TCS Basys Controls SZ1009 User Manual

Other manuals for SZ1009: Product Manual
Manual is about: Conventional Heating & Cooling Thermostats

Summary of SZ1009

  • Page 1

    R 2800 laura lane l middleton, wi 53562 l (800) 288-9383 l fax (608) 836-9044 l www.Tcs-basys.Com 1 r communicating thermostats sz1009/sz1022/ sz1031/sz1035 conventional heating & cooling thermostats product manual description the sz1009, sz1022, sz1031 and sz1035 are microproces- sor-based programm...

  • Page 2

    Powering the superstat superstats are powered from 24 vac +/- 20%. If wiring for communications, dedicated power must be used to power the superstat. Several “s” series thermostats may be powered from the same transformer, provided that the trans- former has sufficient power. (superstats require 8 v...

  • Page 3

    R 2800 laura lane l middleton, wi 53562 l (800) 288-9383 l fax (608) 836-9044 l www.Tcs-basys.Com 3 setup note: if using remote sensor(s), the calibration may need to be adjusted. See “checkout and troubleshooting” section. Temperature sensor selection the dipswitches in the cover (shown above) must...

  • Page 4

    R 2800 l a ura l ane l middleton, wi 53562 l (800) 288-9383 l f ax (608) 836-9044 l www .Tcs-basys.Com 4 programming the sz1009, sz1022, sz1031 and sz1035 may be pro- grammed through the keypad on the face, or with a pc. If programming with a pc, the following must be set via the display and keypad ...

  • Page 5

    R 2800 laura lane l middleton, wi 53562 l (800) 288-9383 l fax (608) 836-9044 l www.Tcs-basys.Com 5 program setup program setup program setup program setup program setup program setup heat stage 1 21. Offset: 0f enable third cool stage as: 20. 18. Enable second stage cool? Enable second stage heat? ...

  • Page 6

    R 2800 laura lane l middleton, wi 53562 l (800) 288-9383 l fax (608) 836-9044 l www.Tcs-basys.Com 6 program setup program setup program setup program setup program setup program setup program setup program setup 40. 39. 38. 37. 36. 35. 34. 33. 32. Cool stage 3 diff: program setup enable discharge ai...

  • Page 7

    R 2800 laura lane l middleton, wi 53562 l (800) 288-9383 l fax (608) 836-9044 l www.Tcs-basys.Com 7 setting clock & schedule the sz1009, sz1022, sz1031 and sz1035 clock and sched- ule may be set through the keypad and display, or with a pc. For more information on programming through the pc, con- su...

  • Page 8

    R 2800 laura lane l middleton, wi 53562 l (800) 288-9383 l fax (608) 836-9044 l www.Tcs-basys.Com 8 operation unoccupied setback the sz1009, sz1022, sz1031 and sz1035 operate in either an occupied or unoccupied mode. During the occupied mode, the occupied heating and cooling setpoints will be mainta...

  • Page 9

    R 2800 laura lane l middleton, wi 53562 l (800) 288-9383 l fax (608) 836-9044 l www.Tcs-basys.Com 9 d12 setpoint shift the sz1009, sz1022, sz1031 and sz1035 allow di2 to be set for setpoint shift for energy demand setback. This is enabled by setting di2 to the monitor mode. A digital con- tact that ...

  • Page 10

    R 2800 laura lane l middleton, wi 53562 l (800) 288-9383 l fax (608) 836-9044 l www.Tcs-basys.Com 10 p + i option the sz1009, sz1022, sz1031 and sz1035 also have a p+i option. Without enabling this option, stages turn on and off based on temperature vs. Setpoint alone, as described above. By enablin...

  • Page 11

    Override 178 minutes heat stage 1 off 4. 5. Heat stage 2 off service status service status on r 2800 laura lane l middleton, wi 53562 l (800) 288-9383 l fax (608) 836-9044 l www.Tcs-basys.Com 11 9. Press the warmer button until the cooling setpoint is greater than the current temperature by one degr...

  • Page 12

    Limiting occupant access setpoint adjustment the occupant may temporarily change the occupied heating and cooling setpoints +/- 5’f by factory default. This setpoint change will remain until the end of the current occupied peri- od, at which time the program reverts to the setpoints defined in progr...