/42/ec sematech s2-93, s8-95 semi s2-0703, s8-0701, f47-02...
Hrx-om-i051 chapter 8 appendix hrz series 8.8 thermo chiller daily inspection sheet 8-25 8.8 thermo chiller daily inspection sheet t o c o n firm d a ily ins p e c tion it e m o n t h e t he rmo c hil ler , s ee “ t a b le 7 -2 d a ily i n s p e c tion ” in “7 .2 .1 d a ily ins p e c tion ” of “ c h...
Product warranty 1. Warranty if a failure is observed in our thermo chiller, repair shall be provided in accordance with the warranty period and preconditions defined below at smc’s option. Repair involves the inspection and/or replacement and/or modification of a defective part. Removed parts shall...