Tau DOOR Installation Manual - page 21
17
DOOR Series -
English
f)
Once the
UPLOAD has been completed, the red BATTERY LED and the yellow PHOTOCELL3 LED will light up.
g)
The battery LED signals that the
S1 MINIDIP is being operated, while the photocell 3 LED signals:
g1)
DIP1 of S1 in the ON position if the LED shows a steady light .
g2)
DIP1 of S1 in the OFF position if the LED shows a flashing light.
h)
To change the status of the
DIP (ON -OFF), press the WINTER OPENING button
.
i)
To go to
DIP2 of S1, press the PHARMACY OPENING button
.
l)
Repeat the last operation above to go to the other
DIPS of S1.
m)
Refer to
TABLES 5 and 6 for the meaning of the DIPS.
n)
To operate
MINIDIP S2, press the SET button
, a
POWER LED will light up.
o)
Repeat the operations described for
MINIDIP S1 to select and change the status of the single DIPS.
p)
To go to
POTENTIOMETER TM1, press the SET button
the
2-WAY traffic LED
will light up.
q)
When you operate the potentiometers, the inputs LED’s will form a scale to indicate the set value.
r )
To change the value of the selected potentiometer, press:
r1)
the
WINTER OPENING button
to lower the value.
r2)
the
PHARMACY OPENING button
to increase the value.
s)
To go to
POTENTIOMETER TM2, press the SET button
.
t)
Repeat the last operation above to go to the other potentiometers.
u)
Refer to
TABLE 7 for the meaning of the potentiometers.
v)
To exit the programming mode and memorize the modified values, proceed as follows:
v1) Set the selector switch’s
locking key in the locked functions position .
v2) Press and hold down the selector switch’s
SET button
.
v3) Return the
locking key to the free functions position .
v4) Release the
SET button
.
v5) The inputs LED’s will light up sequentially from right to left to signal the DOWNLOAD.
v6) Once the
DOWNLOAD has been completed, the control unit will emit 2 beeps.
v7) The selector switch will return to normal operation.
z)
To exit the programming mode without memorizing the modified values, proceed as follows:
z1) Set the selector switch’s
locking key in the locked functions position ;
z2) Return the
locking key to the free functions position ,
z3) The selector switch will return to normal operation and the control unit will emit 1 beep.
15.4_ RESET OPERATION
To RESET the control unit without disconnecting the mains power source, proceed as follows: access the programming mode with
selector DOORPROG, follow steps A) to E) in section 15.3, then quit the programming mode by following steps Z1) to Z3) of section
15.3.