Taco D’MAND Installation And Wiring Instructions - D'Mand System Control Board
3. Remove electrical box cover and carefully remove electronics con-
trol board from terminal strip.
4. Turn control board over and locate voltage dip switches in top left
corner of board. (See diagram below.)
5. Slide dip switch connector from pin marked “5v” to pin marked
“12v”. (See diagram below.)
6. Insert control board firmly into terminal strip and replace electrical
box cover.
7. Place Motion Sensor at a convenient location to detect motion in
the room but out of view from adjoining rooms or hallways.
8. Plug in the D’Mand System power cord. Pump will start automatically,
run until hot water is detected by the temperature sensor, and then
stop.
9. A 4 minute time delay will start after each cycle to prevent repeated
activation. After 4 minutes, D’Mand System will revert to automatic
motion detection mode.
D'MAND SYSTEM CONTROL BOARD
5v 12v
VOLTAGE
DIP SWITCHES
(Set on 12v for
Motion Sensor activation)
ΔT ADJUSTMENT
(Set on 12 o’clock
position for 5˚ ΔT)
Do it Once. Do it Right.
®