vacon 50x parameters
vacon
98
24-hour support +358 (0)40 837 1150 • Email: vacon@vacon.com
7
Parameter
Value
Explanation
Seq Appl
1 sec Base
Sets 1 second time increments
DI1 Configure
Seq1
Allows DI1 to end state 3
DO1 Configure
SeqOut-01
Allows DO1 to be active in state 2
Preset Speed 1
5 Hz
Speed for state 3
Preset Speed 6
50 Hz
Speed for state 1
Seq Cntl1
00010000110
No outputs/FWD/Timed/Primary Ramp/Preset Speed 6
Seq Count 1
3600
1 hour = 3600 seconds
Seq Cntl 2
01000001000
Enable Output/Stop/Timed/Alt Ramp/Speed Ignored
Seq Count 2
120
2 minutes = 120 seconds
Seq Cntl 3
00101100001
No outputs/REV/DI Value/Primary Ramp/Preset Speed 1
Seq Count 3
1
Seq1 active
Table 30:Required Parameter Settings for Sample Sequencer Program