2.3 CH pump operation
If the buffer temperature exceeds the preset value of 45 C (the
parameter) the CH pump turns on.
During loading the warm applicable water container WAW, the CH pump runs cyclically if the WAW
mode is set to
(Limitation of the heat amount flowing into the CH system).
The cyclical operation is based on turning on the pump for 45 secs and then turning off for 4mins (the
parameter).
The control unit protects the system from freezing, automatically turning on the circulating pump if
the measured temperature is below 4 C.
The control unit realizes the after season rundown of the pump by switching it on for 1 min if it
doesn
’
t operate for a week.
o
o
Switch-on Temp. of PUMPS
Stoptime of CH PUMP
PRIORITY
2.4 WAW pump operation
The control unit controls as well the pump loading the warm applicable water container WAW.
The loading pump can be turned on if water temperature in the fireplace is higher than the preset
threshold of 45 C (the
parameter) and higher than in the WAW container
by 5 C (the
parameter).
The WAW pump turns on if the temperature of the WAW container is below 50 C (the
parameter) and turns off if the temperature is above 60 C (the
parameter)
! Loading the WAW container can be switched off in the active ECO zone if the
parameter is set to OFF
!Lack of the temperature sensor of the WAW container causes loading the container at will. The
WAW pump switches on if water temperature in the water jacket of the fireplace reaches the preset
value or is above 50 C (the
parameter).
After ending the loading of the WAW the pump can run for a while (
parameter), which prevents temperature increase of the water jacket especially in summer
time when the CH pump doesn
’
t run.
The control unit realizes the after season rundown of the pump by switching it on for 1 min if it
doesn
’
t operate for a week.
o
o
o
o
o
>
PumpWAWtemp.ON
Delta Temp. of WAW
Minimum temp. of WAW
Maximum temp. of WAW
WAW in ECO
zone
Minimum temp. of WAW
Rundown Time of WAW
PUMP
Connection cable of the control may be replaced only
by producer or his authorized service locations
WARRANTY
WARNING !
ANY MODIFICATION OF THE CONTROL UNIT MADE BY A USER CAN
BE THE CAUSE OF SAFETY CONDITIONS DETERIORATION AND CAN
EXPOSE THE USER TO ELECTRIC SHOCK OR DAMAGE DEVICES
SUPPLIED
.
Date of sale
Seller's signature and stamp
Zak
ł
ad elektroniczny TATAREK Jerzy Tatarek
50-559 Wroclaw, 75 Swieradowska st
ph. (071) 367-21-67, 373-14-88, fax 373-14-58; tax index number 899-020-21-48;
Bank account : BZ WBK S.A. O/WROC
Ł
AW 6910901522-0000-0000-5201-9335
www.tatarek.com.pl.; E-mail: tatarek@tatarek.com.pl
1.Warranty is valid [24] months from the date of sale.
2.Producer does not take responsibility for any mechanical damages made by user.
3.MAKING REPAIRS OR MODYFYING THE DEVICE BY USER IS
FORBIDDEN AND CAUSES WARRANTY CANCELATION
4.Warranty card is valid only with date of sale, seller's signature and stamp
5.Warranty and after-warranty repairs should be done only by producer, damaged
regulators should be sent to producer in order to make all repairs needed.
6.Warranty protection involves the EU
7.Warranty does not exclude, not restrict and not suspend buyer
’
s rights coming from
the incompatibility of the article with the agreement (Laws Journal No. 141 Pos. 1176)
WARNING!
1. Producer does not take the responsibility for damage
caused by atmospheric discharge
2. and overvoltage in the mains
3. Burnt fuses are not subject to warranty replacement
Register No.. GIOS: E 0002240WZ
Worn out electronic
and electric devices must be transfered to
the utilization collection place, where will
be accepted for free
ARGO-FILM
Recycling Plant No. 6
180 Krakowska st., 52-015 Wroclaw
ph.: 071 794 43 01,
0 515 122 142
2.2 Operation of the loading pump of the buffer
The control unit controls the pump loading the buffer. The BUF pump (P2) can be switched on if
water temperature in the fireplace is above the preset threshold 48
o
o
o
C (
) and higher than temperature in the container by 2 C (
).
Turning off the pump below the parameter
causes a faster heating of the
water jacket above the dew point and as a result the longer life time of the fireplace.
The control unit protects the system from freezing, automatically turning on the circulating pump if
the measured temperature is below 4 C.
The control unit realizes the after season rundown of the pump by switching it on for 1 min if it
doesn
’
t operate for a week.
parameter
PumpBUFtemp.ON
parameter “DeltaBUF”
PumpBUFtemp.ON