VAC V200E Installation, Operation And Maintenance Instructions

Manual is about: V200 Positioner

Summary of V200E

  • Page 1

    V200 positioner www.Vacaccessories.Com 92026r15 1.

  • Page 3: V200 Positioner

    V200 positioner www.Vacaccessories.Com 92026r15 3 1 introduction .................................................................................. 4 1.1 principle of operation .............................................................. 4 1.2 productidentification ...................................

  • Page 4: Www.Vac.Se

    Www.Vac.Se 92026r15 v200 positioner 4 1.1 principle of operation thev200incorporatestheforcebalance principal of operation. The desired value, in theformofpressure,affectsthemembrane(1) with the force that is created and transferred to the balance arm(2). The opposing force, which represents the act...

  • Page 5: V200 Positioner

    V200 positioner www.Vacaccessories.Com 92026r15 5 caution: beware of moving parts when positioner is operated! Caution: beware of parts with live voltage! A voltage, which is normally not dangerous, is supplied to the positioner. Avoid touching live parts and bare wires as well as short circuiting l...

  • Page 6: Www.Vac.Se

    Www.Vac.Se 92026r15 v200 positioner 6 connection back iii.Ep s 2. Installation 2.1 connections s–supplyair v200p:max.145psi/1mpa v200e:23-145psi/0,15-1mpa i–input,pressuresignal v200p:3-15psi/20-100kpa v200e:plugged i e –input,currentsignal v200e:4-20ma(rimax250ohm) v200p:plugged c+ -actuatorconnect...

  • Page 7: V200 Positioner

    V200 positioner www.Vacaccessories.Com 92026r15 7 hole pattern ii.Eps depth depth thev200hastheisof05holepattern(1) and 2¼” x 2¼” hole pattern(2). 2.2.1 rotary actuator thevacv200hasaverystableandproperly sized drive shaft bearing. However, the posi- tioner drive(a) should be aligned properly to the...

  • Page 8: Www.Vac.Se

    Www.Vac.Se 92026r15 v200 positioner 8 r spl it ra ng e 90 ° d 0% 90°l in 10 0% 100% 180 °li n 50 % 0% r spl it ra ng e 90 ° d 0% 90°l in 10 0% 100% 180 °li n 50 % 0% r spl it ra ng e 90 ° d 0% 90°l in 10 0% 100% 180 °li n 50 % 0% sp lit ra ng e90 ° d r 0% 50% 180 °li n 100 % 10 0% 90 °lin 0% b sp li...

  • Page 9: V200 Positioner

    V200 positioner www.Vacaccessories.Com 92026r15 9 2.4 installation instructions for linear actuators 2.4.1 double acting 2.4.2 single acting direct (ccw) signal closes signal opens reverse (cw) spring opens spring closes direct (ccw) spring opens spring closes reverse (cw) signal opens signal closes...

  • Page 10: Www.Vac.Se

    Www.Vac.Se 92026r15 v200 positioner 10 r spl it ra ng e 90 ° d 0% 90°l in 10 0% 100% 180 °li n 50 % 0% 0% 9 sp lit r a ng e 90° d r 0% 50 % 180° lin 100 % 10 0% 90 °l in 0% b r sp li t ra n g e 90 ° d 0% 90° lin 10 0% 100 % 180 °li n 50 % 0% 2.5 cam the v200 is standard shipped with the c1-cam, fact...

  • Page 11: V200 Positioner

    V200 positioner www.Vacaccessories.Com 92026r15 11 2.6 spindle (drive) vacoffersavarietyofspindles/drives(1),suitable for the most frequently used actuator types. 2.6.1 spindle removal releasethespindle/drivebypryingwith two screwdrivers, equally under the edges(2) of thespindle/drive,usingthehousin...

  • Page 12: Www.Vac.Se

    Www.Vac.Se 92026r15 v200 positioner 12 2.7 installing ip converter 2.7.1 internal ip converter remove the front cover and indicator. (see page 15) 1. Loosen the two screws that secure the pneumatic sealing plate(1) and remove the plate. 2. Make sure the two o-rings(2) are still in the positioner hou...

