Vega VEGACAP 65 Operating Instructions Manual

Manual is about: Transistor NPN/PNP, Contactless electronic switch

Summary of VEGACAP 65

  • Page 1

    Operating instructions vegacap 65 with contactless electronic switch.

  • Page 2: Contents

    Contents 1 about this document 1.1 function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 1.2 target group . . . . . . . . . . . . . . . . . . . . . . . . . . 4 1.3 symbolism used . . . . . . . . . . . . . . . . . . . . . . . 4 2 for your safety 2.1 authorised personnel . . . . . . . ....

  • Page 3

    8.2 disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 9 supplement 9.1 technical data. . . . . . . . . . . . . . . . . . . . . . . . . 28 9.2 dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 9.3 industrial property rights. . . . . . . . . . . . . . . . . . 35 v...

  • Page 4: 1 About This Document

    1 about this document 1.1 function this operating instructions manual has all the information you need for quick setup and safe operation. Please read this manual before you start setup. 1.2 target group this operating instructions manual is directed to trained, qualified personnel. The contents of t...

  • Page 5: 2 For Your Safety

    2 for your safety 2.1 authorised personnel all operations described in this operating instructions manual must be carried out only by trained specialist personnel authorised by the operator. For safety and warranty reasons, any internal work on the instruments must be carried out only by personnel a...

  • Page 6

    2.6 safety information for ex areas please note the ex-specific safety information for installation and operation in ex areas. These safety instructions are part of the operating instructions manual and come with the ex- approved instruments. 2.7 manufacturer declaration in conformity with din en 600...

  • Page 7

    L mount the instrument in such a position that the sensor cannot touch the vessel wall or vessel installations. Keep the influences of product movements in the vessel in mind. L the surface temperature on the housing must not exceed the ingnition temperature of the concerned explosive atmosphere this...

  • Page 8: 3 Product Description

    3 product description 3.1 configuration the scope of delivery encompasses: l vegacap 65 level sensor l documentation - this operating instructions manual - ex specific safety instructions (with ex versions), if necessary further certificates vegacap 65 consists of the following components: l housing co...

  • Page 9

    3.2 principle of operation vegacap 65 is a level sensor with capacitive electrode for level detection. Vegacap 65 is very rugged and maintenance-free and can be used in all areas of industrial process technology. Probes such as vegacap 65 can be used in solids and in non-conductive liquids. Typical ...

  • Page 10

    Vegacap 65 is a compact instrument, i.E. It can be operated without external evaluation system. The integrated electronics evaluates the level signal and outputs a switching signal. With this switching signal, a connected device can be operated directly (e.G. A warning system, a plc, a pump etc.). T...

  • Page 11: 4 Mounting

    4 mounting 4.1 general instructions in general, vegacap 65 can be mounted in any position. The instrument must be mounted in such a way that the probe is at the height of the requested switching point. With screwed versions, the housing must not be used for screwing in! Tightening can cause damages ...

  • Page 12

    4.2 mounting information agitators, equipment vibration, etc., can cause the level switch to be subjected to strong lateral forces. For this reason, do not use an overly long probe for vegacap 65, but check if you can mount a short level switch on the side of the vessel in horizontal position. If ve...

  • Page 13

    In silos with bulk solids, material cones can form which change the switching point. Please keep this in mind when installing the sensor in the vessel. We recommend selecting an installation location where the probe detects the average value of the material cone. The measuring probe must be mounted ...

  • Page 14

    D d 6 1 2 3 fig. 6: filling in the center, emptying laterally 1 vegacap 65 2 emptying opening 3 filling opening make sure that the max. Permissible tensile load of the suspension cable is not exceeded. The danger of this happening exists particularly with very heavy solids and large meas. Lengths. T...

  • Page 15

    5 connecting to power supply 5.1 preparing the connection always observe the following safety instructions: l connect only in the complete absence of line voltage connect the power supply acc. To the following diagrams. Oscillator cp60c is designed in protection class 1. To maintain this protection ...

  • Page 16

    7 press down the opening levers of the terminals, you will hear the terminal spring closing 8 check the hold of the wires in the terminals by lightly pulling on them 9 tighten the compression nut of the cable entry, the seal ring must completely encircle the cable 10 screw the housing cover back on ...

  • Page 17

    4 5 6 3 2 1 fig. 9: electronics and connection compartment 1 potentiometer for switching point adaptation 2 dil switch for measuring range selection 3 dil switch for mode adjustment 4 ground terminal 5 terminals 6 control lamp we recommend connecting vegacap 65 in such a way that the switching circu...

  • Page 18

    1 fig. 10: wiring plan 1 voltage supply 18 vegacap 65 - with contactless electronic switch connecting to power supply 30017 -en -060223.

  • Page 19: 6 Set Up

    6 set up 6.1 general the numbers in brackets refer to the following illustrations. On the electronics module you will find the following indicating and adjustment elements: l potentiometer for switching point adaptation l dil switch for measuring range selection l dil switch for mode adjustment - min...

  • Page 20

    The switching status of the electronics can be checked with closed housing (only plastic housing), see "function chart". Note: screw the housing cover tightly to the point where the inspection glass is above the control lamp (led). To adjust vegacap 65, first of all remove the housing cover. You can ...

