V2 City7 Instruction Manual

Other manuals for City7: Manual
Manual is about: ANALOGUE CONTROL UNIT FOR SLIDING GATES

Summary of City7

  • Page 1

    Il n. 252 ediz. 22/06/2011 v2 s.P.A. Corso principi di piemonte, 65/67 12035 racconigi (cn) italy tel. +39.0172.812411 - fax +39.0172.84050 www. Remotecontrolgates.Co.Uk city7 centrale di comando analogica per cancelli a battente i analogue control unit for swing gates gb armoire de commande analogi...

  • Page 3: Index

    English 13 index important remarks ........................................................................................................14 declaration of conformity ........................................................................................14 description of the control unit.............

  • Page 4: Important Remarks

    English 14 important remarks for any installation problem please contact our customer service at the number +39-0172.812411 operating monday to friday from 8:30 to 12:30 and from 14:00 to 18:00. V2 has the right to modify the product without previous notice; it also declines any responsibility to da...

  • Page 5: Technical Specifications

    English 15 description of the control unit the city7 control unit is an innovative v2 product guaranteeing safety and reliability for swing gate automation. The city7 design has been aimed at creating a product which adapts to suit all needs, thus obtaining an extremely versatile control unit satisf...

  • Page 6: Installation

    English 16 installation installation of the control unit, the safety devices and accessories must be performed with the power supply disconnected. Power supply the control unit must be powered by means of a 230 v - 50 hz or 120 v - 60 hz power line, depending on the model, protected by a differentia...

  • Page 7: Photocells

    English 17 photocells the control unit has a 24vac power supply for photocells with switch normally closed, and can perform an operational test before to starting the gate opening procedure. The photocell can be used with two settings: 1. Photocell always active: intervention of the photocell during...

  • Page 8: Start Input

    English 18 start input the start input is preset for connecting devices with the switch normally open. Function depends on the mode of operation set by means of dip-switch 4. Step mode subsequent start command cause, in order: opening stop closure stop “inversion” mode start during opening causes cl...

  • Page 9: Plug-In Receiver

    English 19 plug-in receiver the control unit is suitable for plugging-in an mr1 series receiver with high sensitivity super-heterodyne architecture. M please note: disconnect the power to the control unit before performing the following operations. Pay the utmost attention to the direction of insert...

  • Page 10

    English 20 electrical connection table l1 antenna l2 antenna shield l3 opening command for a standard connection device with switch normally open. L4 pedestrian opening command for a standard connection device with switch normally open. L5 stop command. N.C. Switch l6 photocell. N.C. Switch l7 edge....

  • Page 11: Operational Times

    English 21 adjustment of the power and operational times the power and operating times may be adjusted by means of 4 trimmers located on the control unit: power: motor power. Work: motor operating time (2 - 50 seconds). M please note: it is recommended that operating times be set with the slow down ...

  • Page 12

    English 22 programming the operational logic it is possible for the control unit to use several different operational logic states, by simply moving the dip- switches located on the card. The functions associated with each individual dip-switch are listed below. Dip function setting description 1 pr...

  • Page 13

    English 23 dip function setting description 8 photocell on always active intervention of the photocell during opening or closing causes the gate to stop. When the photocell restores, the gate re-opens completely. Off not active during opening intervention of the photocell during opening is ignored. ...