  • Page 13: V200 Positioner

    V200 positioner www.Vacaccessories.Com 92026r15 13 2.8 4-20 ma connection 2.8.1 connecting the control signal remove the front cover and indicator. (see page 15) terminal block(1) is now easily acces- sible. Connect the cables to their respective pole. Maximum cable size awg 13 (2,5 mm 2 ) 2.8.2 che...

  • Page 14: Www.Vac.Se

    Www.Vac.Se 92026r15 v200 positioner 14 zerorange spri ng iii.Eps zero range iii.Eps 2.9 calibration the v200 is delivered factory calibrated 0-100 % ±1%. Calibration procedure zero position note:alwayssetzerofirst! 1. Set 0% input signal. 2.Waituntilthevalve/actuatorhasresponded. 3. Adjust the zero ...

  • Page 15: V200 Positioner

    V200 positioner www.Vacaccessories.Com 92026r15 15 2.10 front cover and indicator 2.10.1 removing the front cover loosen the two screws(1) and remove the front cover. 2.10.2 removing flat indicator cover with the main cover removed, the indicator cover(2) (clear cover) can be removed with pressure f...

  • Page 16: Www.Vac.Se

    Www.Vac.Se 92026r15 v200 positioner 16 2.10.5 installing flat indicator cover place the indicator cover(1) facing down to- ward the front cover. Press in the center of the indicator cover until it snaps into place. 2.10.6 installing dome indicator cover place the dome indicator cover(2) so that it i...

  • Page 17: V200 Positioner

    V200 positioner www.Vacaccessories.Com 92026r15 17 2.11 main supply filter for ip converter changing the filter 1. Turnoffordisconnectthemainairsupply. Should air supply not be disconnected or turnedoff,thepressuremaycausethe filtercovertoejectfromtheunit. 2. Loosenthescrew(1)andremovefilter cover(2...

  • Page 18: Www.Vac.Se

    Www.Vac.Se 92026r15 v200 positioner 18 max. 20° 2.12 pilot valve removal remove the front cover and indicator. (see p.15) loosen the pilot retaining screw(1). Lift the pilot valve(2) straight up. Cleaning remove the gold plated spool(3) from the valve housing clean the parts with a soft cloth and pi...

  • Page 19: V200 Positioner

    V200 positioner www.Vacaccessories.Com 92026r15 19 intentionally blank.

  • Page 20: Www.Vac.Se

    Www.Vac.Se 92026r15 v200 positioner 20 59 3. Spare parts 3.1 exploded drawing.

  • Page 21: V200 Positioner

    V200 positioner www.Vacaccessories.Com 92026r15 21 item description material part no qty 1 ......Housing ..................................Aluminum, painted ........N/a ................... 1 .......- bearing 15x8 ...............................................................171508 ............ 2 .....

  • Page 22: Www.Vac.Se

    Www.Vac.Se 92026r15 v200 positioner 22 4.1 specifications v200 pneumatic electropneumatic electropneumatic intrinsically safe v200p v200e v200is i nputsignal: 3-15psi 4-20ma(max:ri250ohm) 4-20ma(max:ri250ohm) supplypressure: 21.8-145psi(0.15-1mpa) 21.8-145psi (0.15-1mpa) linearityerror: hysteresis: ...

  • Page 23: V200 Positioner

    V200 positioner www.Vacaccessories.Com 92026r15 23 13/32 " 10 hex size 6 13/16" 173,4 4 3/4" 121 1 25/32" 45 1 25/32" 45 1 5/8" 41 3/16" 5 2 13/32" 61 2 11/16" 68 8 3/16" 208 gauges 1/8" npt(4x) (optional ) 1/2" 12, 5 25/32" 20 31/32" 25 1 7/8" 47, 5 conduit entr y 1/2" npt (2x) 1 19/32 " 40,5 7/8" ...

  • Page 24: Www.Vac.Se

    Www.Vac.Se 92026r15 v200 positioner 24.