1.1 Principle of Operation
TheV200incorporatestheforcebalance
principal of operation. The desired value, in
theformofpressure,affectsthemembrane(1)
with the force that is created and transferred to
the balance arm(2). The opposing force, which
represents the actual control value, is provided
by the feedback spring(5) and creating force in
the opposite direction on the balance arm(2).
The feedback spring, resting on the feedback
arm(3), is positioned by the shape and re-
sponse of the cam. The cam(4) is connected
to the cylinder’s (actuator) piston rod via the
drive.
The pilot valve(6) is connected to the balance
arm and follows the balance arm’s movement.
The system is stable when the gold plated
spool(7) is in the neutral position and the forces
thataffectthebalancearmisinequilibrium.
As soon as a signal change occurs or a change
inthepositionofthevalve/actuatorpackage
occurs, the “force balance” is also changed
and the spool responds. Air immediately begins
toflowintothepartoftheactuator(C+orC-)
which allows the feedback mechanism to return
the spool to the neutral position.
The system is self-stabilizing and searches for a
steady state position.
1.2 Product identification
TheV200identificationtags,Serialnumber
tag(1), product model tag(2) and feedback op-
tion tags(3), are placed as shown.
The product model tag contains information on
control signal, maximum working pressure and
temperature ranges. Other information can be
shown depending on the model.
1 INTRODUCTION
4
5
2
1
6
7
3