  • Page 21

    Control lamp for indication of the switching condition. L green = switch closed l red = switch open l red (flashing) = failure the adjustment of the switching point is only possible in installed condition. The specifications in parenthesis refer to the above illustration. Vertically mounted probes 1 s...

  • Page 22

    Level switching sta- tus control lamp max. Mode overfill protection 2 1 switch closed green max. Mode overfill protection 2 1 switch open red min. Mode dry run protection 2 1 switch closed green min. Mode dry run protection 2 1 switch open red failure of the supply voltage (min./max. Mode) any 2 1 swi...

  • Page 23

    7 maintenance and fault rectification 7.1 maintenance when used as directed in normal operation, vegacap 65 is completely maintenance-free. 7.2 fault rectification vegacap 65 offers maximum reliability. Nevertheless faults can occur during operation. These may be caused by the following, e.G.: l sensor...

  • Page 24

    à check if there is buildup on the probe, and if so, remove it. L unfavourable installation location à mount the instrument at a location in the vessel where no dead zones or mounds can form. à check if the probe is covered by buildup on the socket. L wrong mode selected à set the correct mode on th...

  • Page 25

    2 1 fig. 12: loosen the screws 1 electronics module 2 screws (2 pcs.) 6 remove the old oscillator 7 compare the new oscillator with the old one. The type label of the oscillator must correspond to that of the old oscillator. This applies particularly to instruments used in hazardous areas. 8 compare...

  • Page 26

    7.4 instrument repair if a repair is necessary, please proceed as follows: from our homepage in the internet www.Vega.Com, you can download a return form (23 kb) under: “downloads – forms and certificates – repair form” by doing this you help us carry out the repair quickly and without having to call...

  • Page 27: 8 Dismounting

    8 dismounting 8.1 dismounting steps warning: before dismounting, be aware of dangerous process con- ditions such as e.G. Pressure in the vessel, high temperatures, corrosive or toxic products etc. Take note of chapters "mounting" and "connecting to power supply" and carry out the listed steps in rev...

  • Page 28: 9 Supplement

    9 supplement 9.1 technical data general data material 316l corresponds to 1.4404 or 1.4435 materials, wetted parts - process fitting - thread 316l - process fitting - flange 316l - process seal klingersil c-4400 - insulation (partly insulated) pa, ptfe - probe (cable ptfe partly insulated ø 6 mm/ø 0.2...

  • Page 29

    Output variable output contactless electronic switch modes (adjustable) min./max. Integration time - when immersed approx. 0.7 s - when laid bare approx. 0.7 s - in case of failure approx. 1 s ambient conditions ambient temperature on the housing -40 … +80°c (-40 … +176°f) storage and transport temp...

  • Page 30

    Electromechanical data cable entry/plug (dependent on the version) - single chamber housing l 1x cable entry m20x1.5 (cable-ø5 … 9 mm), 1x blind stopper m20x1.5, attached 1x cable entry m20x1.5 or: l 1x cable entry ½ npt, 1x blind stopper ½ npt, 1x cable entry ½ npt or: l 1x plug m12x1, 1x blind sto...

  • Page 31

    Overfill protection acc. To whg ship approvals supplement vegacap 65 - with contactless electronic switch 31 30017 -en -060223.

  • Page 32

    9.2 dimensions vegacap 65 4) ø77mm (3 1 / 32 ") 112mm (4 13 / 32 ") 69mm (2 23 / 32 ") ø77mm (3 1 / 32 ") 69mm (2 23 / 32 ") 117mm (4 39 / 64 ") 116mm (4 9 / 16 ") ø84mm (3 5 / 16 ") 116mm (4 9 / 16 ") m20x1,5 m20x1,5/ ½ npt m20x1,5/ ½ npt m20x1,5/ ½ npt 1 2 3 fig. 14: housing versions 1 plastic hou...

  • Page 33

    142mm (5 19 / 32 ") 200mm (7 7 / 8 ") ø6mm ( 15 / 64 ") l g 1 a, g 1 1 / 2 a 56 mm (2 1 / 4 ") 22mm (2 1 / 4 ") ø30 (1 3 / 16 ") fig. 15: vegacap 65 - threaded version g1 a l = sensor length, see "technical data" supplement vegacap 65 - with contactless electronic switch 33 30017 -en -060223.

  • Page 34

    73mm (2 7 / 8 ") ø 40mm (1 37 / 64 ") fig. 16: temperature adapter supplement 34 vegacap 65 - with contactless electronic switch 30017 -en -060223.

  • Page 35

    9.3 industrial property rights vega product lines are global protected by industrial property rights. Further information see http://www.Vega.Com. Only in u.S.A.: further information see patent label at the sensor housing. Vega produktfamilien sind weltweit geschützt durch gewerbliche schutzrechte. ...

  • Page 36

    Vega grieshaber kg am hohenstein 113 77761 schiltach germany phone +49 7836 50-0 fax +49 7836 50-201 e-mail: info@de.Vega.Com www.Vega.Com iso 9001 all statements concerning scope of delivery, application, practical use and operating conditions of the sensors and processing systems correspond to the...