Vacon nxsp User Manual

Other manuals for nxsp: User Manual
Manual is about: Frequency Converter

Summary of nxsp

  • Page 1

    User's manual nxs/p frequency converters l o n w o r k s ® o p t i o n b o a r d o p t - c 4 archived document.

  • Page 2

    Index 1. General ........................................................................................................................... 3 2. Lonworks option board technical data .................................................................... 4 2.1 general .....................................

  • Page 3

    General vacon • 3 24-hour service: +358-40-8371 150 • email: vacon@vacon.Com 1 1. General vacon nx frequency converters can be connected to the lonworks® network using a fieldbus board. The converter can then be controlled, monitored and programmed from the host system. The lonworks® board shall be ...

  • Page 4

    4 • vacon technical data tel: +358-201-2121 • fax: +358-201-212 205 2 2. Lonworks option board technical data 2.1 general lonworks connections interface pluggable connector (5 mm) channel type tp/ft-10 transfer cable twisted pair communications baud rate 78 kbit/s ambient operating temperature –10°c...

  • Page 5

    Technical data vacon • 5 24-hour service: +358-40-8371 150 • email: vacon@vacon.Com 2 2.2 physical media and wiring l on w orks networks can be implemented on many different physical media. Vacon opt- c4 option board is equipped with an ft-x1 transceiver supporting the free topology transformer coup...

  • Page 6

    6 • vacon technical data tel: +358-201-2121 • fax: +358-201-212 205 2 converters. Attention should be paid to proper grounding of the shield to ensure bus operation. Grounding of the shield should be done at both ends of the cable. Cable type max. Doubly terminated bus length max. Free topology wire...

  • Page 7

    Layout and connections vacon • 7 24-hour service: +358-40-8371 150 • email: vacon@vacon.Com 3 3. Lonworks fieldbus board layout and connections vacon lonworks fieldbus board is connected to the fieldbus through 3-pin pluggable bus connector. The communication with the control board takes place throu...

  • Page 8

    8 • vacon layout and connections tel: +358-201-2121 • fax: +358-201-212 205 3 3.2 grounding of bus cable shield in opt-c4 the bus cable shield can be grounded to the frame of the frequency converter through an rc filter located on the opt-c4 board. Note: normally, the option board has already been i...

  • Page 9

    Layout and connections vacon • 9 24-hour service: +358-40-8371 150 • email: vacon@vacon.Com 3 figure 3-4. 3 insert the data cables and the shield in their respective terminals. See table 3-1. Figure 3-5. 4 if the lonworks board was detached from the control unit place it into slot e of the control b...

  • Page 10

    10 • vacon layout and connections tel: +358-201-2121 • fax: +358-201-212 205 3 3.3 bus termination resistors to assure a proper data transmission, termination of the network segments is required. Depending on the type of network, either one or two terminations are necessary. Free topology network se...

  • Page 11

    Layout and connections vacon • 11 24-hour service: +358-40-8371 150 • email: vacon@vacon.Com 3 neuron status (h3) green led is: meaning: state code off configured 4 on applicationless and unconfigured 3 flashing unconfigured 2 board status led (h2) yellow led is: meaning: off option board not activa...

  • Page 12

    12 • vacon installation tel: +358-201-2121 • fax: +358-201-212 205 4 4. Installation of vacon nx lonworks board ! Note make sure that the frequency converter is switched off before an option or fieldbus board is changed or added! A vacon nx frequency converter b remove the cable cover. C open the co...

  • Page 13

    Installation vacon • 13 24-hour service: +358-40-8371 150 • email: vacon@vacon.Com 4 d install lonworks option board in slot e on the control board of the frequency converter. Make sure that the grounding plate (see below) fits tightly in the clamp. 21 22 23 h3 h2 h1 x5 lw1.Fh8 e make a sufficiently...

  • Page 14

    14 • vacon installation tel: +358-201-2121 • fax: +358-201-212 205 4 4.1 board information sticker the lonworks option board package delivered by the factory includes a sticker (shown below). Please mark the board type (1), the slot into which the board is mounted (2) and the mounting date (3) on th...

  • Page 15

    Commissioning vacon • 15 24-hour service: +358-40-8371 150 • email: vacon@vacon.Com 5 5. Commissioning read first chapter 8 'commissioning' in vacon nx user's manual (document nr. Ud00701, please visit http://www.Vacon.Com/support/documents.Html ). 5.1 fieldbus board parameters the vacon lonworks bo...

  • Page 16

    16 • vacon commissioning tel: +358-201-2121 • fax: +358-201-212 205 5 5.2 start-up test frequency converter application choose fieldbus (bus/comm) for the active control place (see vacon nx user's manual, chapter 7.3.3). Master software 1. Write 100.0 1 to nvidrvspeedstpt. 2. Frequency converter sta...

