11. TROUBLESHOOTING
Call or e-mail customer service for free consultation during business hours (central time)
at: 1-800-553-6418; 1-651-653-7000; fax: 1-888-439-3565; 1-651-653-7600
e-mail: inverterinfo@sensata.com; http://dimensions.sensata.com
1) No AC output power:
1.1) No LEDs on:
• Check in-line fuse which is located within 18” from the battery’s positive post.
• DC connections to be tight and clean.
• Battery voltage to be above 9 VDC.
• Bypass or disconnect remote On/Off switch if used.
1.2) Green LED “Inverter Power” on: Disconnect all loads and connect a test
light to the GFCI output outlet (make sure all breakers are reset)
• If test light is on: Check your AC connections and loads.
• If test light is off: Possible bad GFCI or transfer relay
1.3) Green LED “External Power” on: Repeat 1.2 steps above.
2)
Red LED “Low Battery” on:
The use of battery isolator is not recommended
due to excessive voltage drop across terminals
• Battery voltage to be above 10.5 when vehicle’s engine is OFF, and above 13
VDC when it is ON.
• Check for proper DC wire gage (see wire gauge & fusing section)
3)
Red LED “Overload” on:
Unplug all loads, and reset the inverter On/Off:
• If the overload condition persist, possible bad inverter.
• Overload conditions clears, check for short circuits or check load size versus
inverter output wattage size.
4)
Red LED “High Temp.” on:
Let the inverter to cool down to 40°C (104°F)