Theben TR 610 top3 Manual

Summary of TR 610 top3

  • Page 1

    1 tr 610 top3 6100130 tr 612 top3 6120130 307253 time switch en 1. Basic safety information danger of death through electric shock or fire! ¾ ¾ installation should only be carried out by a qualified electrician! Warning • the device is designed for installation on din top hat rails (in accordance wi...

  • Page 2

    2 4. Device description display & buttons 0 6 12 18 24 menu ok ok menu programmed switching times date display channel status c1, c2 on off time display days of the week from 1 to 7 display of the active buttons with the relevant function – activate display – open menu – cancel menu – esc (leave men...

  • Page 3

    3 5. Settings and functions set switching time channel c1 same switching time for several days = block switching time for one day program menu new check modify delete end mem free 56 on hour minute monday save copy add tuesday u u save u u l a switching time always consists of a start time and an en...

  • Page 4

    4 setting holiday function manual channel c1 menu perm on perm off overr on holiday end on begin holiday end holiday u ... ... ¾ press menu ¾ select manual and press ok to confirm ¾ select channel c1 or c2, confirm with ok ¾ select holiday and press ok to confirm ¾ select on and press ok to confirm ...

  • Page 5

    5 u u u u u obelisk copy obelisk -> tswi copy tswi -> obelisk run obelisk check obelisk end overwrite ok u bluetooth copy all data copy program end connect time switch, bluetooth obelisk top3 and smartphone (via app) the devices in the top3 range can be programmed using an app (for android, ios) on ...

  • Page 6

    6 6. Technical data operating voltage: 230 v ac +10 % / –15 % frequency: 50–60 hz standby: 0,4 w max switching capacity: 16 a (at 250 v, cos ϕ = 1) switching capacity: 10 a (at 250 v, cos ϕ = 0,6) min. Switching capacity: 10 ma/230 v ac 100ma/ 24 v ac/dc switch output: switching of any phase is per-...