  • Page 17

    Lonworks interface vacon • 17 24-hour service: +358-40-8371 150 • email: vacon@vacon.Com 6 6. Lonworks interface features of the lonworks interface: • direct control of vacon nx (e.G. Run, stop, direction, speed reference, fault reset) • full access to all vacon nx parameters • monitor vacon nx stat...

  • Page 18

    18 • vacon lonworks interface tel: +358-201-2121 • fax: +358-201-212 205 6 variable speed motor drive: 6010 nv1 nvidrvspeedstpt snvt_switch nv4 nvodrvspeed snvt_levpercent mandatory network variables optional network variables nv2 nvidrvspeedscale snvt_lev_percent nv3 nvodrvcurnt snvt_amp nv8 nvirst...

  • Page 19

    Lonworks interface vacon • 19 24-hour service: +358-40-8371 150 • email: vacon@vacon.Com 6 6.2 input network variables function variable name snvt type min. Value max. Value node object request nvirequest snvt_obj_request driver speed setpoint nvidrvspeedstpt snvt_switch n/a n/a driver set point spe...

  • Page 20

    20 • vacon lonworks interface tel: +358-201-2121 • fax: +358-201-212 205 6 nvirstfault this input network variable provides a fault reset. Setting value 1 for state and a non-zero value for value will reset an active fault in vacon nx. Default value is 0; 0. State value command 0 any no action (0; 0...

  • Page 21

    Lonworks interface vacon • 21 24-hour service: +358-40-8371 150 • email: vacon@vacon.Com 6 nviparcmd this input network variable is used to read and write the parameters. The parameter addresses are determined in the application. Every parameter and actual value has been given an id number in the ap...

  • Page 22

    22 • vacon lonworks interface tel: +358-201-2121 • fax: +358-201-212 205 6 if the read command is successful then nvoparout value is - ln_recall 112 0 0 0 0 if the read command fails then nvoparout value is - ln_ ln_nul 112 0 0 0 0 6.3 output network variables function variable name snvt type min. M...

  • Page 23

    Lonworks interface vacon • 23 24-hour service: +358-40-8371 150 • email: vacon@vacon.Com 6 nvodrvspeed this output network variable provides the speed of the drive as a percentage of the nominal speed. Nvodrvcurnt this output network variable provides the drive output current in amperes. Nvodrvpwr t...

  • Page 24

    24 • vacon lonworks interface tel: +358-201-2121 • fax: +358-201-212 205 6 nvodigitalout1..8 these output network variables are sent directly from the application (see more detailed explanation in chapter 6.5 process data). State value command 0 0 off (0; 0) 1 200 (0xc8) on (200; 1) -1 (0xff) any in...

  • Page 25

    Lonworks interface vacon • 25 24-hour service: +358-40-8371 150 • email: vacon@vacon.Com 6 6.4 network configuration variables function variable name snvt type maximum motor speed ncimaxspeed scptmaxsetpoint minimum motor speed nciminspeed scptminsetpoint receive heartbeat time ncircvhrtbt scptmaxrc...

  • Page 26

    26 • vacon lonworks interface tel: +358-201-2121 • fax: +358-201-212 205 6 nciminouttime this configuration property defines the minimum period of automatic network variable tansmission. Ncinmlspeed this configuration property is used to provide the nominal speed of the motor in rpm. This value is n...

  • Page 27

    Lonworks interface vacon • 27 24-hour service: +358-40-8371 150 • email: vacon@vacon.Com 6 6.5 process data nvoprocessout1..8 nviprocessin1..8 fbprocessdatain1..8 fbprocessdataout1..8 nvidigitaln 1 bit 3 fbfixedcontrolword bit 4 bit 5 bit 6 bit 7 bit 10 bit 11 bit 12 nvidigitaln 2 nvidigitaln 3 nvid...

  • Page 28

    28 • vacon fault tracking tel: +358-201-2121 • fax: +358-201-212 205 6 7. Fault tracking the table below presents the faults related to the lonworks option board. For more information, see also vacon nx user's manual, chapter 9. The lonworks option board status leds are described in more detail in c...

  • Page 29

    Appendix vacon • 29 24-hour service: +358-40-8371 150 • email: vacon@vacon.Com 8 8. Appendix 1 process data out the nodes can read the frequency converter’s actual values using process data variables. Basic, standard, local/remote, multi-step, pid control and pump and fan control applications use pr...

  • Page 30

    30 • vacon appendix tel: +358-201-2121 • fax: +358-201-212 205 7 pid control and pump and fan control applications data value unit step process data in1 reference for pid controller % 0.01% process data in2 actual value 1 to pid controller % 0.01% process data in3 actual value 2 to pid controller % ...

  • Page 31

    Head office and production: vaasa vacon plc runsorintie 7 65380 vaasa firstname.Lastname@vacon.Com telephone: +358 (0)201 2121 fax: +358 (0)201 212 205 production: suzhou, china vacon suzhou drives co. Ltd. Building 13cd 428 xinglong street suchun industrial square suzhou 215126 telephone: +86 512 6...